3905 Eagan Outlets Pkwy Unit 715 - Johnston & Murphy - Test & Balance Report t Test and Balance Report
Johnston & Murphy
Eagan, MN
Date Tested
July 17th 2014
Johnston & Murphy
Eagan, MN
July 17th 2014
Air Handling Unit Test
Unit RTU-1
Manufacture Trane
Model THC102E3
Total CFM 3,400
Fan RPM 1125
Motor RPM 1060
Motor Volts 208/60/3
Motor Amps
Horsepower 2
O.A. Damper CFM 680
Johnston & Murphy
Eagan, MN
July 17th 2014
Unit Number: RTU-1
Unit Manufacture: Trane
Unit Model: THC102
AREA Outlet Diffuser DESIGN Actual Percent of
SERVED Number TYPE SIZE CFM CFM Required
Stockroom 1 Re 12x8 300 298 90%
Stockroom 2 Re 12x8 300 301 90%
Retail 3 Re 12x8 280 284 90%
Retail 4 Re 12x8 280 283 90%
Retail 5 Re 12x8 280 278 90%
Retail 6 Re 12x8 280 279 90%
Retail 7 Re 12x8 280 281 90%
Retail 8 Re 12x8 280 283 90%
Retail 9 Re 12x8 280 284 90%
Retail 10 Re 12x8 280 285 90%
Retail 11 Re 12x8 280 277 90%
Retail 12 Reg 12x8 280 276 90%
Totals 3,400 3,409 100%
Outside air set and measure at unit, 680 CFM,