990 Apollo Rd - Test & Balance Report990 AT
BSOLU7E
EC HAN !CAL.
C ontractors
Test and Balance Report
Questar
Eagan MN
Tested By
Rick Kessel
Date Tested
February 16, 2011
the
Questar
Eagan MN
February 16, 2011
Air Handling Unit Test
1
Unit
Manufacture
Model
Total CFM
Fan RPM
Motor RPM
Motor Volts
Motor Amps
Horsepower
O.A. Damper CFM
# 1 Office
Lennox
KGA036S4D
1,200
120
Unit
Manufacture
Model
Total CFM
Fan RPM
Motor RPM
Motor Volts
Motor Amps
Horsepower
O.A. Damper CFM
#2 Breakroom
Lennox
KGA036S4D
1,200
120
AREA
SERVED
Outlet
Number
Diffuser
TYPE
Neck
SIZE
DESIGN
CFM
Actual
CFM
Percent of
Required
101
1
Lay -in
10
275
263
96%
101
2
Lay -in
10
275
270
98%
103
1
Lay -in
8
150
245
163%
104
1
Lay -in
8
100
100
100%
105
1
Lay -in
8
100
95
95%
106
1
Lay -in
Lay -in
8
8
150
150
145
140
97%
93%
107
1
Totals
1200
1258
105%
Questar
Eagan MN
February 16, 2011
Unit Number: # 1 Office
Unit Manufacture: Lennox
Unit Model: KGA036S4D
REMARKS: Outside air set for 10 %, 120 cfm nominal
AREA
SERVED
Outlet
Number
Diffuser
TYPE
Neck
SIZE
DESIGN
CFM
Actual
CFM
Percent of
Required
120
1
Lay -in
10
300
290
97%
120
2
Lay -in
10
300
290
97%
120
3
Lay -in
10
300
285
95%
120
4
Lay -in
10
300
295
98%
Totals
1200
1160
97%
Questar
Eagan MN
February 16, 2011
Unit Number: #2 Breakroom
Unit Manufacture: Lennox
Unit Model: KGA036S4D
REMARKS: Outside air set for 10 %, 120 cfm nominal