516 Severn Way - Permit#96411 Wall AssemblyNom Pipe Diam In. (mm) Wall Assembly Rating Hr Closed (c) or Vented (v) T Rating Hr 1/2 to 3 (13 to 76) 1 c 1 1/2 to 1 -1/4 (13 to 32) 1 v 1 1/2 to 1-1/4 (13 to 32) 2 c 2 1/2 to 1 -1/4 (13 to 32) 2 v 1 2(51) 1 v 0 2(51) 2 v 0 i gkk n,i . 9 o�I /I 5/c sviv it* iy 1. Wall Assembly —The 1 or 2 hr fire rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300, U400 or V400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features: A. Studs — Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 in. by 4 in. (51 mm by 102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 3 -1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC. B. Gypsum Board* — Thickness, type, number of layers and fasteners as required in the individual Wall and Partition Design. Diam of opening shall be 7/8 in. (22 mm) larger than the outside diam of nonmetallic pipe or conduit (Item 2). The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed. 2. Through Penetrants — One nonmetallic pipe or conduit to be installed either concentrically or eccentrically within the firestop system. The annular space for max 1 -1/4 in. (32 mm) diam pipe or conduit shall be min 0 in. (point contact) to max 7/8 in. (0 mm to max 22 mm). The annular space for pipe or conduit larger than nom 1 -1/4 in. (32 mm). diam shall be min 1/2 in. to max 1 in. (13 mm to max 25 mm). Pipe or conduit to be rigidly supported on both sides of wall assembly. The following types and sizes of nonmetallic pipes or conduits may be used: A. Polyvinyl Chloride (PVC) Pipe — Nom 2 in. (51 mm) diam (or smaller) Schedule 40 solid core or cellular core PVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping system. B. Polyvinyl Chloride (PVC) Pipe — Nom 3 in. (76 mm) diam (or smaller) Schedule 40 solid core PVC pipe for use in closed (process or supply) piping system. C. Chlorinated Polyvinyl Chloride (CPVC) Pipe — Nom 3 in. (76 mm) diam (or smaller) SDR 11 CPVC pipe for use in closed (process or supply) piping systems. D. Rigid Nonmetallic Conduit++ — Nom 3 in. (76 mm) diam (or smaller) Schedule 40 PVC conduit installed in accordance with Article 347 of the National Electrical Code (NFPA No 70). E. Electrical Nonmetallic Tubing (ENT)-H- — Nom 1 in. (25 mm) diam (or smaller) ENT formed of PVC, installed in accordance with Article 331 of the National Electrical Code (NFPA No. 70). See Rigid Nonmetallic Conduit (DZKT) and Electrical Nonmetallic Tubing (FKHU) categories in the UL Electrical Construction Equipment Directory for names of manufacturers. F. Acrylonitrile Butadiene Styrene (ABS) Pipe — Nom. 2 in. (51 mm) diam (or smaller) Schedule 40 solid core or cellular core ABS pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. The hourly T Rating is dependent on the hourly rating of the wall assembly, the pipe or conduit size and whether the pipe is intended for use as a closed or vented system, as shown in the following table. ire Protection Z. �..... /S:se.,... roduc System No. W L -2088 May 23, 2005 F Ratings —1 and 2 Hr (See Item 1) T Ratings — 0, 1 and 2 Hr (See Item 2) ti SECTION A -A 0 N C 3 3. Fill, Void or Cavity Materials* — Caulk, Sealant or Putty — Min thickness of 5/8 in. and 1-1/4 in. (16 mm and 32 mm) of caulk or putty for 1 and 2 hr rated wall assemblies, respectively, applied within annulus between pipe or conduit and periphery of the opening, flush with both surfaces of wall assembly. At the point contact location between pipe or conduit and gypsum board, a min 1/2 in. (13 mm) diam bead of caulk or putty shall be applied at the pipe or conduit/wallboard interface on both surfaces of wall assembly. 3M COMPANY — CP 25WB+, IC 15WB+ caulk, FB -3000 WT sealant or MP+ Stix putty (Note: CP 25WB+ not suitable for use with CPVC pipes.) +++Bearing the UL Listing Mark. *Bearing the UL Classification Marking Reprinted from the Online Certifications Directory with permission from Underwriters Laboratories Inc. Copyright © 2010 Underwriters Laboratories Inc.® Note: Systems with Nonmetallic Through Penetrant(s) have not been evaluated with a pressure differential of 50 Pa between the exposed and unexposed surfaces as required by the National Building Code of Canada. System No. W L -2088 continued 'ire protection Product Zxt in-. 14irecinw woof W- 1 -9nRR • 9 nf 9 c -L us