3965 Eagan Outlets Pkwy Unit 350 - Janie & Jack - Testing & Balancing Report
r
375 230th Ave, Somerset WI 54025 - Phone: (612) 834-0311 Fax: (414) 377-3349
www.Premierbalancing.com
T£STMOY AW STING AND @ALANCING OUR"U
THE PROf£SS 0t"1.'S CMO1C£'"
Testing, Adjusting & Balancing Report
TABB TECHNICIAN
Technician: Tony Kompelien
Cell Phone: 612-419-1425
Email Address: tony@premierbalancing.com
PROJECT
Janie and Jack Outlet
3965 Eagan Outlets Parkway,
Suite 350
CLIENT
Allan Mechanical Contractors
7875 Fuller Road
Eden Prairie, MN 55344
ENGINEER
Emanuelson-Podas Consulting Engineers
10401 Bren Road East
Minnetonka, MN 55343
Report Date
August 1, 2014
TABB CERTIFICATION
TABB certification of a Supervisor is TABB's statement that the Supervisor is able to
supervise testing, adjusting and balancing of building environmental systems to produce the
design objectives or optimum system performance. For TABB Certification purposes, a
Supervisor is the person who, while employed by a TABB Certified Contractor, is
responsible and accountable for overseeing, coordinating and ensuring that projects are
performed by TABB Certified Technicians in accordance with TABB standards (including the
ICB Code of Conduct and the TAB General Rules).
Measurements recorded in this report are in accordance with the SMACNA / TABB HVAC Systems,
Testing, Adjusting and Balancing manual.
0~~~~ C:ertiff~a
tr
ANSI
ANSI' 0
Anthony Kompelien Anthony Kornpelien
Pren,r , LLG
TAUT, Y,, an '1AE9"ure-..:or
15HS7522AT TES75224S
D laid crgr r 21 2014
fed Tec1~~' ~h'ed ,SUPO
Peter
Korzenowski
T60458712C
[tom F o
Supervisor #0728
No lid Unless Signe
Exp.1213112014
TABB Certified "The Professional's Choice"
Page 2
TABB QUALITY ASSURANCE PROGRAM
BACKGROUND
TABB seeks to ensure the integrity of its certification program by: (a) setting eligibility criteria for TABB
Certified Supervisors and TABB Certified Contractors, (b) establishing testing procedures for TABB
Certified Supervisors, (c) requiring continuing education and continuous compliance with eligibility criteria
for renewal of certification, and (d) periodically reviewing its recognition of technician certification. High
quality work on the part of TABB Certified Technicians and TABB Certified Supervisors and TABB Certified
Contractors ( TABB Professionals ) is essential to integrity of the TABB Certification Program. TABB offers
this TABB Quality Assurance Program to help assure high quality work. By accepting TABB qualification or
certification, every TABB Professional accepts the responsibilities or this Program.
Quality Assurance
Every customer of a TABB Certified Contractor shall be entitled to expect: (1) that testing, adjusting and
balancing work by the contractor and its TABB Professionals will meet TABB standards; (2) that testing,
adjusting and balancing reports provided to the customer will have been prepared by a TABB Certified
Technician, and reviewed by a TABB Certified Supervisor; and (3) that the report(s) will include
measurements taken accurately with the date and mode of operation of the systems.
TABB
8403 Arlington Boulevard
Fairfax, VA 22031
Phone-(703)299-5646
Fax - (703) 683-7615
TABB Certified "The Professional's Choice"
Page 3
INSTRUMENT
CALIBRATION REPORT
INSTRUMENT MODEL MANUFACTURER SERIAL NUMBER CALIBRATION
DATE
Rotating Measuring Instrument PLT-5000 Mitchell Instruments B12A8503P 12/02/13
Temperature Measuring Instrument ADM-870C Shortridge M12072 01/21/14
Electrical Measuring Instruments 117 Fluke 18561871 01/15/14
322 Fluke 17830473 01/15/14
Air Pressure Measuring Instrument ADM-870C Shortridge M12072 01121114
Air Velocity Measuring Instrument ADM-870C Shortridge M12072 01/21/14
Hydronic Pressure Measuring Instrument HM-670 Alnor 71133088 01/15/14
0 to 300 psi
Humidity Measuring Instrument MITCT917 Mitchell Instruments 100610809 01/20/14
TABB Certified "The Professional's Choice" Page 4
Premier Test & Balance Index
Project: Janie and Jack Outlet Premier Job Number: 1234
Technician: Tony Kompelien Report Date: 8/1/14
Page System I Equipment Description Start Date Completion Date
6 RTU 350-1 Constant Air Volume 6/9/14 7/30/14
TABB Certified "The Professional's Choice"
Page 5
Premier Test & Balance Air Handling Unit Test Data
Project: Janie and Jack Outlet
System: RTU 350-1 Premier Job Number: 1234
Technician: Tony Kompelien Completion Date: 7/30/14
System Scheduled Data
Model number: LCH060H4EG2G Serial number: 5613LO9661
Manufacturer: Lennox Outlet Total CFM: 2,000
Total Design CFM: 2,000 Min.Outside Air CFM: 400
Fan Static Pressure: E ui ment Location: Roof
Performance Data
Description Scheduled 1 Submittal Data Actual Field Measurements
Motor HP: 1.00 1.00
Motor RPM: 1750 1750
Motor Hertz: 60 60
Motor Service Factor: 1.15 1.15
Motor Phase: 1 1
Motor Voltage: 460 473.
Motor Amperage: 33 3.7
Motor BHP: - 1.03
Fan RPM: - Direct Drive
Static Pressure Data
Component Static Pressure Pressure Pressure
In Out Rise I Drop Total
Fan: -0.24 0.57 Rise 0.81
Airflow Measurements
Su I Air
Opening Area Size K Design Final Reading Preliminary Reading
No. Served Factor Velocity CFM Velocity CFM % Velocity CFM
1 Various 15.5 x 5.5 0.59 473 280 505 299 107% 374 221
2 Various 18" 1.77 973 1720 957 1691 98% 708 1251
Total 2000 1990 99% 1473
Minimum Outside Air
Size K Design Final Reading Preliminary Reading
Factor Velocity CFM Velocity CFM % Velocity CFM
Total 30x19 3.96 101 400 103 408 102% 62 245
Remarks: a)
b)
C)
d)
e)
TABB Certified "The Professional's Choice"
Page 6
Premier Test & Balance Air Outlet Test Report
Project: Janie and Jack Outlet
System: RTU 350-1 Premier Job Number: 1234
Technician: Tony Kompelien Completion Date: 7/30/14
Airflow Measurements
Opening Area Size K Design Final Reading Preliminary Reading
No. Served Factor Velocity CFM Velocity CFM % Velocity CFM
1 Stockroom 15.5 x 5.5 0.59 473 280 505 299 107% 374 221
2 Sales Flow Hood 1.00 280 280 289 289 103% 322 322
3 Sales Flow Hood 1.00 280 280 277 277 99% 267 267
4 Sales Flow Hood 1.00 280 280 258 258 92%0 275 275
5 Sales Flow Hood 1.00 280 280 254 254 91% 238 238
6 Sales Flow Hood 1.00 300 300 309 309 103% 358 358
7 Sales Flow Hood 1.00 300 300 301 301 100% 260 260
Total 2000 1987 99% 1942
Remarks: a)
b)
C)
d)
e)
TABB Certified "The Professional's Choice"