3597 Lemieux Cir i
Use BLUE or BLACK Ink
~~1~3~i Doc"
For Office Use
ermit 1~ I
City of Ea 1 ~TT
705~1 Permit Fee: t7o
3830 Pilot Knob Road I ! I
Eagan MN 55122 I Date Received: F Z 31
Phone: 1) 675-5675
Fax: 651 675-5694 ~ W l I Staff: I
I I
2013 RESIDENTIAL BUILDING PERMIT APPLICATION
Date: 19?/ 4> I A Site Address: X G~ . Unit
Name: f..~ GL1~ :~C C~iJS"I"r• Phone:dl 52. ff 4n. z o38
Resident!,
Owner Address I City I Zip: Irr l -790-44 SEC. Vyil111 A,
si; L
P L: Applicant is: owner Contractor Z U✓`ti J
_Z 4Z
x Description of work:
~7~ype of Work
n ` Construction Cost: Multi-Family Building: (Yes Z No )
Company: X A %S .~=~ZE__ Contact: HAjb~ o~2 fZN,.J 1 K
Address: City:
Contractor:
State: Zip: Phone:
License IZZ Lead Certificate
If the project is exempt from lead certification, please explain why: (see Page 3 for additional information)
COMPLETE THIS AREA ONLY IF CONSTRUCTING A NEW BUILDING
In the last 12 months, has the City of Eagan issued a permit for a similar plan based on a master plan?
Yes ZNo If yes, date and address of master plan:
Licensed Plumber: 0.1 = ttl~ , Phone:q 5Z.4d4G.4C&12.
Mechanical Contractor: ~ r'~ ~+"tl i•.~~ Phone: 61S2. aq4 . Cocos
Sewer & Water Contractor: Phone:
- , .z3 r~?..crwts~:, iv .~:.3^'rf--it'e, i+ ~~v zs~.-4 .Ee.:..r ynf~`~'a rr' }'qF?1.x .v ~ 3. tv .c~:.
NOTE >Plans antlsuppoi#mg do men. is a~you subrrl dare cprlsrde~retl,~ o;be publtcarnformafion ~°Port~ons~of ,
the information maybe classrfied asrnon puibhc rf you proviale sp'ecr is 'easons that wo y1c permit fhe City to
s b t conc u~a!e thaf tie .are- a secrets".~, _
CALL BEFORE YOU DIG. Call Gopher State One Call at (651) 454-0002 for protection against underground utility damage. Call 48 hours
before you intend to dig to receive locates of underground utilities. www.gopherstateonecall.org
I hereby acknowledge that this information is complete and accurate; that the work will be in conformance with the ordinances and codes of the City of
Eagan; that I understand this is not a permit, but only an application for a permit, and work is not to start without a permit; that the work will be in
accordance with the approved plan in the case of work which requires a review and approval of plans.
Exterior work authorized by a building permit issued in accordance with the Minnesota State Building Code must be completed within 180
days of permit issuance. .
1
Applicant's Printed Name lic t igna ure
Page 1 of 3
DO NOT WRITE BELOW THIS LINE 3D~
SUB TYPES
Foundation _ Fireplace _ Porch (3-Season) _ Storm Damage
_ Single Family _ Garage _ Porch (4-Season) _ Exterior Alteration (Single Family)
_ Multi _ Deck _ Porch (Screen/Gazebo/Pergola) _ Exterior Alteration (Multi)
01 of I Plex _ Lower Level _ Pool _ Miscellaneous
Accessory Building
WORK TYPES
- New _ Interior Jmprovement _ Siding _ Demolish Building*
Addition _ Move Building _ Reroof _ Demolish Interior
Alteration _ Fire Repair _ Windows _ Demolish Foundation
- Replace _ Repair _ Egress Window _ Water Damage
Retaining Wall *Demolition of entire building - give PCA handout to applicant
DESCRIPTION ! y /
Valuation N Occupancy MCES System
Plan Review ( Code Edition SAC Units
(25%_ 100%q Zoning (90 City Water
Census Code Stories Booster Pump
# of Units Square Feet PRV
# of Buildings Length Fire Sprinklers
Type of Construction - Width
REQUIRED INSPECTIONS
Footings (New Building) Meter Size:
Footings (Deck) Final / C.O. Required
Footings (Addition) T Final I No C.O. Required
Foundation HVAC _ Gas Service Test Gas Line Air Test
Drain Tile Other:
Roof: -Ice & Water Final Pool: -Footings -Air/Gas Teats Final
Framing Siding: -Stucco Lath Stone Lath Brick
Fireplace: Rough In ,Air Test Final Windows
Insulation Retaining Wall: _ Footings _ Backfill _ Final
Sheathing Radon Control
Sheetrock Erosion Control
Reviewed By: , Building Inspector
RESIDENTIAL FEES G~~
Base Fee A ~f L
Surcharge l°+ (7 015-.725r- / 0 57 X, ~l Y
Plan Review l a I e7
MCES SAC 7 !
( l/ 73
City SAC
Utility Connection Charge ► ~5
S&W Permit & Surcharge 111 ( I
i
Treatment Plant
Copies`( f~( l w d
TOTAL
LAO,
Page 2 of 3
L(~3uo
New Construction Energy Code Compliance Certificate
Per N1101.8 Building Certificate. A building certificate shall be posted in a permanently visible location inside Date Certificate Posted
the building. The certificate shall be completed by the builder and shall list information and values of
components listed in Table N1101.8.
Mailing Address of the Dwelling or Dwelling Unit City
3597 Lemieux Circle Eagan
Name of Residential Contractor MN License Number
Ron Clark Construction & Design 1220
THERMAL ENVELOPE RADON SYSTEM
Type: Check All That Apply X Passive (No Fan)
o ~
y c
K Active ([Pith fan and monometer or
other sYstern monitoring device )
. v C O
a
O Q. G U y 0
~ O vi vi O N U
Insulation Location z c~ p w
~ ~ on on
o N o re r2 0 o v d
E~ z s s u s R R Other Please Describe Here
Below Entire Slab X
Foundation Wall R-5 X Exterior
Foundation Wall At Walk Out R-10 X interior
Rini Joist (Foundation) R-12 X Interior
Rini Joist (1't Floor+) X
Wall R-19 X
Ceiling, flat R-44 X
Ceiling, vaulted X
Bay Windows or cantilevered areas R-30 X
Four Season Porch Above Unconditioned Space R-35 X X FGoreiownR30 i t"RigidR5
Describe other insulated areas
I
Windows & Doors Heating or Cooling Ducts Outside Conditioned Spaces
Average U-Factor (excludes skylights and one door) U: 0.31 x Not applicable, all ducts located in conditioned space
Solar Heat Gain Coefficient (SHGC): 0.35 R-value R-8 in garage area
MECHANICAL SYSTEMS Make-up Air Select. Type
Appliances Heating System Domestic Water Heater Cooling System X Not required per mech. code
Fuel Type GAS Electric R41 OA Passive
Manufacturer Bryant Marathon Bryant Powered
Interlocked with exhaust device.
Nlodel 912SB36060S14 MR105245 CA13030 Describe:
input in 60,000 Capacity in 105 Output in 2.5 Other, describe:
Rating_ or Size BTUS: Gallons: Tons:
Heat Loss. 55,180 Heat 21,664 Location of duct or system:
Structure's Calculated Gain:
AFUE or 92% SEER: 13
HSPF%
Calculated 24,974
Efficient cooling load Cfin's
" round duct OR
Mechanical Ventilation System " metal duct
Describe any additional or combined heating or cooling systems if installed: (e.g. two furnaces or air Combustion Air Select a Type
source heat pump with gas back-up furnace): Not required per mech. code
Select Type X Passive 6" Flex
X Heat Recover Ventilator (HRV) Capacity in cfms: Low: 80 High: 150 Other, describe:
Energy Recover Ventilator (ERV) Capacity in cfms: Low: High: Location of duct or system:
Continuous exhausting fan(s) rated capacity in cfms: Basement
Location of fan(s), describe: Cfm's
Capacity continuous ventilation rate in cfms: " round duct OR Flex
Total ventilation (intermittent + continuous) rate in cfms: " metal duct
Created by BAM version 052009
3597 Lemieux Cir
HVAC Load Calculations
for
Ron Clark
mk~m
VACRxsiDwmA,t,
RH WA LoAns
Prepared By;
Alan Dobson
Burnsville Heating & A/C Inc.
3451w Burnsville Pkwy, Suite 120
Bumsviiie.MN 55337
952-884-0005
Tuesday, October 22, 2013
Rhvac is an ACCA approved Manual J and Manual D computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
Rhvic - rtesfa#W1 & Lid it Comr&rcial lids £1 a So to De iaptnertt Inc.
Burnsville Heating & A/C Inc 3597 Lemieux Cir
Burnsville; MN 5,5337 Page 2
Project Report
G ne l Pro ect inform- on
Project Title: 3597 Lemieux Cir
Designed By: Alan Dobson
Project Date: Tuesday, October 22, 2013
Project Comment;
Client Name: Ron Clark
Company Name: Burnsville Heating & A/C Inc.
Company Representative: Alan Dobson
Company Address: 3451w Burnsville Pkwy, Suite 128
Company City: Burnsviile,MN 55337
Company Phone: 952-8940005
Company Fax: 952-894-0925
Company Comment:
Reference City: Minneapolis, Minnesota
Building Orientation: Front door faces West
Daily Temperature Range: Medium
Latitude: 44 Degrees
Elevation: 834 ft.
Altitude Factor 0.970
Elevation Sensible Adj. Factor. 1.000
Elevation Total Adj. Factor: 1.000
Elevation Heating Adj. Factor: 1.000
Elevation Heating Adj. Factor: 1.000
Outdoor Outdoor Outdoor Indoor Indoor Grains
Dry Bulb Wet Bulb ell Hu Bel. um Dry Bulb Difference
Winter: -15 -15.33 80% n/a 72 Ma
Summer: 88 73 50% 50% 75 35
Total Building Supply CFM: 1,015 CFM Per Square ft.: 0.289
Square ft. of Room Area: 3,515 Square ft. Per Ton: 1,689
Volume (ft') of Cond. Space: 31,623
Total Heating Required Including Ventilation Air: 55,180 Btu'h 55.180 MBH
Total Sensible Gain: 21,664 Btuh 87 %
Total Latent Gain: 3,310 Btuh 13 %
Total Cooling Required Including Ventilation Air: 24,974 Btuh 2.08 Tons (Based On Sensible + Latent)
-
'WES
Rhvac is an ACCA approved Manual J and Manual D computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
your design conditions.
\\SBS2011\RedirectedFokiers ...%Ron Clark Covington 1113597 lemleux cir.rhv Tuesday, October 22, 2013, 4:30 PM
2hvac - Restden ffil & Light Co1►iTieic 11VAC Loa s Elite S' re Developme Int.
sumsville Heating & AIC Inc 3597 Lemieux Cir
~Busxill,14N 5.5337 Miscellaneous Re ort
Sy re ii M n Floor outdoor ,O'Dtdoor Qu oor' Indoor,'indoor Grains-
L u3 Dry Bulb Wit Bulb Rep(Hum fRei.HUm D AL b -I3iffere:.. .
Winter: - _ - -15 -15.33 80% n/a 72 n/a
Summer: 88 73 50% 50% 75 35.17
ring inputs
Main frunk Runouts
Calculate: Yes Yes
Use Schedule: No No
Roughness Factor: 0.00300 0.01000
Pressure Drop: 0.1000 In.wg./100 ft. 0.1000 in.wg./100 ft
Minimum Velocity: 650 ft./min 450 ft./min
Maximum Velocity: 900 ft./min 750 ft./mm
Minimum Height: 0 in. 0 in.
Maximum Height: 0 in. 0 in.
(:Otw*Air
in r Summer
infiltration Specified: 0.320 AC/hr 0.170 AC/hr
169 CFM 90 CFM
Infiltration Actual: 0.320 AC/hr 0.170 AC/hr
Above Grade Volume: CX 31.623 Cu.ft. X 31.623 Cu.ft.
10,119 Cu.ft./hr 5,376 Cu.ft./hr
X 0.0167 X 0.0167
Total Building Infiltration: 169 CFM 90 CFM
Total Building Ventilation: 0 CFM 0 CFM
--System 1-
Infiltration & Ventilation Sensible Gain Multiplier: 13.87 = (1.10 X 0.970 X 13.00 Summer Temp. Difference)
Infiltration & Ventilation Latent Gain Multiplier: 23.20 = (0.68 X 0.970 X 35.17 Grains Difference)
Infiltration & Ventilation Sensible Loss Multiplier: 92.85 = (1.10 X 0.970 X 87.00 Winter Temp. Difference)
Winter Infiltration Specified: 0.320 AC/hr (169 CFM), Construction: Average
Summer Infiltration Specified: 0.170 AC/hr (90 CFM), Construction: Average
r1juct Loa 'Fac "'r Soenarios'for y °m.1
Attic - ~ Duct' Duct Surface From
No. e Descnption Location _ Ceiling _ Le act rw tion Area tiQC~
1 Supply Main ^ Attic 16B 0.12 6 150 No
1 Return Main Attic 16B 0.24 6 56 No
\\SBS2011\RedirectedFolders ...\Ron Clark Covington 1113597 lemieux cir.rhv Tuesday, October 22, 2013, 4:30 PM
3
Rhvac - Residlsii6 "Lidbt Commercial RVKC M-ds are tiewelop rrt lr .
Burnsville Heating & A/C Inc - - T - 3597 Lemieux Cir
Burnsv,&, MN 55337 poe 11
Total Building Summa Loads
Compon rit" . Area- Sin p- tat T Sen Total'.
D on Chian Loss Gam Gain Gain;
hbt: Glazing-hbt, ground reflectance = 0.23, u-value 0.29, - 30 756 mm 0 283 283
SHGC 0.3
hbt: Glazing-hbt, ground reflectance = 0.23, u-value 0.31, 35 945 0 511 511
SHGC 0.32
1A-rv-d: Glazing-Single pane, sliding glass door, 40.8 1,171 0 1,591 1,591
reflective, vinyl frame, ground reflectance = 0.23, u-
value 0.33, SHGC 0.35
hbt: Glazing-hbt, ground reflectance = 0.23, u-value 0.31, 127 3,428 0 4,359 4,359
SHGC 0.35
hbt: Glazing-hbt, ground reflectance = 0.23, a-value 0.3, 55 1,436 0 2,227 2,227
SHGC 0.37
hbt: Glazing-hbt, ground reflectance = 0.23, u-value 0.33, 40.8 1,171 0 1,591 1,591
SHGC 0.35
hbt: Glazing-hbt, u-value 0.31, SHGC 0.35 30 809 0 320 320
Front Door: Door- 20.4 248 0 69 69
hbt: Door-hbt 19 232 0 64 64
12E-0sw: Wall-Frame, R-19 insulation in 2 x 6 stud 2285.5 13,519 0 2,394 2,394
cavity, no board insulation, siding finish, wood studs
R-5 wall: Wall- 461.2 2,728 0 482 482
RC Rim Joist: Wall-Frame, Custom, RC Rim joist 234.8 1,696 0 300 300
1613-44-ad: Roof/Ceiling-Under Attic with Insulation on 1771.1 3,389 0 1,870 1,870
Attic Floor (also use for Knee Walls and Partition
Ceilings), vented attic, no radiant barrier, R44
insulation, dark asphalt
20P-30: Floor Over open crawl space or garage, Passive, 24 73 0 7 7
R-30 blanket insulation, any cover
RC Floor: Floor-Over open crawl space or garage, 27 66 0 6 6
Custom, RC Porch Floor
21A-32-v: Floor-Basement, Concrete slab, any thickness, 1742.7 3,032 0 0 0
2 or more feet below grade, no insulation below floor,
_ vinyl covering, shortest side of floor slab is 32 wide
Subtotals for structure: 34,699 0 16,074 16,074
People: 2 460 600 1,060
Equipment: 400 1,200 1,600
Lighting: 0 0 0
Ductwork: 4,819 371 2,173 2,544
Infiltration: Winter CFM: 169, Summer CFM: 90 15,662 2,079 1,244 3,323
Ventilation: Winter CFM: 0, Summer CFM: 0 0 0 0 0
AED Excursion: 0 0 373 373
Total Building Load Totals: 55,180 3,310 21,664 24,974
`%'as Fig s - - - _ - -
Total Building Supply CFM: 1,015 CFM Per Square ft.: 0.289
Square #t. of Room Area: 3,515 Square ft. Per Ton: 1,689
Volume (ft') of Cond. Space: 31,623
Total Heating Required Including Ventilation Air: 55,180 Btuh 55.180 MBH
Total Sensible Gain: 21,664 Btuh 87 %
Total Latent Gain: 3,310 Btuh 13 %
Total Cooling Required Including Ventilation Air: 24,974 Btuh 2.08 Tons (Based On Sensible + Latent)
Rhvac is an ACCA approved Manual J and Manual D computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
your design conditions.
\\SBS2011\RedirectedFokiers ...\Ron Clark Covington 1113597 lerrseux cir.rhv Tuesdav. October 22, 2013, 4:30 PM
Rhvac-Reslde al & UgM CommefflM HVAC= da' s - Hite So are [3eve ett, Ine.
Burnsville Heating & A/C Inc 3597 Lemieux Cir
Burnsville, MN 55337` Page 14
System 1 Main Floor Summary Loads
Component' •Area Sen Later Sen Total
LDegcngA1pn QWn Lpss Gain Gain
hbt Glazing-hb#, ground reflectance = 0.23, u: value 0.29, 30 756 0 283 283
SHGC 0.3
hbt: Glazing-hbt, ground reflectance = 0.23, u-value 0.31, 35 945 0 511 511
SHGC 0.32
1A-rv-d: Glazing-Single pane, sliding glass door, 40.8 1,171 0 1,591 1,591
reflective, vinyl frame, ground reflectance = 0.23, u-
value 0.33, SHGC 0.35
hbt: Glazing-hbt, ground reflectance = 0.23, u-value 0.31, 127 3,428 0 4,359 4,359
SHGC 0.35
hbt: Glazing-hbt, ground reflectance= 0.23, u-value 0.3, 55 1,436 0 2,227 2,227
SHGC 0.37
hbt. Glazing-hbt, ground reflectance = 0.23, u-value 0.33, 40.8 1,171 0 1,591 1,591
SHGC 0.35
hbt: Glazing-hbt, u-value 0.31, SHGC 0.35 30 809 0 320 320
Front Door. Door- 20.4 248 0 69 69
hbt: Door-hbt 19 232 0 64 64
12E-Osw: Wail-Frame, R-19 insulation 2 x 6 stud 2285.5 13,519 0 2,394 2,394
cavity, no board insulation, skiing finish, wood studs
R-5 wall: Wall- 461.2 2,728 0 482 482
RC Rim Joist: Wall-Frame, Custom, RC Rim gist 234.8 1,696 0 300 300
16B-44-ad: Roof/Ceiling-Under Attic with insulation on 1771.1 3,389 0 1,870 1,870
Attic Floor (also use for Knee Walls and Partition
Ceilings), vented attic, no radiant barrier, R-44
insulation, dark asphalt
20P-30: Floor-Over open crawl space or garage, Passive, 24 73 0 7 7
R-30 blanket insulation, any cover
RC Floor. Floor-Over open crawl space or garage, 27 66 0 6 6
Custom, RC Porch Floor
21A-32-v: Floor Basement, Concrete slab, any thickness, 1742.7 3,032 0 0 0
2 or more feet below grade, no insulation below floor,
___.vinyi coyggng, shorttst side of_floor slab is 32' wide_..__
Subtotals for structure: 34,699 0 18,074 16,074
People: 2 460 600 1,060
Equipment: 400 1,200 1,600
Lighting: 0 0 0
Ductwork: 4,819 371 2,173 2,544
Infiltration: Winter CFM: 169, Summer CFM: 90 15,662 2,079 1,244 3,323
Ventilation: Winter CFM: 0, Summer CFM: 0 0 0 0 0
AED Excursion: 0 0 373 373
System 1 Main Floor Load Totals: 55,180 3,310 21,664 24,974
Ids
Supply CFM: 1,015 CFM Per Square ft.: 0.289
Square ft. of Room Area: 3,515 Square ft. Per Ton: 1,689
Volume of Cond. Space: 31,623
- -
s ern' ds
Total Heating Required Including Ventilation Air. 55,180 I3tuh 55.180 MBH
Total Sensible Gain: 21,664 Btuh 87 %
Total Latent Gain: 3,310 Btuh 13 %
Total Cooling Required Including Ventilation Air: 24,974 Btuh 2.08 Tons (Based On Sensible + Latent)
Rhvac Is an ACCA approved Manual J and Manual D computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
your design conditions.
\\SBS2011\RedirectedFokiers ...\Ron Clark Covington 1113597 Lemieux cir.rhv Tuesday, October 22, 2013, 4:30 PM
R? vac - Resid& fiat & Li jComme-rclai HVAC Loads - - Elfte'Sd a're ~$lopmerrt, lnp.
Burnsville Heating & A/C Inc 3597 Lemieux 6
LDyrn jdie MAT 55337 P s 1..
System 1, Zone 1 Summary Loads (Peak Load Procedure for Rooms -
Corti o' bnt Area Sen tat Sen Total°
Descri' t(on Cin ss Gain_ Gain _ Gain
hbt: Glazing-hbt, ground reflectance = 0.23, u-value 0.29, 30 756 0 283 283
SHGC 0.3
hbt: Glazing-hbt, ground reflectance = 0.23, u-value 0.31, 35 945 0 511 511
SHGC 0.32
1A-rv-d: Glazing-Single pane, sliding glass door, 40.8 1,171 0 1,591 1,591
reflective, vinyl frame, ground reflectance = 0.23, u-
value 0.33, SHGC 0.35
hbt: Glazing-hbt, ground reflectance = 0.23, u-value 0.31, 57 1,538 0 2,209 2,209
SHGC 0.35
hbt: Glazing-~hbt, ground reflectance = 0.23, u-value 0.3, 30 783 0 1,215 1,215
SHGC 0.37
Front Door: Door- 20.4 248 0 69 69
hbt: Door-hbt 19 232 0 64 64
12E-0sw: Wall-Frame, R-19 insulation In 2 x 6 stud 1402.2 8,293 0 1,469 1,469
cavity, no board insulation, siding finish, wood studs
16B-44-ad: Roof/Ceiling-Under Attic with Insulation on 1771.1 3,389 0 1,870 1,870
Attic Floor (also use for Knee Walls and Partition
Ceilings), vented attic, no radiant barrier, R-44
insulation, dark asphalt
20P-30: Floor-Over open crawl space or garage, Passive, 24 73 0 7 7
R-30 blanket insulation, any cover
RC Floor. Floor-Over open crawl space or garage, 27 66 0 6 6
Custom, RC Porch Floor
Subtotals for structure: 17,494 0 11,034 11,034
People: 2 460 600 1,060
Equipment: 400 1,200 1,600
Lighting: 0 0 0
Ductwork: 2,399 0 1,298 1,298
Infiltration: _Winter ~CFM: 82, Summer CFM_43 7,575 1,0_5_ 602 1,607
System 1, Zone 1 Load Totals: 27,468 1,865 -14,957 16,822
Supply CFM: 701 ` CFM Per Square ft.: 0.395
Square ft. of Room Area: 1,772 Square ft. Per Ton: 1,264
Volume (ft') of Cond. Space: 15,939
Wd-s
Total Heating Required: 27,468 Btuh 27.468 MBH
Total Sensible Gain: 14,957 Btuh 89 %
Total Latent Gain: 1,865 Btuh 11 %
Total Cooling Required: 16,822 Btuh 1.40 Tons (Based On Sensible + Latent)
Rhvac is an ACCA approved Manual J and Manual D computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
your design conditions.
\\SBS2011%RedirectedFoklers ...1Ron Clark Covington 1113597 lemieux cir.rhv Tuesday, October 22, 2013, 4:30 PM
- -
FihVac - Residential "@ tCemme&fia''I HYAC Dad-s -s Ei oftr+vare E?avelopme "t, Inca
8umsville Heating & A/C Inc 3597 Lemieux Cir
B'll+ tlN 5337 - P e 18
[_System 9, zone 2 Summa Loads Peak Load Procedure for Rooms
em ohent - - Area Sen Lab Sen T
DW. ri n t uan _ Lois i►? Gain Gain
hbt: Glazing-hbt, ground reflectance = 0.23, u-value 0.31, 70 1,890 0 2,150 2,150
SHGC 0.35
hbt: Glazing-hbt, ground reflectance = 0.23, u-value 0.33, 40.8 1,171 0 1,591 1,591
SHGC 0.35
hbt: Glazing-hbt, ground reflectance = 0.23, u-value 0.3, 25 653 0 1,012 1,012
SHGC 0.37
hbt: Glazing-hbt, u-value 0.31, SHGC 0.35 30 809 0 320 320
12E-0sw: Wall-Frame, R-19 insulation in 2 x 6 stud 883.3 5,226 0 925 925
cavity, no board insulation, siding finish, wood studs
R-5 wall: Wall- 461.2 2,728 0 482 482
RC Rim Joist: Wall-Frame, Custom, RC Rkn joist 234.8 1,696 0 300 300
21A-32-v: Floor-Basement, Concrete slab, any thickness, 1742.7 3,032 0 0 0
2 or more feet below grade, no insulation below floor,
vinyl covering, shortest side of floor slab is 32' wide
Subtotals for structure: 17,205 0 8,416 8,416
People: 0 0 0 0
Equipment: 0 0 0
Lighting: 0 0 0
Ductwork: 2,420 0 875 875
Infiltration: Winter CFM: 87, Summer CFM: 46 8,087 1,074 642 __1,716
System 1, Zone 2 Load Totals: 27,712 1,074 10,083 11,157
Supply CFM: 472 CFM Per Square ft.: 0.271
Square ft. of Room Area: 1,743 Square ft. Per Ton: 1,875
Volume (ft') of Cond. Space: 15,684
Total Heating Required: 27,712 Btuh 27.712 MBH
Total Sensible Gain: 10,083 Btuh 90 %
Total Latent Gain: 1,074 Btuh 10 %
Total Cooling Required: 11,157 Btuh 0.93 Tons (Based On Sensible + Latent)
~-1
Rhvac is an ACCA approved Manual J and Manual D computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
your design conditions.
\\SBS2011\RedirectedFolders ...\Ron Clark Covinqton 1113597 lemieux clr.rhv Tuesday, October 22, 2013, 4:30 PM
Elite S " Dever Inc.
Rfrvac - Wes-itleit ' 1 L@ ht Com ' Ycial HVAC L
3597 Lemieux Cir
Burnsville Heating & WC inc Pa e 32
lip
Bur Mile .•AAN 5537 _
Detailed Room Loads-Room 10 - Basement Peak Fenestration Gain Procedure
e e 1
Room is in zone 2, which peaks at 10 am
Calculation Mode: Htg. & cig. Occurrences: 1
Room Length: 45.9 ft. System Number 1
Room Width: 38.0 ft. Zone Number. 2
Area: 1,743.0 sq.ft. Supply Air: 472 CFM
Ceiling Height: 9.0 ft. Supply Air Changes: 1.8 AC/hr
Volume: 15,684.0 cu.ft. Req. Vent Clg: 0 CFM
Number of Registers: 1 Actual Winter Vent.: 0 'CFM
Runout Air: 472 CFM Percent of Supply.: 0 %
Runout Duct Size: 12 in. Actual Summer Vent.: 0 CFM
Runout Air Velocity: 601 ft./min. Percent of Supply. 0 %
Runout Air Velocity: 601 ft./min. Actual Winter Infil.: 87 CFM
Actual Loss: 0.087 in.wg./100 ft. Actual Summer Infii.: 46 CFM
Item Area U fitg Sen G tit Sen
e '.tion QUa8tity Value : ATM LOSS' FtTM' Gail' _ Gam
E -Wall-1 2E-0sw 38 X e - 226.2 0.068 5.9 1,338 1.0 0 237
S -Wall12E-Osw 45.9 X 9 412.7 0.068 5.9 2,442 1.0 0 432
W Wall-R-5 wail 38 X 9 342 0.068 5.9 2,023 1.0 0 358
N -Wail-R-5 wall 16 X 9 94 0.068 5.9 556 1.0 0 98
N -Wall-12E-Osw 22.8 X 9 205.2 0.068 5.9 1,214 1.0 0 215
N -Wall-12E-0sw 7 X 5,6 39.2 0.068 5.9 232 1.0 0 41
N -Wall-R-5 wall 7 X 3.6 25.2 0.068 5.9 149 1.0 0 26
E -Wall-RC Rim Joist 38 X 1.4 53.2 0.083 7.2 384 1.3 0 68
W -Wall-RC Rim Joist 38 X 1.4 53.2 0.083 7.2 384 1.3 0 68
S -Wall-RC Rim Joist 45.9 X 1.4 64.2 0.083 7.2 464 1.3 0 82
N -Wall-RC Rim Joist 45.9 X 1.4 64.2 0.083 7.2 464 1.3 0 82
E -GIs-hbt shgc-0.35 0%S (2) 30 0.310 27.0 810 52.8 0 1,584
E -GIs-hbt shgc-0.35 0%S (2) 20 0.310 27.0 540 52.8 0 1,056
E -GIs-hbt shgc-0.35 0%S 40.8 0.330 28.7 1,171 52.9 0 2,159
E -GIs-hbt shgc-0.37 0%S 25 0.300 26.1 653 55.6 0 1,389
N -GIs-hbt shgc-0.35 O%S (2) 20 0.310 27.0 540 10.4 0 208
N -GIs-hbt shgc-0.35 0%S 30 0.310 27.0 809 10.4 0 313
Floor-21A-32 38 X 45.9 1742.7 0.020 .1.73,032 0.0 0
Subtotals for Structure: 17,205 0 8,416
Infil.: Win.: 87.1, Sum.: 46.3 1,745 4.634 8,087 0.368 1,074 642
Ductwork: 2,420 875
AED Excursion: _ 150
Room Totals: 27,712 1,074 10,083
\\SBS2011\RedirectedFoiders ...\Ron Clark Covington 1113597 lemieux cir.rhv Tuesday, October 22, 2013, 4:30 PM
Mvac - ResfdderAl && Ligfit Ci miner6al HVAC Loads Elite is f3'e`velopme Ir1C.
Burnsville Heating & A/C Inc 3597 Lemieux Cir,
Bµ. uille MN 15337 Page 35
[system 9 Room Load Summa
Min f3Gn Ran C1g CIg irl AcY;
Room Area -Sens Htg t7HICE Duct SenSLei ±Sid Sys
No N e - SF Btuh CFM S¢e Vel St Stun. C1=fV! CFM:
-Zone 1---
1 Kitchen 238 4,389 59 1-6 572 2,397 172 112 112
2 Dining 204 2,008 27 1-4 282 524 66 25 25
3 Powder Room 160 1,125 15 1-3 283 296 42 14 14
4 Den 162 4,608 62 1-7 539 3,076 152 144 144
5 Great Room 273 3,839 51 1-8 511 3,804 109 178 178
6 Master Bedroom 194 4,081 55 1-7 560 3,195 615 150 150
7 Master Bath 353 2,487 33 1-3 624 653 493 31 31
8 Mud Room 70 2,026 27 1-3 354 371 93 17 17
9 Flex Room 118 2,902 39 1-3 612 641 123 30 30
Zone 1 subtotal 1,772 27,468 368 14,957 1,865 701 701
--Zone 2--
10 Basement 1,743 27,712 371 1-12 601 10,083 1,074 472 472
_ ---Zone 2 subtotal 1,743 _ 27,712 _ 371 10,083_ 1,074 472 472
Duct Latent 371
System 1 total 3,615 55,180 ` 739 21,664 3,310 1,015 1,015
System 1 Main Trunk Size: 11x16 In.
Velocity: 830 ft./min
Loss per 100 ft.: 0.107 in.wg
Note: Since the system is muItizone, the Peak Fenestration Gain Procedure was used to determine glass senses gains
at the room and zone levels, so the sums of the zone sensible gains and airflows for cooling shown above are not intended
to equal the totals at the system level. Room and zone sensible gains and cooling CFM values are far the hour in which
the glass sensible gain for the zone is at its peek. Sensible gains at the system level are based on the "Average Load
Procedure + Excursion" method.
Cc~oit y m Summary
Cooling Sensible/Lateht Sensible Latent Total
T. 4 s It Btukz huh Btu Il
Net Required: 2.08 87%/13% 21,664 3,310 24,974
\\SBS2011\RedirectedFolders ...\Ron Clark Covington 111 3597 lemieux cir.rhv Tuesday, October 22, 2013, 4:30 PM
Burnsville Heating & Air Conditioning, Inc.
3451 W. Burnsville Pkwy, Suite 120, Burnsville, MN 55337
Phone 952-894-0005 - Fax 952-894-0925 - Web www.burnsvilleheating.com
Ventilation, Makeup and Combustion Air Calculations
Submittal Form for New Dwellings
Site address 3597 Lemieux Circle Date
Contractor Burnsville Heating & Air Conditioning, Inc Completed By Alan Dobson
Section A
Ventilation Quantity
(Determine quantity by using Table N1104.2 or Equation 11-1)
Square feet (Conditioned area including 3515 Total required ventilation 130
Basement-finished or unfinished)
Number of bedrooms 3 Continuous ventilation 65
Directions - Determine the total and continuous ventilation rate by either using Table N1104.2 or equation 11-1.
The table and equation are below.
Table N1104.2
Total and Continuous Ventilation Rates (in cfm)
Number of Bedrooms
1 2 3 4 5 6
Conditioned Total/ Total/ Total/ Total/ Total/ Total/
space (in sq. ft. continuous continuous continuous continuous continuous continuous
1000-1500 60/40 75/40 90/45 105/53 120/60 135/68
1501-2000 70/40 85/43 100/50 115/58 130/65 145/73
2001-2500 80/40 95/48 110/55 125/63 140/70 155/78
2501-3000 90/45 105/53 120/60 135/68 150/75 165/83
3001-3500 100/50 115/58 130/65_ 145/73 160/80 175/88
3501-4000 110/55 125/63 140/70 155/78 170/85 185/93
4001-4500 120/60 135/68 150/75 165/83 180/90 195/98
4501-5000 130/65 145/73 160/80 175/88 190/95 205/103
5001-5500 140/70 155/78 170/85 185/93 200/100 215/108
5501-6000 150/75 165/83 180/90 195/98 210/105 225/113
Equation 11-1
(0.02 x square feet of conditioned space) + [15 x (number of bedrooms + 1)] = Total ventilation rate (cfm)
Total ventilation - The mechanical ventilation system shall provide sufficient outdoor air to equal the total
ventilation rate average, for each one-hour period according to the above table or equation. For heat recovery
ventilators (HRV) and energy recovery ventilators (ERV) the average hourly ventilation capacity must be
determined in consideration of any reduction of exhaust or outdoor air intake, or both, for defrost or other
equipment cycling.
Continuous ventilation - A minimum of 50 percent of the total ventilation rate, but not less than 40 cfm shall be
provided, on a continuous rate average for each one-hour period. The portion of the mechanical ventilation
system intended to be continuous may have automatic cycling controls providing the average flow rate for each
hour is met.
G:\SAFETy\1K\Vent-makeup-comb air submittal (2).docx Page 1 of 6
Section B
Ventilation Method
(choose either balanced or exhaust only)
® Balanced, HRV(Heat Recovery Ventilator) or ERV (Energy ❑ Exhaust only
Recovery Ventilator) -cfm of unit in low must not exceed Continuous fan rating in cfm
continuous ventilation rating by more than 1009
Low cfm: 80 High cfm:150 Continuous fans rating in cfm (capacity
must not exceed continuous ventilation
rating by more than 1009)
Directions - Choose the method of ventilation, balanced or exhausts only. Balanced ventilation systems are typically HRV or
ERV's. Enter the low and high cfm amounts. Low c fm airflow must be equal to or greater than the required continuous
ventilation rate and less than 10096 greater than the continuous rate. (For instance, if the low cfm is 40 cfm, the ventilation fan
must not exceed 80 cfm.) Automatic controls may allow the use of a larger fan that is operated a percentage of each hour.
Section C
Ventilation Fan Schedule
Description Location Continuous Intermittent
Bath Fan Master Bath so
Bath Fan Main Bath so
Directions - The ventilation fan schedule should describe what the fan is for, the location, cfm, and whether it is used for
continuous or intermittent ventilation. The fan that is chose for continuous ventilation must be equal to or greater than the low
c fm air rating and less than 100% greater than the continuous rate. (For instance, if the low cfm is 40 cfm, the continuous
ventilation fan must not exceed 80 cfm. Automatic controls may allow the use of a larger fan that is operated a percentage of
each hour.
Section D
Ventilation Controls
(Describe operation and control of the continuous and intermittent ventilation)
Control Located In Mech Room
Directions- Describe the operation of the ventilation system. There should be adequate detail for plan reviewers and inspectors
to verify design and installation compliance. Related trades also need adequate detail for placement of controls and proper
operation of the building ventilation. If exhaust fans are used for building ventilation, describe the operation and location of any
controls, indicators and legends. If an ERV or HRV is to be installed, describe how it will be installed. If it will be connected and
interfaced with the air handling equipment please describe such connections as detailed in the manufactures' installation
instructions. If the installation instructions require or recommend the equipment to be interlocked with the air handling
equipment for proper operation, such interconnection shall be made and described.
Section E
Make-up air
Passive (determined from calculations from Table 501.3.1)
Powered (determined from calculations from Table 501.3.1)
Interlocked with exhaust device (determined from calculations from Table 501.3.1)
Other, describe:
Location of duct or system ventilation make-up air: Determined from make-up air opening table
NR cfm Size and type (round, rectangular, flex or rigid)
2 1 P a g e
Directions - In order to determine the makeup air, Table 501.3.1 must be filled out (see below). For most new installations,
column A will be appropriate, however, if atmospherically vented appliances or solid fuel appliances are installed, use the
appropriate column. For existing dwellings, see IMC 501.3.3. Please note, if the makeup air quantity is negative, no additional
makeup air will be required for ventilation, if the value is positive refer to Table 501.3.2 and size the opening. Transfer the cfm,
size of opening and type (round, rectangular, flex or rigid) to the last line of section D. The make-up air supply must be installed
per IMC 501.3.2.3.
Table 501.3.1
PROCEDURE TO DETERMINE MAKEUP AIR QUANITY FOR EXHAUST EQUIPMENT IN DWELLINGS
(Additional combustion air will be required for combustion appliances, see KAIR method for calculations)
One or multiple One or multiple fan- One atmospherically Multiple
power assisted vent atmospherically
vent or direct vent appliances and gas or oil appliance vented gas or oil
appliances power vent or direct or appliances or solid
or no combustion vent one solid fuel fuel
appliances appliances appliance appliances
Column A Column B Column C Column D
1. 0.15 0.09 0.06 0.03
a) pressure factor
(cfm/sf)
b) conditioned floor area (sf) (including 3515
unfinished basements)
Estimated House infiltration (cfm): [la 527.25
x 1b]
2. Exhaust Capacity
a) continuous exhaust-only ventilation
system (cfm); (not applicable to balanced
ventilation systems such as
HRV)
b) clothes dryer (cfm) 135 135 135 135
c) 800 of largest exhaust rating (cfm); 240
Kitchen hood typically
(not applicable if recirculating system
or if powered makeup air is electrically
interlocked and match to exhaust)
d) 80% of next largest exhaust rating Not
(cfm); bath fan typically Applicable
(not applicable if recirculating system
or if powered makeup air is electrically
interlocked and matched to exhaust)
Total Exhaust Capacity (cfm); 375
[2a + 2b +2c + 2d]
3. Makeup Air Quantity (cfm) 375
a) total exhaust capacity (from above)
b) estimated house infiltration (from 527.25
above)
Makeup Air Quantity (cfm); -152.25
Da - 3b]
(if value is negative, no makeup air is
needed)
4. For makeup Air Opening Sizing, refer
to Table 501.4.2
A. Use this column if there are other than fan-assisted or atmospherically vented gas or oil appliance or if there are no combustion appliances.
(Power vent
and direct vent appliances may be used.)
B. Use this column if there is one fan-assisted appliance per venting system. (Appliances other than atmospherically vented appliances may also
be included.)
C. Use this column if there is one atmospherically vented (other than fan-assisted) gas or oil appliance per venting system or one solid fuel
appliance.
D. Use this column if there are multiple atmospherically vented gas or oil appliances using a common vent or if there are atmospherically
vented gas or oil
appliances and solid fuel appliances.
3 P a g e
Makeup Air Opening Table for New and Existing Dwelling
Table 501.3.2
One or multiple One or multiple One atmospherically Multiple
power fanassisted vented gas or oil atmospherically
vent, direct vent appliances and appliance vented gas or oil
appliances, power vent or direct or one solid fuel appliances Duct diameter
or no combustion vent appliances appliance or solid fuel
appliances appliances
Column A Column B Column C Column D
Passive opening 1-36 1-22 1-15 1-9 3
Passive opening 37 - 66 23 - 41 16 - 28 10-17 4
Passive opening 67-109 42 - 66 29 - 46 18 - 28 5
Passive opening 110-163 67-100 47 - 69 29 - 42 6
Passive opening 164-232 101-143 70-99 43-61 7
Passive opening 233 -317 144- 195 100 -135 62- 83 8
Passive opening 318-419 196-258 136-179 84-110 9
w/motorized
damper
Passive opening 420- 539 259 -332 180 -230 111-142 10
w/motorized
damper
Passive opening 540 -679 333 -419 231- 290 143- 179 11
w/motorized
damper
Powered makeup air 2679 >419 >290 >179 NA
Notes:
A. An equivalent length of 100 feet of round smooth metal duct is assumed. Subtract 40 feet for the exterior hood and ten feet for each 90-
degree elbow to determine the remaining length of straight duct allowable.
B. If flexible duct is used, increase the duct diameter by one inch. Flexible duct shall be stretched with minimal sags. Compressed duct shall not
be accepted.
C. Barometric dampers are prohibited in passive makeup air openings when any atmospherically vented appliance is installed.
D. Powered makeup air shall be electrically interlocked with the largest exhaust system.
Sections F
Combustion air
Not required per mechanical code (No atmospheric or power vented appliances)
X Passive (see IFGC Appendix E, Worksheet E-1) Size and type 4" smooth or 5" Flex
Other, describe:
Explanation - If no atmospheric or power vented appliances are installed, check the appropriate box, not
required. If a power ventedor atmospherically vented appliance installed, use IFGC Appendix E,
Worksheet E-1 (see below). Please enter size and type. Combustionair vent supplies must communicate
with the appliance or appliances that require the combustion air.
Section F calculations follow on the next 2 pages.
4 1 P a g e
Directions - The Minnesota Fuel Gas Code method to calculate to size of a required combustion air
opening, is called the Known Air Infiltration Rate Method. For new construction, 4b of step 4 is
required to be filled out.
IFGC Appendix E, Worksheet E-1
Residential Combustion Air Calculation Method
(for Furnace, Boiler, and/or Water Heater in the Same Space)
Step 1: Complete vented combustion appliance information.
Furnace/Boiler:
-Draft Hood -Fan Assisted or Power Vent _X_Direct Vent Input:-80000 BTU/HR
Water Heater:
-Draft Hood -Fan Assisted or Power Vent -Direct Vent Input:_Electric BTU/HR
Step 2: Calculate the volume of the Combustion Appliance Space (CAS) containing combustion appliances.
The CAS includes all spaces connected to one another by code compliant openings. CAS Volume: ft
LxWxH L W H
Step 3: Determine Air Changes per Hour (ACH)1
Default ACH values have been incorporated into Table E-1 for use with Method 4b (KAIR Method).
If the year of construction or ACH is not known, use method 4a (Standard Method).
Step 4: Determine Required Volume for Combustion Air. (DO NOT COUNT DIRECT VENT APPLIANCES)
4a. Standard Method
Total Btu/hr input of all combustion appliances Input: Btu/Hr
Use Standard Method column in Table E-1 to find Total Required TRV: ft3
Volume (TRV)
If CAS Volume (from Step 2) is greater than TRV then no outdoor openings are needed.
If CAS Volume (from Step 2) is less than TRV then go to STEP S.
4b. Known Air Infiltration Rate (KAIR) Method (DO NOT COUNT DIRECT VENT APPLIANCES)
Total Btu/hr input of all fan-assisted and power vent appliances Input:-40000 Btu/Hr
Use Fan-Assisted Appliances column in Table E-1 to find RFVA:_3000 ft3
Required Volume Fan Assisted (RVFA)
Total Btu/hr input of all Natural draft appliances Input: Btu/hr Input: -0 Btu/Hr
Use Natural draft Appliances column in Table E-1 to find RVNFA:_none ft3
Required Volume Natural draft appliances (RVNDA)
Total Required Volume (TRV) = RVFA + RVNDA TRV=_3000 + none = 3000 TRV ft3
If CAS Volume (from Step 2) is greater than TRV then no outdoor openings are needed.
If CAS Volume (from Step 2) is less than TRV then go to STEP S.
Step 5: Calculate the ratio of available interior volume to the total required volume.
Ratio = CAS Volume (from Step 2) divided by TRV (from Step 4a or Step 4b)
Ratio 3000 =
Step 6: Calculate Reduction Factor (RF).
RF= 1 minus Ratio RF = 1- _
Step 7: Calculate single outdoor opening as if all combustion air is from outside.
Total Btu/hr input of all Combustion Appliances in the same CAS Input: Btu/Hr
(EXCEPT DIRECT VENT)
Combustion Air Opening Area (CAOA):
Total Btu/hr divided by 3000 Btu/hr per in2 CAOA = 40000 /3000 Btu/hr per in 13.33
Step 8: Calculate Minimum CAOA.
Minimum CAOA = CAOA multiplied by RF Minimum CAOA = 13.33 x = in
Step 9: Calculate Combustion Air Opening Diameter (CAOD)
CAOD = 1.13 multiplied by the square root of Minimum CAOA CAOD = 1.13 V Minimum CAOA = in. diameter
go up one inch in size if using flex duct
1 If desired, ACH can be determined using ASHRAE calculation or blower door test. Follow procedures in Section
G304.
5 Page
IFGC Appendix E, Table E-1
Residential Combustion air (Required Interior Volume Based on Input Rating of Appliance)
Known Air Infiltration Rate (KAIR) Method (cu ft)
Fan Assisted or Power Vent Natural Draft
Input Rating Standard Method 1994 to present Pre-1994 1994 to present Pre-1994
(Btu/hr)
5,000 250 375 188 525 263
10,000 500 750 375 1,050 525
15,000 750 1,125 563 1,575 788
20,000 1,000 1,500 750 2,100 1,050
25,000 1,250 1,875 938 2,625 1,313
30,000 1,500 2,250 1,125 3,150 1,575
35,000 1,750 2,625 1,313 3,675 1,838
40,000 2,000 3,000 1,500 4,200 2,100
45,000 2,250 3,375 1,688 4,725 2,363
50,000 2,500 3,750 1,675 5,250 2,625
55,000 2,750 4,125 2,063 5,775 2,888
60,000 3,000 4,500 2,250 6,300 3,150
65,000 3,250 4,875 2,438 6,825 3,413
70,000 3,500 5,250 2,625 7,350 3,675
75,000 3,750 5,625 2,813 7,875 3,938
80,000 4,000 6,000 3,000 8,400 4,200
85,000 4,250 6,375 3,188 8,925 4,463
90,000 4,500 6,750 3,375 9,450 4,725
95,000 4,750 7,125 3,563 9,975 4,988
100,000 5,000 7,500 3,750 10,500 5,250
105,000 5,250 7,875 3,938 11,025 5,513
110,000 5,500 8,250 4,125 11,550 5,775
115,000 5,750 8,625 4,313 12,075 6,038
120,000 6,000 9,000 4,500 12,600 6,300
125,000 6,250 9,375 4,688 13,125 6,563
130,000 6,500 9,750 4,875 13,650 6,825
135,000 6,750 10,125 5,063 14,175 7,088
140,000 7,000 10,500 5,250 14,700 7,350
145,000 7,250 10,875 5,438 15,225 7,613
150,000 7,500 11,250 5,625 15,750 7,875
155,000 7,750 11,625 5,813 16,275 8,138
160,000 8,000 12,000 6,000 16,800 8,400
165,000 8,250 12,375 6,188 17,325 8,663
170,000 8,500 12,750 6,375 17,850 8,925
175,000 8,750 13,125 6,563 18,375 9,188
180,000 9,000 13,500 6,750 18,900 9,450
185,000 9,250 13,875 6,938 19,425 9,713
190,000 9,500 14,250 7,125 19,950 9,975
195,000 9,750 14,625 7,313 20,475 10,238
200,000 10,000 15,000 7,500 21,000 10,500
205,000 10,250 15,375 7,688 22,525 10,783
210,000 10,500 15,750 7,875 22,050 11,025
215,000 10,750 16,125 8,063 22,575 11,288
220,000 11,000 16,500 8,250 23,100 11,550
225,000 11,250 16,875 8,438 23,625 11,813
230,000 11,500 17,250 8,625 24,150 12,075
1. The 1994 date refers to dwellings constructed under the 1994 Minnesota Energy Code. The default KAIR used in this section
of the table is 0.20 ACH.
2. This section of the table is to be used for dwellings constructed prior to 1994. The default KAIR used in this section of the
table is 0.40 ACH.
61 Page
LOT SURVEY CHECKLIST FOR RESIDENTIAL
` BUILDING PERMIT APPLICATION ~D
PROPERTY LEGAL:
DATE OF SURVEY: I4I~~/3
LATEST REVISION:
d
a~
c
U
O z Q DOCUMENT STANDARDS
❑ ❑ • Registered Land Surveyor signature and company
❑ ❑ • Building Permit Applicant
❑ ❑ • Legal description
0 0 • Address
0 ❑ • North arrow and scale
0 ❑ • House type (rambler, walkout, split w/o, split entry, lookout, etc.)
0 0 • Directional drainage arrows with slope/gradient %
❑ ❑ • Proposed/existing sewer and water services & invert elevation
0 0 • Street name
0 0 • Driveway (grade & width - in R/W and back of curb, 22' max.)
❑ ❑ • Lot Square Footage
❑ ❑ • Lot Coverage
ELEVATIONS
Existing
❑ 0 • Property corners
,2( 0 0 * Top of curb at the driveway and property line extensions
❑ ❑ • Elevations of any existing adjacent homes
g 0 ❑ • Adequate footing depth of structures due to adjacent utility trenches
❑ V ❑ . Waterways (pond, stream, etc.)
Proposed
❑ ❑ • Garage floor
❑ ❑ • Basement floor
~J ❑ ❑ • Lowest exposed elevation (walkout/window)
,y ❑ ❑ • Property corners
0 0 • Front and rear of home at the foundation
PONDING AREA (if applicable)
❑ 0 • Easement line
❑ 0 • NWL
❑ ~2( ❑ • HWL
❑ ❑ • Pond # designation
D 0 • Emergency Overflow Elevation ;
❑ 0 • Pond/Wetland buffer delineation
Y . Shoreland Zoning Overlay District lry Y • Conservation Easements
DIMENSIONS
❑ ❑ • Lot lines/Bearings & dimensions
2' ❑ ❑ • Right-of-way and street width (to back of curb)
,.g' 0 ❑ • Proposed home dimensions including any proposed decks, overhangs greater than 2', porches, etc.
(i.e. all structures requiring permanent footings)
❑ ❑ • Show all easements of record and any City utilities within those easements
"K ❑ 0 • Setbacks of proposed structure and"' yard setback of adjacent existing structures
❑ 0 • Retaining wall requirements:
Reviewed By:, Date1n/&~1-3
G:/FORMS/Building Permit Application Rev. 11-26-04 7
359-7 Lz~uwy 611,
Certificate of Survey for: RON CLARK CONSTRUCTION & DESIGN
~a Denotes Existing Elevation ~T Job # B1601.10-126 Book/Page: N/A
981.5 Denotes Proposed Elevation l~ Scale: 1"=30' Date: 10/10/2013
Imb, Denotes Surface Drainage
O Denotes 1/2" iron pipe set HOUSE TYPE: TOWNHOUSE FULL BASEMENT WALKOUT
PROPOSED HOUSE ELEVATIONS:
• Denotes 1/2" iron pipe found.
GARAGE FLOOR ELEVATION = 883.5
TOP OF FOUNDATION ELEV = 883.8
t•LOWEST FLOOR ELEVATION = 875.1
tt V-jail wa
Be jaNuired ..J
EXISTING BUILDING J I '
17-
C& ' Io 89 53'33"E 120.00
ti~
i - - 25 a~ WMPI
1 - / I2. t50 4- o I O C0 rn U00 \ ?j5y \e p \ 0~ ~G
i r♦ ► g'1° r ~ g19' I 1
0
I C) Q r M W ° 36.67 ~~P~ a$% I C
L
L1J ° I~ °aa - -M r ( O L G
-i- IOO LO w lO 4.0 N N I ro a (ro `V 000 Napo 8220
Im O r0 23 °o °o 0\\'' j I~ f~ t4j
Y O w o o 2.83 0 0 38.58 883.5 ~I I O af w J
I
s ~s Q > J GARAGE ~ V
~ 2.108, N JC> m I 4a$~ry e~o~ I V
13.0 a~ <
~~j IM 8739 N M N p~j GARAGE~~M N Z`
a U) co ar,
L.L -2.0
J0 Do a° O $ 39.92 883.5 2 O O o f Ba\~°
JDjLO 2 4`
Oo
C '6 13-
- - o ,2.0 F-: 0 _ ~i oCS Q- w I
Z L N° Q o I o ° co
~ O W
p , o Z
-T- I ~E of N039.58 IN
o O O O ~
1 e>9 9J- h °
Z I t L O a~35 ui ao 0) 2
0
> ~ry , gG
w \ 13.29 \9 ~I 9~~a\Q a^o 00
\ i - a\\2
w 11- 32.00 - 882. a~ $
N89°53'33"E 120.0
„ 882 e
r-----I~
w I L L 38. I I 88
2.6
I EXISTING BUILDING F
D
ir:AGAN hNG NLWQ*%4; utter.
Lots 23 and 24, Block 1, PEARLMONT HEIGHTS, Dakota County, MN
I hereby certify that this survey, plan, or report was prepared by me or under
my direct supervision and that I am a duly Licensed Land Surveyor under the
laws of the state of Minnesota.
Oliver Surveying & Engineering, Inc.
-12-~ V.-jn,- Oliver Surveying & Engineering, Inc.
By: Rick M. Blom, LS Land Surveying • Civil Engineering • Land ft miing
License No. 21729
Date: License No 172 580 Dodge Ave. Elk River, MN 55330 - 763.441.2072 • fac. 763.441.5665
10/10/2013 Revised 10/15/13 (added ex. house to south) wwK'•oliver-secom
Revised 12/05/13 (added 2' cant. to #3597)
PERMIT
City of Eagan Permit Type:Building
Permit Number:EA121076
Date Issued:03/12/2014
Permit Category:ePermit
Site Address: 3597 Lemieux Cir
Lot:24 Block: 01 Addition: Pearlmont Heights
PID:10-56950-01-240
Use:
Description:
Sub Type:Fireplace
Work Type:Gas Insert
Description:two fireplaces - main floor and lower level
Census Code:434 -
Zoning:
Square Feet:0
Occupancy:
Construction Type:
Comments:Improvements to the home may require smoke detectors in all bedrooms. Chimney / flue must be inspected prior to
concealing.
Carbon monoxide detectors are required by law in ALL single family homes .
Valuation: 3,000.00
Fee Summary:BL - Base Fee $3K $88.50 0801.4085
Surcharge - Based on Valuation $3K $1.50 9001.2195
$90.00 Total:
I hereby acknowledge that I have read this application and state that the information is correct and agree to comply with all applicable State
of Minnesota Statutes and City of Eagan Ordinances.
Contractor:Owner:- Applicant -
Pearlmount Heights Llc
7500 78th St W
Edina MN 55439
Hearth and Home Technologies
2700 N. Fairview Ave
Roseville MN 55113
(651) 638-3309
Applicant/Permitee: Signature Issued By: Signature
s ~ ~ N05 s a ~o•w
d Z
z ~ ~ " ~ of ~ ~ ~ ~\NGS~o PO~ N/ S RQ Pp ~1\\\ ~ R 6$ ~op o r Z
JC3
as W m~ O
- - -1- J g / (oQQ Sze"~°°r ~i 11
g.. g I age 522yA?6 ~/~5 \ 30~ t
o I 1 m 1
6, n$a
' o
00 g ~Ea \ 3Q~ , , .s' ~ 1
\ o 1
% In
V) ze
m-o6
z o ~'v \ u' l
~0 \ °z W 1
P Sy ~ZI 10 1
LLI
} > \ y0 I~ W 11
_ m. \ 1 a
L..'~ a 3 1 F
C3 o \7-
1
C14
r \ \ 1
z
\ 1 N 1
\ 1 ~ i
~r = 9£'LL M.O-UZ.L0S ° \
1 ~iSUxvEr . I I
V .L) 5 50.3J 134.24 I
5'OlY4'07 E' I ~ \ 1
V \ 1
Ln a
O \
~ 1 \
I \ 73.50
44.51 506'0128 E
O r
Z
506'°1'28' E 118.01
ooh Z o-Q
w o
" w
'S y 3 ~ Q ~ Sf • ~ ~ w CG u~J 'N ggyJ w , Q NZ.
lop eI5
C y 0OQ
~ p .x~.
=t F w m O w p
3 h{ ~ 5 ~ axZ L; i/ > FO: U
` T oQ
,fay u ' 3 y O
9 G
•tl ~ N y S c I
I 5 n E n
e 3 - rv
~ I gg~ 3Y ~ ~ T a N
. A 9
z, ~ ~ o ~ „ o s e
a
`
a `
lo $ 8 9
0 3 •a a G I .L ~ ~ " ~ 5
ed g $ q a$' c a ,o„ t U
e B S C;
fi e s a , < ~ Z
.60 is F:
m N v ,b„' 1 N ae b O u z V/
o m e, J /may7t
o Z v<xi °c -c o .e ° n 5 C a O 5 V
e gg O 'n
U OO ' 6 ore,' o 3 0.' a o
F G a ti r .p e H rv 3 m x < 3 W
o~ m z5 °3 o 'U < w of
m ^ga~ x~ ~ ~ a~ °9 a c y WN
a Ow
a 8 F H
g s 3 y V V p 9 v U a u= F o ° Q
r z m 9 «r U ~ ~ ° a ~ ~a ~ ; 9 U o c p n~ ~ aUG -'ai
m 5 •o :o < ` e V E~ ~ ~ ~ v I a n ~ ~ b~ g m y
ti r e _ F - 3 o e~ 0 0. n 5
n = a T p>~ 3 5 m o w Qa''~
C °u a m eo v ao •i `g ;5 ZZ. E
0. ' m a s a 4 > v < 2Y E Z e vOi S= g C V Z U e
r „ m o o c H " , a` -1 li E (g a O m ~ ~ ~ 1= F• 3 e ~ ~ 7
u F a' } o c I u I V b . I g O I y'°~1. O`'We
4A
d rr,'o 00 < roc o~ ey~~v ,~•5 < o O m$ 6'v 0.i U pe6`
m V
z 0 999 ~ii 99 9s Q. S 0 Ic Iz UU F. O
Clty of E��a�
Address: 3597 Lemieux Cir Zip: 55122 Permit#: 119300
The following items were/were not completed at the Final Inspection on:
� ��������,�ti ' � � a�
ii Yi! a�' °i iy� �, � E�7 suw�^w N �le'+4�s; ����■y��� �'am a j�yµ�yy,�
� C�l��'ll�te#� �tl�0�xtp��t� r ����h�l�:���q',ktJ����Y 1��yY���C�I�L��� I f I 3y..�
Final grade - 6"from siding
Permanent steps — Garage
Permanent steps — Main Entry
Permanent Driveway
Permanent Gas
Retaining Wall or 3:1 Max Slope �
Sod / Seeded Lawn
Trail / Curb Damage
Porch
Lower Level Finish V''� �� P�� C�
Deck ✓f
Fireplace �" ��;� � ���„��
• Verify with your builder that roof test caps from the plumbing system have been removed.
• Turn off water supply to the outside lawn faucets before freeze potential exists.
• Call the Engineering Department at (651) 675-5646 prior to working in the right-of-way or installing an
irrigation system.
Building Inspector:
G:\Building Inspections\FORMS\Checklists
.�.
�
.
UseBLUE or BLACK Ink
---------,
j For Office Use i
� �a� �
i Permit#: V "' �
�t� �f�a�a� , ��,�q ;
� Pertnit Fee:
3830 Pilot Knob Road 1
Eagan MN 55122 � Date Received: �;3 �•� �
i
Phone:(651)675-5675 �� �
Fax:(651)675-5694 j 5��= 1
I �
�--------------��-f�
� �
2014 RESIDENTIAL BUILDIWG PERMIT APPLICATION
Date: Site Address: Unit#: ` � �� ��
%� << �. �j�'
Name: /�+,c,c.J �i' j'd)Ce v'v� /�t.[.✓� G�`"`� Phone: G �2= 7�L f- 1,(�2Z i r�
R$S�a��,ti .
OW�igr Address I City 1 Zip: ���' L��� -�r�t 5c �.��
Applicant is: Owner � Contractor �I
i
Ty�@ Of WOfIC Description of work: �G<<��� f�`•c,f �(,�.�'� ���'"./'L,�a �R �I°e�le�y �,n���i�y �'�
�
` Construction Cost: ��i � Multi-Family Building:(Yes /No�
Company: /"�!'�i 3a�Per��A5'�r�.e•✓'� �f<'r. � Contact: �7 P�r~c /�,�PG/�°ey
'Contractor
Address: J��tl �tccef'(f s<�Y %� �V� I City: ��`E C.CS<-�:"�' /"oc s'l�
State:�Zip:� Phone:�/a-7d/•a�-�� / Email: �'/��Pcl���`'�i� t'.i�fl�l��r.P� .CU►�..
License#: �C "�t�� �Z( Lead Certificate#: ��
If the project is exempt from lead certification, please explain why: (see Page 3 for additional information)
COMPLETE THIS AREA ONLY IF CONSTRUCTING A NEW BUILDING
In the last 12 months,has the City of Eagan issued a peRnit for a similar plan based on a master plan?
_Yes _No If yes,date and address of master plan:
Licensed Plumber: Phone:
Mechanical Contractor: Phone•
Sewer 8�Water Contractor; Phone:
AIOTE:Plans antl supportir�g'documents i/►at,you submi#ar�cansicl�rsed#a be p�btic�i►fQrma�n. Fart3ons��`
the information may be classifred as hon�p�btic i�you provide�pecil��reastut�ifia#arauld pernr#€he City to
conc/ude tirat the are trade secr�ets.
CALL BEFORE YOU DIG. Call Gopher State One Gall at(651)454-0002 for protection against underground utility damage. Ca1148 hours
before you intend to dig to receive locates o#underground utilities. www.QOpherstateonecall.orq
I hereby acknowledge that this information is complete and accurate;that the work will be in confortnance with the ordinances and Codes of the City of
Eagan; that I understand this is not a permit, but only an application for a permit, and w+oric is not to start without a permit;that the woric will be in
accordance witM the approved plan in the case of work which requires a review and approval ot plans.
Exterior work authorized by a building pertnit issued in accordance with the Min�esota State Building Code must be pl within 1$0
days of permit issuance.
/� �.
� x (�7�'1�.� ��I�fot��-�� � X �.G.-L,i�� � �
Applicant's Printed Name licant's Si nature
ApP 9
Page 1 of 3
.
. ���� L.�����v� C,-�
DO NOT WRITE BELOW THIS LINE �����' I
SUB TYPES
Foundation _ Fireplace � Porch(3-Season) _ Exterior Alteration(Single Family)
��Singie Family Garage Porch(4-Season) E�ctenor Alteration(Multi)
Multi _ beck _ Porch(ScreeNGazebo/Pergola) _ Miscellaneous
� 01 of'�Plex � Lower Level _ Pool _ Accessory Building
WORK TYPES �,� �_�Lc�-�;h^�
` New _ Interior Improvement _ Siding _ Demolish Building*
Addition _ Move Building _ Reroof _ Qemalish interior
� Alteration T Fire Repair _ Windows i Demolish Foundation
_ Replace _ Repair _ Egress Window _ Water Damage
_ Retai�ing Wal) *Demolition of entire building—give PCA handout to appiicaM
DESCRIPTION
Valuation �d� Occupancy �(�,L 2 MCES System
Plan Review Code Edition �1 N�,��o SAC Units
(25%,_100%� Zoning �(� City Water
Census Code Stories Booster Pump
#of Units Square Feet PRV
#of Buildings Length Fire Sprinklers
Type of Construction �^ Width
REQUIRED INSPECTIONS
Footings(New Building) Meter Size:
Footings(Deck) Final/C.O. Required
Footings(Addition) x Final/No C.O.Required
Foundation HVAC Gas Service Test Gas Line Air Test
Roof:_ice&Water _Final Pool:_Footings �Air/Gas Tests �Finai
� Framing Drain Tile
Fireplace:_Rough In Air Test _�inal Siding:_Stucco Lath _Stone Lath _Brick
Insulation Windows
Sheathing Retaining Wall:_Footings_Backfill_Finai
Sheetrock Radon Contrai
Fire Walls Erosion Controi
Braced Wall Other:
Reviewed By: . Building Inspector
RESIDENTIAL FEES
Base Fee ��\�. '� � G�� k o�,�-t,��
�� � v�
Surcharge
Plan Review (�
/
MCES SAC 2 v � �"
City SAC r
Utility Connection Charge
S�W Permit 8 Surcharge
7reatment Plant
Copies
TOTAL
Page 2 of 3