3925 Eagan Outlets Pkwy Ste 940 - Samsonite - Testing & Balancing Report
375 230th Ave, Somerset WI 54025 - Phone: (612) 834-0311 Fax: (414) 377-3349
www.Premierbalancing.com
'rl~$~r~a, gpdu;na¢ .v+o ~e. ~HCinG euuC~t}
trs oaoreasroHni ; Ho3t~"
Testing, Adjusting & Balancing Report
TABB TECHNICIAN
Technician: Tony Kompelien
Cell Phone: 612-419-1425
Email Address: tony@premierbalancing.com
PROJECT
Sampsonite
Paragon Outlets Twin Cities
Suite 940
CLIENT
Allan Mechanical Contractors
7875 Fuller Road
Eden Prairie, MN 55344
ENGINEER
Larson Binkley
310 W 20th St.
Suite 200
Kansas City, MO 64108
Report Date
August 1, 2014
TABB CERTIFICATION
TABB certification of a Supervisor is TABB's statement that the Supervisor is able to
supervise testing, adjusting and balancing of building environmental systems to produce the
design objectives or optimum system performance. For TABB Certification purposes, a
Supervisor is the person who, while employed by a TABB Certified Contractor, is
responsible and accountable for overseeing, coordinating and ensuring that projects are
performed by TABB Certified Technicians in accordance with TABB standards (including the
ICB Code of Conduct and the TAB General Rules).
Measurements recorded in this report are in accordance with the SMACNA 1 TABB HVAC Systems,
Testing, Adjusting and Balancing manual.
f
Certr ertific,
No
ANSI , v o (ANSI
Anthony Kompelien Anthony Kompelien
TAF F Technician TASB Supervisor
2H875224T 788752248
Ncember 31; 2014 Derember 31, 2 11<1
ininc0d, '.2aY3 a°Y~ ~ ~i Sa ] 1.-~2G3^
4 5 8AZ
Peter
Korzenowski
T604 7120
0
Q ~ a
SUpesviSor 10)728
Rfo alid Unless Signe
Exp. 12131 /2014 TABB Certified "The Professional's Choice"
Page 2
TABB QUALITY ASSURANCE PROGRAM
BACKGROUND
TABB seeks to ensure the integrity of its certification program by: (a) setting eligibility criteria for TABB
Certified Supervisors and TABB Certified Contractors, (b) establishing testing procedures for TABB
Certified Supervisors, (c) requiring continuing education and continuous compliance with eligibility criteria
for renewal of certification, and (d) periodically reviewing its recognition of technician certification. High
quality work on the part of TABB Certified Technicians and TABB Certified Supervisors and TABB Certified
Contractors ( TABB Professionals ) is essential to integrity of the TABB Certification Program. TABB offers
this TABB Quality Assurance Program to help assure high quality work. By accepting TABB qualification or
certification, every TABB Professional accepts the responsibilities or this Program.
Quality Assurance
Every customer of a TABB Certified Contractor shall be entitled to expect: (1) that testing, adjusting and
balancing work by the contractor and its TABB Professionals will meet TABB standards; (2) that testing,
adjusting and balancing reports provided to the customer will have been prepared by a TABB Certified
Technician, and reviewed by a TABB Certified Supervisor; and (3) that the report(s) will include
measurements taken accurately with the date and mode of operation of the systems.
TABB
8403 Arlington Boulevard
Fairfax, VA 22031
Phone - (703) 299-5646
Fax - (703) 683-7615
TABB Certified "The Professional's Choice"
Page 3
INSTRUMENT
CALIBRATION REPORT
INSTRUMENT MODEL MANUFACTURER SERIAL NUMBER CALIBRATION
DATE
Rotating Measuring Instrument PLT-5000 _ Mitchell Instruments B12A8503P 12/02/13
Temperature Measuring Instrument ADM-870C Shortridge M12072 01/21114
Electrical Measuring Instruments 117 Fluke 18561871 01/15114
322 Fluke 17830473 01/15/14
Air Pressure Measuring Instrument ADM-870C Shortridge M12072 01/21114
Air Velocity Measuring Instrument ADM-870C Shortridge M12072 01/21/14
Hydronic Pressure Measuring Instrument HM-670 Alnor 71133088 01/15/14
0 to 300 psi
Humidity Measuring Instrument MITCT917 _ Mitchell Instruments 100610809 01/20/14
TABB Certified "The Professional's Choice"
Page 4
Premier Test & Balance Air Handling Unit Test Data
Project: Sampsonite
System: RTU 940-1 Premier Job Number: 1237
Technician: Tony Kompelien Completion Date: 7/30/14
System Scheduled Data
Model number: LCH072H4BJ2G Serial number: 5613LO4507
Manufacturer: Lennox Outlet Total CFM: 2,500
Total Design CFM: 2,500 Min.Outside Air CFM: 480
Fan Static Pressure: 1.00 E ui ment Location: Roof
Performance Data
Description Scheduled 1 Submittal Data Actual Field Measurements
Motor HP:. 2.00 2.00
Motor RPM: 1755 1755
Motor Hertz: 60 60
Motor Service Factor: 1.15 1.15
Motor Phase: 3 3
Motor Voltage: 460 476 476 476
Motor Amperage: 2.9 2.6 2.6 2.6
Motor BHP: 1.86
Fan RPM: 810
Static Pressure Data
Component Static Pressure Pressure Pressure
In Out Rise 1 Drop Total
Fan: -0.18 0.48 Rise 0.66
Airflow Measurements
Supply Air
Opening Area Size K Design Final Reading Preliminary Reading
No. Served Factor Veloci CFM Velocity CFM % Velocity CFM
1 Stockroom 14' 1.07 701 750 743 795 106% 974 1042
2 Sales 18" 1.77 990 1750 1002 1771 101% 1184 2092
Total 2500 2566 103% 3134
Minimum Outside Air
Size K Design Final Reading Prelimina Reading
Factor Velocity CFM Velocity CFM % Velocity CFM
Total 30x19 3.96 121 480 120 475 99% 32 127
Remarks: a)
b)
C)
d)
e)
TABB Certified "The Professional's Choice" Page 6