3905 Eagan Outlets Pkwy Unit 230 - Crazy 8 - Testing & Balancing Report
i
375 230th Ave, Somerset WI 54025 - Phone: (612) 834-0311 Fax: (414) 377-3349
www.Premierbalancing.com
'~$pIN6, f.IJ Jl15TIIIG AND ā¯‘ALANLING ~UNR/1 ~J
7NllROii~$~ONA4'S GHtl!{".~."'
Testing, Adjusting & Balancing Report
TABB TECHNICIAN
Technician: Tony Kompelien
Cell Phone: 612419-1425
Email Address: tony@premierbalancing.com
PROJECT
Crazy 8 Outlet
3905 Eagan outlets parkway
Suite 230
CLIENT
Allan Mechanical Contractors
7875 Fuller Road
Eden Prairie, MN 55344
ENGINEER
Emanuelson-Podas Consulting Engineers
10401 Bren Road East
Minnetonka, MN 55343
Report Date
August 1, 2014
TABB CERTIFICATION
TABB certification of a Supervisor is TABB's statement that the Supervisor is able to
supervise testing, adjusting and balancing of building environmental systems to produce the
design objectives or optimum system performance. For TABB Certification purposes, a
Supervisor is the person who, while employed by a TABB Certified Contractor, is
responsible and accountable for overseeing, coordinating and ensuring that projects are
performed by TABB Certified Technicians in accordance with TABB standards (including the
ICB Code of Conduct and the TAB General Rules).
Measurements recorded in this report are in accordance with the SMACNA 1 TABB HVAC Systems,
Testing, Adjusting and Balancing manual.
A
r~ ANSI Q 1V A ISf ~
r.
0- ~ CJ-
Anthony Kompelien Anthony Kompelien
Perm r Test E 3.a-ame i
TAFZT, r TA669u rvisor
5887522flT TB$752298
Dec(,nbe, ~D Decomber 31, 2014
d Zecr~' d SUP
Bq
Pater C
N- Korzenowslci
T80458712C
Supervisor #0728
No acid unless Sign
A
exp. 12131 /2014
@ttlitB6
TABB Certified "The Professional's Choice"
Page 2
TABB QUALITY ASSURANCE PROGRAM
BACKGROUND
TABB seeks to ensure the integrity of its certification program by: (a) setting eligibility criteria for TABB
Certified Supervisors and TABB Certified Contractors, (b) establishing testing procedures for TABB
Certified Supervisors, (c) requiring continuing education and continuous compliance with eligibility criteria
for renewal of certification, and (d) periodically reviewing its recognition of technician certification. High
quality work on the part of TABB Certified Technicians and TABB Certified Supervisors and TABB Certified
Contractors ( TABB Professionals ) is essential to integrity of the TABB Certification Program. TABB offers
this TABB Quality Assurance Program to help assure high quality work. By accepting TABB qualification or
certification, every TABB Professional accepts the responsibilities or this Program.
Quality Assurance
Every customer of a TABB Certified Contractor shall be entitled to expect: (1) that testing, adjusting and
balancing work by the contractor and its TABB Professionals will meet TABB standards; (2) that testing,
adjusting and balancing reports provided to the customer will have been prepared by a TABB Certified
Technician, and reviewed by a TABB Certified Supervisor; and (3) that the report(s) will include
measurements taken accurately with the date and mode of operation of the systems.
TABB
8403 Arlington Boulevard
Fairfax, VA 22031
Phone - (703) 299-5646
Fax - (703) 683-7615
TABB Certified "The Professional's Choice"
Page 3
INSTRUMENT
CALIBRATION REPORT
INSTRUMENT MODEL MANUFACTURER SERIAL NUMBER CALIBRATION
DATE
Rotating Measuring Instrument PLT-5000 Mitchell Instruments 1312A8503P 12/02/13
Temperature Measuring Instrument ADM-870C Shortridge M12072 01/21/14
Electrical Measuring Instruments 117 Fluke 18561871 01/15/14
322 Fluke 17830473 01/15/14
Air Pressure Measuring Instrument ADM-870C Shortridge M12072 01/21/14
Air Velocity Measuring Instrument ADM-870C Shortridge M12072 01/21/14
Hydronic Pressure Measuring Instrument HM-670 Alnor 71133088 01/15/14
0 to 300 psi
Humidity Measuring Instrument MITCT917 Mitchell Instruments 100610809 01/20/14
TABB Certified "The Professional's Choice"
Page 4
Premier Test & Balance Index
Project: Crazy 8 Outlet Premier Job Number: 1236
Technician: Tony Kompelien Report Date: 8/1/14
Page System 1 Equipment Description Start Date Completion Date
6 RTU 230-1 Constant Air Volume 617/14 7/30/14
8 EF-1 (Bathroom) Constant Air Volume 617114 7/30/14
TABB Certified "The Professional's Choice"
Page 5
Premier Test & Balance Air Handling Unit Test Data
Project: Crazy 8 Outlet
System: RTU 230-1 Premier Job Number: 1236
Technician: Tony Kompelien Completion Date: 7/30/14
System Scheduled Data
Model number: KCA092H4BN1G Serial number: 5613,110100
Manufacturer: Lennox Outlet Total CFM: 3,000
Total Design CFM: 3,000 Min.Outside Air CFM: 600
Fan Static Pressure: 0.80 E ui ment Location: Roof
Performance Data
Description Scheduled i Submittal Data Actual Field Measurements
Motor HP: 2.00 2.00
Motor RPM: 1755 1755
Motor Hertz: 60 60
Motor Service Factor: 1.15 1.15
Motor Phase: 3 . 3
Motor Voltage: 460 476 476 476
Motor Amperage: 2.9 2.4 2.4 2.4
Motor BHP: 1.71
Fan RPM: 720
Static Pressure Data
Component Static Pressure Pressure Pressure
In Out Rise 1 Drop Total
Fan: -0.15 0.42 Rise 0.57
Airflow Measurements
Supply Air
Opening Area Size K Design Final Reading Preliminary Reading
No. Served Factor Velocity CFM Velocity CFM % Velocity CFM
1 Various 14" 1.07 860 920 871 932 101% 1138 1218
2 Various 18" 1.77 1177 2080 1167 2062 99% 1266 2237
Total 3000 2994 100% 3455
Minimum Outside Air
Size K Desi n Final Reading Preliminary Reading
Factor Velocity CFM Velocity CFM % Velocity CFM
Total 28x23 4.47 134 600 133 595 99% 71 318
Remarks: a)
b)
C)
d)
e)
TABB Certified "The Professional's Choice"
Page 6
Premier Test & Balance Air Outlet Test Report
Project: Crazy 8 Outlet
System: RTU 230-1 Premier Job Number: 1236
Technician: Tony Kompelien Completion Date: 7130114
Airflow Measurements
Opening Area Size K Design Final Reading Preliminary Reading
No. Served Factor Velocity CFM Velocity CFM % Velocity CFM
1 Hall 11x7 0.53 187 100 203 109 109% 189 101
2 Stockroom 11x5 0.38 785 300 766 293 98%0 817 312
3 Sales 11x5 0.38 681 260 707 270 104% 585 223
4 Sales 11x5 0.38 681 260 714 273 105% 845 323
5 Sales 11x5 0.38 681 260 678 259 100% 794 303
6 Sales 11x5 0.38 681 260 660 252 97%u 644 246
7 Sales 11x5 0.38 681 260 661 252 97% 667 255
8 Sales 11x5 0.38 681 260 699 267 103% 824 315
9 Sales 11x5 0.38 681 260 650 248 95%a 584 223
10 Sales 11x5 0.38 681 260 619 236 91%a 760 290
11 Sales 11x5 0.38 681 260 630 241 93%0 706 270
12 Sales 11x5 0.38 681 260 623 238 92%0 615 235
Total 3000 2938 98% 3095
Remarks: a)
b)
C)
d)
e)
TABB Certified "The Professional's Choice"
Page 7
Premier Test & Balance Fan Test Data
Project: Crazy 8 Outlet
System: EF-1 (Bathroom) Premier Job Number: 1236
Technician: Tony Kompelien Completion Date: 7/30/14
System Scheduled Data
Model number: SP-B110 Serial number: 13374729
Manufacturer: Greenheck Outlet Total CFM: 100
Total Design CFM: 100 Equipment Location: Restroom
Fan Static Pressure: .25 ESP
Performance Data
Description Scheduled 1 Submittal Data Actual Field Measurements
Motor HP: 0.15 0.15
Motor RPM: 950 950
Motor Hertz: 60 60
Motor Service Factor: 1.15 1.15
Motor Phase: 1 1
Motor Voltage: 115 115
Motor Amperage: 1.0 0.9
Motor BHP: 0.13
Fan RPM: 950 Direct Drive
Static Pressure Data
Component Static Pressure Pressure Pressure
In Out Rise 1 Drop Total
Fan: -0.01 0.18 Rise 0.19
Airflow Measurements
Fan Total
Opening Area Size K Design Final Reading Preliminary Reading
No. Served Factor Velocity CFM Velocity CFM % Velocity CFM
1 Bathroom Flow Hood 1.00 100 100 108 108 108% 108 108
Total 100 108 108% 108
Remarks: a) No speed control - no problems anticipated.
b)
C)
d)
e)
TABB Certified "The Professional's Choice"
Page 8