Loading...
3905 Eagan Outlets Pkwy Unit 715 - Johnston & Murphy - Test & Balance Report t Test and Balance Report Johnston & Murphy Eagan, MN Date Tested July 17th 2014 Johnston & Murphy Eagan, MN July 17th 2014 Air Handling Unit Test Unit RTU-1 Manufacture Trane Model THC102E3 Total CFM 3,400 Fan RPM 1125 Motor RPM 1060 Motor Volts 208/60/3 Motor Amps Horsepower 2 O.A. Damper CFM 680 Johnston & Murphy Eagan, MN July 17th 2014 Unit Number: RTU-1 Unit Manufacture: Trane Unit Model: THC102 AREA Outlet Diffuser DESIGN Actual Percent of SERVED Number TYPE SIZE CFM CFM Required Stockroom 1 Re 12x8 300 298 90% Stockroom 2 Re 12x8 300 301 90% Retail 3 Re 12x8 280 284 90% Retail 4 Re 12x8 280 283 90% Retail 5 Re 12x8 280 278 90% Retail 6 Re 12x8 280 279 90% Retail 7 Re 12x8 280 281 90% Retail 8 Re 12x8 280 283 90% Retail 9 Re 12x8 280 284 90% Retail 10 Re 12x8 280 285 90% Retail 11 Re 12x8 280 277 90% Retail 12 Reg 12x8 280 276 90% Totals 3,400 3,409 100% Outside air set and measure at unit, 680 CFM,