920 Apollo Rd - Steel Parts Dist Permit EA098147' 5 ( f 1.6 1 5Et L ?k r°S P(''Tet OTC e,-; '1Z.b AP) L&-6 lab ,
151-64 PtP.M t 1,0(4
ERECTA -RAK
5209 W 65 St. Bedford Park IL 60638
(630) 253 -2773 phone (708) 924 -9610 fax
To whom it may concern.
Regarding pallet rack anchoring the following applies to non seismic areas:
1) 1/2" x 3 %" — 4 %z" recommended anchors (0.5" x 2.75" embed)
2) Frames sizes 12' -18' tall (minimum 2 spacers per frame line)
Frames sizes 18' -26' tall (minimum 3 spacers per frame line)
April 15, 2011
3) Each base plate of rack frames requires (1) anchor per post on all aisle ends, (1) anchor
per frame on back to back rows that follows the above mentioned spacer requirements
not to exceed 10 consecutive frame lines. For single row ALL posts MUST have (1)
anchor. NO torque testing required on anchors, NO special inspection required.
Additional requirements for 1 -4 seismic areas including stamped engineered plans with Design
Data and Definition of Components, Seismic Loads, Bracing, Base Plates, Slab on Grade.
Frank Gonzales
Premier Rack Installers
Bedford Park IL