3184 Riverview Ave - Energy Compliance Forms
New Construction Energy Code Compliance Certificate
Per N1101.8 Building Certificate. A building certificate shall be posted in a permanently visible location inside the Date Certlileate Posted
building. The certificate shall be completed by the builder and shall list information and values of componentsy
listed in Table N l 101.8. SUPERIOR
Mailing Address of the Dwelling or Dwelling Unit City Riverview Avenue Ea an %Name of Residential Contractor - MN License Nnrnher
,Superior Companies of Minnesota Inc MB4551
THERMAL ENVELOPE RADON SYSTEM
Type: Check All That Apply X Passive (No Fan )
o °
~ c
o Active (With fan and manometer or
Ey a other system monitoring device)
0 a ~ 2 U , o b
frs v U "e b
15
Insulation Location ° z v " w
a 7 ° to
E ti o
H a z w w Outer Please Describe Here
Below Entire Slab X
Foundation Wail 10 X Type in location: interior exterior or integral
Perimeter of Slab on Grade 10 X
Rim Joist (Foundation) 19 X Type in location: interior exterior or integral
Rim Joist (1st Floor) 19 X Type in location: interior exterior or integral
Wall 23 X
Ceiling, flat 49 X
Ceiling, vaulted X
Bay Windows or cantilevered areas 56.5 X X
Bonus room over garage 56.5 X X
Describe other insulated areas
Windows & Doors Heating or Cooling Ducts Outside Conditioned Spaces
Average U-Factor (excludes skylights and one door U: 0.30 Not applicable, all ducts located in conditioned space
Solar Heat Gain Coefficient (SHGC): 0.33 R-value
MECHANICAL SYSTEMS Make-up Air Selecta Type
Appliances Heating System Domestic Water Heater Cooling System X Not required per mech. code
Fuel Type NG NG Electric Passive
Manufacturer Carrier AO Smith Carrier Powered
Interlocked with exhaust device.
Model 59TP5A040E14 GPD-40 24ACB318A30 Describe:
Input in 40,000 Capacity in 40 Output in 1.5 Other, describe:
Rating or Size BTUS: Gallons: Tons:
Heat Loss: 18,380 Heat Gain: 5,630 Location of duct or system:
Structure's Calculated
AFUE or 96.5 SEER: 15.5
HSPFa/o
Calculated 5,630
Efficient cooling load: Cm's round duct OR
Mechanical Ventilation System " metal duct
Describe any additional or combined heating or cooling systems if installed: (e.g. two furnaces or air Combustion Air Select a type
source heat pump with gas back-up furnace): Not required per mech. code
Select T}pe X Passive
Heat Recover Ventilator (HRV) Capacity in cfins: Low: High: Other, describe:
Energy Recover Ventilator (ERV) Capacity nr cfins: Low: Hi Location of duct or system:
Continuous exhausting fan(s) rated capacity in cf ms:
Location of fan(s), describe: Cfm's
Capacity continuous ventilation rate in cfms: 44 6 " round duct OR
Total ventilation (intermittent + continuous) rate in cfms: 87 .metal duct
Date: 7/112013 Revision Date: 7/1/2013 New Construction
Site Information
Address 1: Type B Unit Project
Address 2: i,IVef'Vid.L0 A~jenu~ Lot: Block:
City: Eagan County: Subdivision:
Application Information
Business Name: Superior Mechanical MN Contractor License
Contact Person: Rob Jones
Office Ph: 507-289-0229 Fax: 507-281-9807 Cell Ph:
Address 1: 1244 60th Avenue NW
City. Rochester State: MN Zip Code: 55901
House Details
Square Feet: 1200 sq. ft. Avg. Ceiling Ht: 8 ft. Number of Bedrooms: 2
Ventilation : Exhaust
Total Ventilation Capacity : 45 cfm.
Minimum Continuous Ventilation :45cfm.
Ventilation: Exhaust: 45 cfm.
Combustion Appliance
Water Heater: Power Vent Input BTUs: 40,000 Independently Vented
Furnace/Boiler: Direct Vent/Sealed Combustion Input BTUs: 40,000 independently Vented
Other Combustion Appliances
Gas Fired Direct Vent Fireplace(s): No Gas Fired Power Vent Fireplace(s): No
Gas Fired Natural Draft Fireplace(s): No Solid Fuel Appliance(s): No
Exhaust Equipment
Exhaust Ventilation Capacity (cfm): 45 Clothes Dryer (cfm): 135
Exhaust Fan Rating (cfm): 175
Make-Up Air
Total Make-Up Air Required (cfm): 140
Passive Make-Up, Round Rigid: 6 inches or Insulated Flex: 7 inches
Combustion Air
Round Rigid Required: 4 inches or Insulated Flex: 5 inches
metcfmf. ICIi t- Y-2> $9ie F-13
Applicant Name (print):S,Ipi~2razMP-►nr mgL-,fi? sSignature/Date:
Code Official (print): Signature/Date.
0 2004 CenterPoint Energy Minnegasco. 2004 Mechanical Code Guidelines. Page I
2009 Mechanical & Energy Code - Ventilation, Makeup, and Combustion Air Calculations
Please submit at time of application of a mechanical permit for new construction
Site address Date
HVAC U?Sj4D9. COMPAt4I M K MrrtrbES,5-rA C mpieted „h
Contractor By
Section A
Ventilation Quantity
(Determine quantity by using Table N1104.2 or Equation 11-1)
Square feet (Conditioned area including ~f ,ter, 1 ~S
Basement - finished or unfinished) 12.DO Total required ventilation t0 _I
Number of bedrooms Continuous ventilation 35
Section B
Ventilation Method
(Choose either balanced or exhaust only)
Balanced, HRV (Heat Recovery Ventilator) or ERV (Energy Z Exhaust only
Recovery Ventilator) - cfm of unit in low must not exceed Continuous fan rating cfm
continuous ventilation ratio b more than 100°/x.
Low cfm: I I High cfm: Continuous fan rating in cfm (capacity must not exceed
continuous ventilation ratio by more than 100%) ~s
Section C
Ventilation Fan Schedule
Description Location Continuous Total Ventilation
# n -so
P" v 1o IG T ErJ
Section D
Controls
Describe operation and control of the continuous ventilation),
INna,aat., WN-n(ivtou ViNTILATI tJ CDNT2DL
WALL 3wii-c.A POLL MWMu V9M t Arlo T
Section E
Make-up air for ventilation
Passive (determined from calculations from Table 501.4.1)
Powered (determined from calculations from Table 501.4.1)
Interlocked with exhaust device (determined from calculation from Table 501.4.1)
Other, describe: N I A
Location of duct or system ventilation make-up air: Determined from make-up air opening table
Cfm ~Q Size and type (round, rectangular, flex or rigid)
Section F
Make-up air for combustion
Not required per mechanical code (No atmospheric or power vented appliances)
Passive (see IFGC Appendix E, Worksheet E-1) Size and type n p
Other, describe:
Notes: Instructions and example forms are available at the Building Safety website and at the Building Safety office. This form must be
submitted at the time of application of a mechanical permit (or new construction. Additional forms maybe downloaded and printed at:
River Ridge Town Home Unit 8
HVAC Load Calculations
for
Superior Mechanical
1244 60th Ave NW
Rochester, MN 55901
H T ! R - C HVAC ;V.,A
Prepared By:
Monday, September 09, 2013
i
Rhvac - Residential & Light Commercial HVAC Loads Elite Software Development, Inc.
Minnesota Air River Ridge Town Home Unit B
loomin ton MN 55438
Pro'ect Report
General Pro'ect Information
Project Title: River Ridge Town Home Unit B
Project Date: Tuesday, July 02, 2013
Client Name: Superior Mechanical
Client Address: 1244 60th Ave NW
Client City: Rochester, MN 55901
Design Data
Reference City: Minneapolis, Minnesota
Daily Temperature Range: Medium
Latitude: 44 Degrees
Elevation: 834 ft.
Altitude Factor: 0.970
Elevation Sensible Adj. Factor: 1.000
Elevation Total Adj. Factor: 1.000
Elevation Heating Adj. Factor: 1.000
Elevation Heating Adj. Factor: 1.000
Outdoor Outdoor Indoor Indoor Grains
Dry Bulb t Bulb Rel.Hum U Bulb Difference
Winter: -20 0 30 72 34
Summer: 92 73 50 72 35
Check Fi ures
Total Building Supply CFM: 246 CFM Per Square ft.: 0.157
Square ft. of Room Area: 1,563 Square ft. Per Ton: 3,114
Volume (ft') of Cond. Space: 13,553 Air Turnover Rate (per hour): 1.1
Building Loads
Total Heating Required With Outside Air: 18,380 Btuh 18.380 MBH
Total Sensible Gain: 4,518 Stuh 80 %
Total Latent Gain: 1,112 Btuh 20 %
Total Cooling Required With Outside Air: 5,630 Btuh 0.47 Tons (Based On Sensible + Latent)
0.50 Tons (Based On 75% Sensible Capacity)
Notes
Calculations are based on 8th edition of ACCA Manual J.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads.
I
C:\Users\Chad.MNAIR\Desktop\Office Doc\Sales\river ridge unit B.rhv Monday, September 09, 2013, 1:04 PM
Rhvac -Residential & Light Commercial HVAC Loads Elite Software Development, Inc.
Minnesota Air River Ridge Town Home Unit B
Bloomington-MN 543 P e
Miscellaneous Report
Systern 1 Outdoor Outdoor Indoor Indoor Grains
Input Data Dry Bulb Wet Bulb Rel Hum Dry Bulb Difference
Winter: -20 0 30 72 34.40
Summer: 92 73 50 72 35.16
Duct Sizing Inputs
Main Trunk Runouts
Calculate: Yes Yes
Use Schedule: Yes Yes
Roughness Factor: 0.00300 0.01000
Pressure Drop: 0.1000 in.wg.1100 ft. 0.1000 in.wg./100 ft.
Minimum Velocity: 650 ft./min 450 ft./min
Maximum Velocity: 900 ft./min 750 ft./min
Minimum Height: 0 in. 0 in.
Maximum Height: 0 in, 0 in.
Outside Air Data
Winter Summer_
Infiltration: 0.430 AC/hr 0.230 AC/hr
Above Grade Volume: X 12.517 Cu.ft. X 12.517 Cu.ft.
5,382 Cu.ft./hr 2,879 Cu.ft./hr
X 0,0167 X 0.0167
Total Building Infiltration: 90 CFM 48 CFM
Total Building Ventilation: 0 CFM 0 CFM
---System 1---
Infiltration & Ventilation Sensible Gain Multiplier: 21.35 = (1.10 X 0.970 X 20.00 Summer Temp. Difference)
Infiltration & Ventilation Latent Gain Multiplier: 23.19 = (0.68 X 0.970 X 35.16 Grains Difference)
Infiltration & Ventilation Sensible Loss Multiplier: 98.19 = (1.10 X 0.970 X 92.00 Winter Temp. Difference)
C:\Users\Chad.MNAIR\Desktop\Office Doc\Sales\river ridge unit B.rhv Monday, September 09, 2013, 1:04 PM
Rhvac - Residential & Light Commercial HVAC Loads Elite Software Development, Inc.
Minnesota Air River Ridge Town Hom~Pa Unit B
I C Bloomin ton MN 55438 e 4'
Load Preview Report
Sys: Sys' Sys
Has': Net Rec V Sen Lat: Net Sen Ht9 CIg Act, Duct
Scope AED~ Ton Ton:; /Ton Area 'Gain; Gain! Gain Loss; ; Size
CFM: CFM;. CFM;
.
Building 0.47 0.50 3,114 1,563 4,518 1,112 5,630 18,380 246 212 246
System 1 No 0.47 0.50 3,114 1,563 4,518 1,112 5,630 18,380 246 212 246 7x7
Zone 1 1,563 4,518 1,112 5,630 18,380 246 212 246 7x7
1-Basement 543 1,117 528 1,645 7,498 100 52 100 1.6
2-Main Floor 510 1,675 309 1,984 5,865 79 78 79 1-5
3-Upper Floor 510 1,726, 275 2,001 5,017 67 81 67 1-5
C:\Users\Chad.MNAIR\Desktop\Office Doc\Sales\river ridge unit B.rhv Monday, September 09, 2013, 1:04 PM
Rhvac - Residential & Light Commercial HVAC Loads Elite Software Development, Inc.
Minnesota Air River Ridge Town Home Unit B
Bloomington, M 56438 9. 21~ Page 51
Total Building Summa Loads
Component Area. Sen Let Sen Total
Description Qu n La Gain Gin Gain
Dbl Pane Low e: Glazing-Double Pane Operable Window 70 1,932 0 1,295 1,295
Low e, u-value 0.3, SHGC 0.33
7A-1: Glazing-Glass or plastic block, smooth or wide ribs 8 442 0 195 195
or flutes, no screen, no coating, u-value 0.6, SHGC
0.65
11 P: Door-Metal - Polyurethane Core 42 1,120 0 378 378
15A-10s3oc-8: Wall-Basement, concrete block wall, R-10 139.5 885 0 23 23
foam board to 3', no framing, no interior finish, open
core, 8' floor depth
R-23 wall: Wall-Frame, , R-23 insulated wall 835.5 3,336 0 735 735
Under Attic w/ R-49: Roof/Ceiling-Under Attic with 510 938 0 561 561
Insulation on Attic Floor (also use for Knee Walls and
Partition Ceilings), Custom, Vented Attic, Dark
Asphalt Shingles
21 B-20: Floor-Basement, Concrete slab, any thickness, 2 100.8 176 0 0 0
or more feet below grade, R-3 or higher insulation
installed below floor, any floor cover, shortest side of
floor slab is 20' wide
R-56.5: Floor-Over open crawl space or garage, Custom, 449.5 744 0 121 121
R-56.5 Over Open Crawl or Garage Floori____v,_.__
Subtotals for structure: 9,573 0 3,308 3,308
People: 0 0 0 0
Equipment: 0 0 0
Lighting: 0 0 0
Ductwork: 0 0 0 0
Infiltration: Winter CFM: 90, Summer CFM: 48 8,807 1,112 1,024 2,136
Ventilation: Winter CFM: 0, Summer CFM: 0 0 0 0 0
_AED_Excursion---------------- - . -.....--.-.0................__186........ .__..g6.
Total Building Load Totals: 18,380 1,112 4,518 5,630
Check Fi ures
Total Building Supply CFM: 246 CFM Per Square ft.: 0.157
Square ft. of Room Area: 1,563 Square ft. Per Ton: 3,114
Volume (W) of Cond. Space: 13,553 Air Turnover Rate (per hour): 1.1
Buildin 'Loads
Total Heating Required With Outside Air: 18,380 Btuh 18.380 MBH
Total Sensible Gain: 4,518 Btuh 80 %
Total Latent Gain: 1,112 Btuh 20 %
Total Cooling Required With Outside Air: 5,630 Btuh 0.47 Tons (Based On Sensible + Latent)
0.50 Tons (Based On 75% Sensible Capacity)
Notes
Calculations are based on 8th edition of ACCA Manual J.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads.
I
I
C:\Users\Chad.MNAIR\Desktcp\Office Doc\Sales\river ridge unit B.rhv Monday, September 09, 2013, 1:04 PM
Rhvac - Residential & Light Commercial HVAC Loads Elite Software Development, Inca
Minnesota Air River Ridge Town Home Unit B
Bloo in ton . MN 5438 Pa 6
system I Room Load Summa
Htg Min Run Run Clg Cig Min Act
Room Area Sens Htg Duct Duct Sens Lat Clg Sys
No Name SF Btuh CFM Size Vel Btuh Btuh CFM CFM r
---Zone 1---
1 Basement 543 7,498 100 1-6 511 1,117 528 52 100
2 Main Floor 510 5,865 79 1-5 576 1,675 309 78 79
- - 3 Upper Floor.. - _.....510....-_..5,017....-.... - -._6.7 .............._.1-5 .493....- 1 726........._275............... 81.__.........._..67...
System 1 total 1,563 18,380 246 4,518 1,112 212 246
System 1 Main Trunk Size: 7x7 in.
Velocity: 723 ft./min
Loss per 100 ft.: 0.157 in.wg
Cooling System Summary
Cooling Sensible/Latent Sensible Latent Total
Tons split Btuh Btu h
Net Required: 0.47 80%/20% 4,518 1,112 5,630
Recommended: 0.50 75%/25% 4,518 1,506 6,023
Equipment Data
Heating System Cooling System
Type:
Model:
Brand:
Efficiency:
Sound:
Capacity:
Sensible Capacity: n/a 0 Btuh
Latent Capacity: n/a 0 Btuh
C:\Users\Chad.MNAIR\Desktop\Office Doc\Sales\river ridge unit B.rhv Monday, September 09, 2013, 1:04 PM