3200 Riverview Ave - Energy Compliance Forms
II
New Construction Energy Code Compliance Certificate
Per N1101.8 Building Certificate. A building certificate shall be posted in a permanently visible location inside the Date Certificate Posted
building. The certificate shall be completed by the builder and shall list information and values of components
listed in Table 8.
Ma ~ f
iling Address ofthe oflheDwellingorDweWngUnit CW V MECHANICAL
Riverview Avenue Eagan
.320,0 Name of Residential Contractor MN License Number
Superior Companies of Minnesota Inc MB4551
THERMAL ENVELOPE RADON SYSTEM
Type: Check All That Apply X Passive (No Fan )
o
N C
T Active (With fan and monometer or
F other system monitoring device)
td ~ 'o 0
u. s: a
y a o b V p c,
? d PO GC ~ a T
> c i; q c o w c
Insulation Location g z e 7
%g o` on oo U O
"R 1~
° r .5 Z w w w° w° Other Please Describe Here
Below Entire Slab X
Foundation Wall 10 X Type in location: interior exterior or integral
Perimeter of Slab on Grade 10 X
Rini Joist (Foundation)
19 X Type in location: interior exterior or integral
Rim Joist (1 u Floor+) 19 X Type in location: interior exterior or integral
wall 23 X
Ceiling, flat 49 X
Ceiling, vaulted X
Bay Windows or cantilevered areas 56.5 X X
Bonus room over garage 56.5 X X
Describe other insulated areas
Windows & Doors eating or Cooling Ducts Outside Conditioned Spaces
Average U-Factor (excludes skylights and one door) U: 0.30 Not applicable, all ducts located in conditioned space
Solar Heat Gain Coefficient (SHGC): 0.33 R-value
MECHANICAL SYSTEMS Make-up Air Select aType
Appliances Heating System Domestic Water Heater Cooling System X Not required per mech. code
Fuel Type NG NG Electric Passive
Manufacturer Carrier AO Smith Carrier Powered
Interlocked with exhaust device.
Model 59TP5A040E14 GPD-40 24ACB31 BA30 Describe:
Input in 40,000 Capacity in 40 Output in 1.5 Other, describe:
Rating or Size BTUS: Gallons: Tons:
Heat Loss: 22,714 Heat Gain: 9,138 Location of duct or system:
Structure's Calculated
AFUE or 96.5 SEER: 15.5
HSPF°n
Calculated 9,138
Efficiency I>< cooling load: Cfm's
" round duct OR
Mechanical Ventilation System " metal duct
Describe any additional or combined heating or cooling systems if installed: (e.g. two furnaces or air Combustion Air Select a Type
source heat pump with gas back-up furnace): Not required per mech. code
Select Type X Passive
f eat Recover Ventilator (HRV) Capacity in cfms: Low: High: Other, describe:
nergy Recover Ventilator (ERV) Capacity in cfms: Low: High: Location of duct or system:
ontinuous exhausting fan(s) rated capacity in cfins:
Location offan(s), describe: Cfm's
Capacity continuous ventilation rate in cfms: 44 6 "round dLLJ
Total ventilation (intermittent + continuous) rate in cfrns: 87 " metal d
Date: 7/1/2013 Revision Date: 7/1/2033 New Construction
Site Information
Address 1: Type A Unit Project
Address 2: 32W J ti'A-v ~az AUeTb- Lot: Block:
City: Eagan County: Subdivision:
Application Information
Business Name: Superior Mechanical MN Contractor License
Contact Person: Rob Jones
Office Ph: 507-289-0229 . Fax: 607-281-9807 Cell Ph:
Address 1: 1244 60th Avenue NW
City: Rochester State: MN Zip Code: 55901
House Details
Square Feet: 1363 sq. ft. Avg. Ceiling Ht: 8 ft. Number of Bedrooms: 3
Ventilation : Exhaust
Total Ventilation Capacity : 60 cfm.
Minimum Continuous Ventilation :60cfm.
Ventilation: Exhaust: 60 cfm.
Combustion Appliance
Water Heater. Power Vent Input BTUs: 40,000 Independently Vented
Furnace/Boiler: Direct Vent/Sealed Combustion Input BTUs: 40,000 Independently Vented
Other Combustion Appliances
Gas Fired Direct Vent Fireplace(s): No Gas Fired Power Vent Fireplace(s): No
Gas Fired Natural Draft Fireplace(s): No Solid Fuel Appliance(s): No
Exhaust Equipment
Exhaust Ventilation Capacity (cfm): 60 Clothes Dryer (cfm): 135
Exhaust Fan Rating (cfm): 175
Make-Up Air
Total Make-Up Air Required (cfm): 131
Passive Make-Up, Round Rigid: 6 inches or Insulated Flex: 7 inches
Combustion Air
Round Rigid Required: 4 inches or Insulated Flex: 5 inches
,tSc~t/~.J 1G/jL ~Zoopr\ 61 ZG : 7 K. 13 x $ ; 7Z8 F-3
Applicant Name (print): Signature/Date: G` 9- -13
Code Official (print): Signature/Date:
0 2004 CenterPoint Energy Minnegasco. 2004 Mechanical Code Guidelines. Page l
2009 Mechanical & Energy Code - Ventilation, Makeup, and Combustion Air Calculations
Please submit at time of application of a mechanical permit for new construction
Site address 32oo vuvi venub Date 9
HVAC lAPUbDP -jAA4I6S a MlrndESarA vPompleted C_JDnel
Contractor By
Section A
Ventilation Quantity
(Determine quantity by using Table N1104.2 or Equation 11-1)
Square feet (Conditioned area including 2 f~
Basement - finished or unfinished) 13 Total required ventilation ,87
Number of bedrooms 3 Continuous ventilation y U
Section B
Ventilation Method
(Choose either balanced or exhaust only)
0 Balanced, HRV (Heat Recovery Ventilator) or ERV (Energy [K Exhaust only
Recovery Ventilator) - cfm of unit in low must not exceed Continuous fan rating cfm
continuous ventilation rating by more than 100%.
Low cfm: High dm: Continuous fan rating in cfm (capacity must not exceed ff'',,(
continuous ventilation rating by more than 100%
Section C
Ventilation Fan Schedule
Description Location Continuous Total Ventilation
Dt rVOSV,KS3 P6L LWL Wt-IEMV, 44
W 5VK a D 50
D 175
Section D
Controls
Describe operation and control of the continuous ventilation)
D l T
Section E
Make-up air for ventilation
Passive (determined from calculations from Table 501.4.1)
Powered (determined from calculations from Table 501.4.1)
Interlocked with exhaust device (determined from calculation from Table 501.4. 1)
A
Other, describe: NIA
Location of duct or system ventilation make-up air, Determined from make-up air opening table
Cfm 115 Size and type (round, rectangular, flex or rigid)
Section F
Make-up air for combustion
Not required per mechanical code (No atmospheric or power vented appliances)
Passive (see IFGC Appendix E, Worksheet E-1) Size and type D
Other, describe:
Notes: instructions and example forms are available at the Building Safety website and at the Building Safety office. This form must be
submitted at the time of application of a mechanical permit for new construction. Additional forms may be downloaded and printed at:
f
River Ridge Town Home Unit A
HVAC Load Calculations
for
Superior Mechanical
1244 60th Ave NW
Rochester, MN 55901
- ,
BF,
R".-Vri` A HVI ACLOADS.
Prepared By:
Monday, September 09, 2093
r
Rhvac - Residential & Light Commercial HVAC Loads Elite Software Development, Inc. i
Minnesota Air River Ridge Town Home Unit A
ha
Bloomington_ MN 55438 e 2
Project Report
General Proiect Information
Project Title: River Ridge Town Home Unit A
Project Date: Tuesday, July 02, 2013
Client Name: Superior Mechanical
Client Address: 1244 60th Ave NW
Client City: Rochester, MN 55901
Design Data
Reference City: Minneapolis, Minnesota
Daily Temperature Range: Medium
Latitude: 44 Degrees
Elevation: 834 ft.
Altitude Factor: 0.970
Elevation Sensible Adj. Factor: 1.000
Elevation Total Adj. Factor: 1.000
Elevation Heating Adj. Factor: 1.000
Elevation Heating Adj. Factor: 1.000
Outdoor Outdoor Indoor Indoor Grains
Dry -Bulb Wet Bu Rel.Hum Drv Bulb Difference
Winter: -20 0 30 72 34
Summer: 92 73 50 72 35
1 Check Figures
Total Building Supply CFM: 382 CFM Per Square ft.. 0.280
Square ft. of Room Area: 1,364 Square ft. Per Ton: 1,505
Volume (ft') of Cond. Space: 11,383 Air Turnover Rate (per hour): 2.0
[Building Loads
Total Heating Required With Outside Air: 22,714 Btuh 22.714 MBH
Total Sensible Gain: 8,157 Btuh 89 %
Total Latent Gain: 981 Btuh 11 %
Total Cooling Required With Outside Air: 9,138 Btuh 0.76 Tons (Based On Sensible + Latent)
0.91 Tons (Based On 75% Sensible Capacity)
Notes .
Calculations are based on 8th edition of ACCA Manual J.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads.
1
C:\Users\Chad.MNAIR\Desktop\Office Doc\Sales\River Ridge Unit A.rhv Monday, September 09, 2013, 11:55 AM
Rhvac - Residential & Light Commercial HVAC Loads Elite Software Development, Inc.
Minnesota Air River Ridge Town Home Unit A 1
I Bloomington MN 55438 Page 3
i Miscellaneous Report
System 1 Outdoor Outdoor Indoor Indoor Grains
Input Data D Bulb Wet Bulb Rel.Hum D Bulb Difference
Winter: -20 0 30 72 34.40
Summer: 92 73 50 72 35.16
Duct Sizing Inputs
Main Trunk R no #
Calculate: Yes Yes
Use Schedule: Yes Yes
Roughness Factor: 0.00300 0.01000
Pressure Drop: 0.1000 in.wg./100 ft. 0.1000 in.wg./100 ft.
Minimum Velocity: 650 ft./min 450 ft./min
Maximum Velocity: 900 ft./min 750 ft./min
Minimum Height: 0 in. 0 in.
Maximum Height: 0 in. 0 in.
Outside Air Data
Winter Summer
Infiltration: 0.430 AC/hr 0.230 AC/hr
Above Grade Volume: X 11.038 Cu.ft. X 11.038 Cu.ft.
4,746 Cu.ft./hr 2,539 Cu.ft./hr
X 0.0167 X 0.0167
Total Building Infiltration: 79 CFM 42 CFM
Total Building Ventilation: 0 CFM 0 CFM
---System 1---
Infiltration & Ventilation Sensible Gain Multiplier: 21.35 = (1.10 X 0.970 X 20.00 Summer Temp. Difference)
Infiltration & Ventilation Latent Gain Multiplier: 23.19 = (0.68 X 0.970 X 35.16 Grains Difference)
Infiltration & Ventilation Sensible Loss Multiplier: 98.19 = (1.10 X 0.970 X 92.00 Winter Temp. Difference)
C:\Users\Chad.MNAIR\Desktop\Office Doc\Sales\River Ridge Unit A.rhv Monday, September 09, 2013, 11:55 AM
Rhvac - Residential & Light Commercial HVAC Loads Elite Software Development, Inc.'
Minnesota Air River Ridge Town Home Unit A=
Bloomington MN 55438 Page 4
Load Preview Report
Has: . Net Rec' ft Zi Sen' Lat Net Sen Sys; Sys Sys Duct
Htg Gig; Act
Scope AED _ Ton Ton. /Ton ; Area Gain ; Gain' Gain' Loss
CFM CFM CFM Sz
.
Building 0.76 0.91 1,505 1,364 8,157 981 9,138 22,714 304 382 382
System 1 Yes 0.76 0.91 1,505 1,364 8,157 981 9,138 22,714 304 382 382 9x9
Zone 1 1,364 8,157 981 9,138 22,714 304 382 382 9x9
1-Basement 104 655 206 861 5,392 72 31 31 1-4
2-Main Floor 630 3,535 399 3,934 8,797 118 186 166 2-5
3-2nd Floor 630 3,967 376 4,343 8,525 114 186 186 2-6
C:\Users\Chad.MNAIR\Desktop\Office Doc\Sales\River Ridge Unit A.rhv Monday, September 09, 2013, 11:55 AM
Rhvac - Residential & Light Commercial HVAC Loads Elite Software Development, Inc.
Minnesota Air River Ridge Town Home Unit A
Bloomin ton MN 55438 paw-5
Total Building Summa Loads
Component Area Sen Lat Sen Total
Description. Quan Loss Gain Gain Gain
Dbl Pane Low e: Glazing-Double Pane Operable Window 172.5 4,761 0 4,914 4,914
Low e, u-value 0.3, SHGC 0.33
11 P: Door-Metal - Polyurethane Core 42 1,120 0 378 378
15A-10sffc-8: Wall-Basement, concrete block wall, R-10 123.5 537 0 26 26
foam board to floor, no framing, no interior finish,
filled core, 8' floor depth
R-23 wall: Wall-frame, , R-23 insulated wall 1237.2 4,939 0 1,090 1,090
15a-1-sffc-8: Wall- 76 421 0 22 22
Under Attic w/ R-49: Roof/Ceiling-Under Attic with 630 1,159 0 693 693
Insulation on Attic Floor (also use for Knee Walls and
Partition Ceilings), Custom, Vented Attic, Dark
Asphalt Shingles
21A-20: Floor-Basement, Concrete slab, any thickness, 2 104 258 0 0 0
or more feet below grade, no insulation below floor,
any floor cover, shortest side of floor slab is 20' wide
22D-10pm: floor-Slab on grade, Vertical board insulation 30 947 0 0 0
covers slab edge, turns under slab and extends 4'
horizontally, any floor cover, R-10 insulation, passive,
heavy dry or light wet soil
R-56.5: Floor-Over open crawl space or garage, Custom, 486 805 0 131 131
R-56.5 Over Open Crawl or Garage Floor
Subtotals for structure: 14,947 0 7,254 7,254
People: 0 0 0 0
Equipment: 0 0 0
Lighting: 0 0 0
Ductwork: 0 0 0 0
Infiltration: Winter CFM: 79, Summer CFM: 42 7,767 981 903 1,884
Ventilation:-Winter CFM:_ 0,_Summer_CFM._0 - - --.-_....-0-- - - p ------0-
Total Building Load Totals: 22,714 981 8,157 9,138
Check Figures
Total Building Supply CFM: 382 CFM Per Square ft.: 0.280 I
Square ft. of Room Area: 1,364 Square ft. Per Ton: 1,505
Volume (ft') of Cond. Space: 11,383 Air Turnover Rate (per hour): 2.0
building , Loads
Total Heating Required With Outside Air: 22,714 Btuh 22.714 MBH
Total Sensible Gain: 8,157 Btuh 89 %
Total Latent Gain: 981 Btuh 11 %
Total Cooling Required With Outside Air: 9,138 Btuh 0.76 Tons (Based On Sensible + Latent)
0.91 Tons (Based On 75% Sensible Capacity)
Notes
Calculations are based on 8th edition of ACCA Manual J.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads.
I
C:\Users\Chad.MNAIR\Desktop\Office Doc\Sales\River Ridge Unit A.rhv Monday, September 09, 2013,11:55 AM
Rhvac - Residential & Light Commercial HVAC Loads Elite Software Development, Inc.
Minnesota Air River Ridge Town Home Unit A
6
Bloomington, MN 55438 Page,
S stem 7 Room Load Summa
Htg Min Run Run Cig Cig Min Act
Room Area Sens Htg Duct Duct Sens Lat Clg Sys I
No Name SF Btuh CFM Size Vel Btuh Btuh CFM CFM I
---Zone 1---
1 Basement 104 5,392 72 1-4 352 655 206 31 31
1 2 Main Floor 630 8,797 118 2-5 607 3,535 399 166 166
3 2nd Floor 630. 8,525 - - 114 2-6 .473 3,967... -3~6 - 186 186_
-
System 1 total 1,364 22,714 304 8,157 981 382 382
System 1 Main Trunk Size: 9x9 in.
Velocity: 679 ft./min
Loss per 100 ft.: 0.117 in.wg
Coolie System Summary,
Cooling Sensible/Latent -Sensible Latent Total
Tons Split:- Btuh Btuh Btuh
Net Required: 0.76 89%/11% 8,157 981 9,138
Recommended: 0.91 75%/25% 8,157 2,719 10,876
`Equipment Data
Heating System Cooling System
Type:
Model:
Brand:
Efficiency:
Sound:
Capacity:
Sensible Capacity: n/a 0 Btuh
Latent Capacity: n/a 0 Btuh
C:\Users\Chad.MNAIR\Desktop\Office Doc\Sales\River Ridge Unit A.rhv Monday, September 09, 2013, 11:55 AM