3985 Eagan Outlets Pkwy Ste 500 - Adidas - Air & Balance Report
ADIDAS
EAGAN, MINNESOTA
AIR & HYDRONIC TESTING & BALANCING REPORTS
ITB PROJECT #: MN2687
17135 W. 10 Mile Road 380 Northwest Highway 8401 73rd Ave North
Suite 112 Suite 210 Suite E-8
Southfield, MI 48075 Des Plaines, IL 60016 Minneapolis, MN 55428
Phone (248) 559-5864 Phone (847)759-1800 Phone (763) 533-8882
JOB NAME:ADIDAS
LOCATION:EAGAN, MINNESOTA
I.T.B. PROJECT #:MN2687
DATE:8/14
THE DATA PRESENTED IN THIS REPORT IS AN EXACT RECORD OF SYSTEM PERFORMANCE AND WAS
OBTAINED IN ACCORDANCE WITH NEBB STANDARD PROCEDURES. ANY VARIANCES FROM DESIGN
QUANTITIES WHICH EXCEED NEBB TOLERANCES ARE NOTED THROUGHOUT THIS REPORT.
THE AIR DISTRIBUTION SYSTEMS HAVE BEEN TESTED & BALANCED AND FINAL ADJUSTMENTS HAVE BEEN
MADE IN ACCORDANCE WITH NEBB "PROCEDURAL STANDARDS FOR TESTING, ADJUSTING, BALANCING
OF ENVIRONMENTAL SYSTEMS" AND THE PROJECT SPECIFICATIONS.
ICB/NEBB FIRM:INTERNATIONAL TEST & BALANCE INC.
CERTIFIED BY:RICK YZERMANS DATE:8/6/2014
THE HYDRONIC DISTRIBUTION SYSTEMS HAVE BEEN TESTED & BALANCED AND FINAL ADJUSTMENTS HAVE
BEEN MADE IN ACCORDANCE WITH NEBB "PROCEDURAL STANDARDS FOR TESTING, ADJUSTING, BALANCING
OF ENVIRONMENTAL SYSTEMS" AND THE PROJECT SPECIFICATIONS.
ICB/NEBB FIRM :INTERNATIONAL TEST & BALANCE INC.
CERTIFIED BY: DATE:
SUBMITTED & CERTIFIED BY:
INTERNATIONAL TEST & BALANCE, INC.
NEBB CERTIFIED: RICK YZERMANS
SIGNATURE:
DATE:8/16/14 CERTIFICATION EXPIRATION DATE:
CERTIFICATION
INTERNATIONAL TEST & BALANCE, INC.
8401 73rd Avenue, N., Suite E-8
Minneapolis, MN 55428
Voice (763) 533-8882 Fax (763) 533-8933
Page 1 of 7
PROJECT: ADIDAS
LOCATION: EGAN, MN
DATE: 8/6/2014
CONTACT: Charles Bruner
Roof Top Unit
PROJECT #: MN2687
Test Date: July 31, 2014
SYSTEM/UNIT: RTU-ADIDAS-01
AREA: RETAIL
Tested By: Charles Bruner
Unit Data
Unit Manufacturer LENNOX
Unit Model Number KCA092H4BK1G
Type Draw-Thru
Unit Serial Number 5613M02987
Blade Type FC
Filter Data 4-20x25x2
Test Data
Design System Total CFM 4000 CFM
Actual System Total CFM 3984 CFM
Design Return Air CFM 3200 CFM
Actual Return Air CFM 3128 CFM
Design Outdoor Air CFM 800 CFM
Actual Outdoor Air CFM 856 CFM
Design Outlet Total CFM 3950 CFM
Actual Outlet Total CFM 3623 CFM
Actual T.F.S.P.1.0467 in. wc
Design T.F.S.P.1 ESP in. wc
Design Fan RPM 944 RPM
Actual Fan RPM 799 RPM
Design Motor RPM 1755 RPM
Actual Motor RPM 1736 RPM
Design Voltage/Phase 460/3 VOLTS
Actual Voltage/Phase 480-486-482 VOLTS
Design Amperage 2.9 AMPS
Actual Amperage 3.06-2.98-,3.25 AMPS
Design Brake Horsepower 2.62 BHP
Actual Brake Horsepower 2.24 BHP
Design Hertz 60 HZ
Actual Hertz 60 HZ
O.A. Damper Position 26 %
R.A. Damper Position 74 %
Motor Data
Motor Manufacturer INTERLINK
Frame Size 56HZ
Service Factor 1.15
PF 73 %
EFF 84 %
Horsepower 2
Sheave Data
Motor Sheave VP34
Motor Sheave PD 2.3 in.
Motor Sheave OD 3 1/8 in.
Motor Bore Size 7/8 in.
Fan Sheave AK60
Fan Sheave PD 5.00 in.
Fan Sheave OD 5.75 in.
Fan Bore Size 1 in.
Shaft Centers 21 3/8 in.
Belt Quantity 1
Belt Number AX54
Motor Adj (Plus)1 1/2 in.
Motor Adj (Minus)2 3/8 in.
Test Pressures
Suction SP -0.8882 in. wc
Discharge SP 0.16 in. wc
International Test & Balance, Inc. Page 2 of 7
PROJECT: ADIDAS
LOCATION: EGAN, MN
DATE: 8/6/2014
CONTACT: Charles Bruner
Roof Top Unit
PROJECT #: MN2687
Test Date: July 31, 2014
SYSTEM/UNIT: RTU-ADIDAS-01 (Cont.)
AREA: RETAIL
Tested By: Charles Bruner
RTU-ADIDAS-01 Supply Outlet Summary
AK
Factor
% Final
Diff.
Final
Airflow
Prelim
Airflow
Design
Airflow
InstrumentSize Outlet
Type
Area ServedSystem / Unit
RETAIL RCD10Outlet-01 1.0025290HOOD280250
RETAIL RCD10Outlet-02 1.0032091HOOD350240
RETAIL RCD10Outlet-03 1.0032593HOOD350415
RETAIL RCD10Outlet-04 1.0028595HOOD300470
RETAIL RCD10Outlet-05 1.0036591HOOD400255
RETAIL RCD10Outlet-06 1.0033094HOOD350415
RETAIL RCD10Outlet-07 *1.0032091HOOD350360
RETAIL RCD10Outlet-08 1.0027090HOOD300240
RETAIL RCD10Outlet-09 1.0025290HOOD280240
RETAIL RCD10Outlet-10 1.0025290HOOD280315
RETAIL RCD10Outlet-11 1.0025290HOOD280195
RETAIL RCD10Outlet-12 1.0025591HOOD280265
Changing RoomSAG8Outlet-13 1.0014597HOOD150176
----- 3,950 3,836 3,623Totals : 92 %
31-Jul-14 COULDN'T FIND A DAMPER. RTU-ADIDAS-01 / Outlet-07 Charles Bruner* Notes
International Test & Balance, Inc. Page 3 of 7
PROJECT: ADIDAS
LOCATION: EGAN, MN
DATE: 8/6/2014
CONTACT: Charles Bruner
Roof Top Unit
PROJECT #: MN2687
Test Date: July 31, 2014
SYSTEM/UNIT: RTU-ADIDAS-02
AREA: RETAIL/BACKROOM
Tested By: Charles Bruner
Unit Data
Unit Manufacturer LENNOX
Unit Model Number KCA120H4BL1G
Type DRAW-THRU
Unit Serial Number 5613L10579
Blade Type FC
Filter Data 4-20x25x2
Test Data
Design System Total CFM 3000 CFM
Actual System Total CFM 3828 CFM
Design Return Air CFM 2400 CFM
Actual Return Air CFM 3062 CFM
Design Outdoor Air CFM 600 CFM
Actual Outdoor Air CFM 766 CFM
Design Outlet Total CFM 2950 CFM
Actual Outlet Total CFM 3200 CFM
Actual T.F.S.P.0.8118 in. wc
Design T.F.S.P.1 ESP in. wc
Design Fan RPM 888 RPM
Actual Fan RPM 719 RPM
Design Motor RPM 1750 RPM
Actual Motor RPM 1768 RPM
Design Voltage/Phase 460/3 VOLTS
Actual Voltage/Phase 488-478-480 VOLTS
Design Amperage 4.00 AMPS
Actual Amperage 3.09-2.95-3.33 AMPS
Design Brake Horsepower 1.6 BHP
Actual Brake Horsepower 2.45 BHP
Design Hertz 60 HZ
Actual Hertz 60 HZ
O.A. Damper Position 17 %
R.A. Damper Position 83 %
Motor Data
Motor Manufacturer INTERLINK
Frame Size 56HZ
Service Factor 1.15
PF 80 %
EFF 86.5 %
Horsepower 3
Sheave Data
Motor Sheave VP44
Motor Sheave PD 2.85 in.
Motor Sheave OD 4.15 in.
Motor Bore Size 7/8 in.
Fan Sheave AK74
Fan Sheave PD 7.00 in.
Fan Sheave OD 7.25 in.
Fan Bore Size 1 in.
Shaft Centers 21 7/8 in.
Belt Quantity 1
Belt Number AX58
Motor Adj (Plus)1 3/4 in.
Motor Adj (Minus)2 1/4 in.
Test Pressures
Suction SP -0.5855 in. wc
Discharge SP 0.23 in. wc
International Test & Balance, Inc. Page 4 of 7
PROJECT: ADIDAS
LOCATION: EGAN, MN
DATE: 8/6/2014
CONTACT: Charles Bruner
Roof Top Unit
PROJECT #: MN2687
Test Date: July 31, 2014
SYSTEM/UNIT: RTU-ADIDAS-02 (Cont.)
AREA: RETAIL/BACKROOM
Tested By: Charles Bruner
RTU-ADIDAS-02 Supply Outlet Summary
AK
Factor
% Final
Diff.
Final
Airflow
Prelim
Airflow
Design
Airflow
InstrumentSize Outlet
Type
Area ServedSystem / Unit
RETAIL RCD10Outlet-01 1.00308110HOOD280340
RETAIL RCD10Outlet-02 1.00300107HOOD280337
RETAIL RCD10Outlet-03 1.00308110HOOD280280
RETAIL RCD10Outlet-04 1.00305109HOOD280265
RETAIL RCD10Outlet-05 1.00300107HOOD280346
RETAIL RCD10Outlet-06 1.00308110HOOD280353
BACKROOM RCD10Outlet-07 1.00330110HOOD300311
BACKROOM RCD10Outlet-08 1.00319106HOOD300310
BACKROOM RCD10Outlet-09 1.00330110HOOD300366
RESTROOM SAD8Outlet-10 1.0077110HOOD70123
BACKROOM RCD10Outlet-11 1.00315105HOOD300283
----- 2,950 3,314 3,200Totals : 108 %
* Notes
International Test & Balance, Inc. Page 5 of 7
PROJECT: ADIDAS
LOCATION: EGAN, MN
DATE: 8/6/2014
CONTACT: Charles Bruner
Fan Unit
PROJECT #: MN2687
Test Date: July 31, 2014
SYSTEM/UNIT: EF-02
AREA: Changing Room
Tested By: Charles Bruner
Unit Data
Fan Manufacturer LOREN COOK
Fan Model Number 70 ACEB
Fan Serial Number 297SF32553-00/0000701
Test Data
Design Airflow 200 CFM
Actual Airflow 203 CFM
Design RPM 1267 RPM
Actual RPM 1306 RPM
Motor Volts T1-T2 121 Volts
Discharge SP ATMOSPHERE in. wc
Motor Data
Rated Airflow Capacity 200 CFM
Motor Manufacturer US motor
Motor HP 1/4 HP
Motor RPM 1725 RPM
Motor Rated Volts 115 Volts
Motor Phase 1
Motor Hertz 60 Hz
Motor FL Amps 4.90 Amps
Motor Service Factor 1.35
Sheave Data
Motor Sheave MFG Maska
Motor Sheave Model 1VP34
Motor Sheave Diam.OD 3 1/8
Motor Sheave Bore 1/2
Fan Sheave MFG Baldor
Fan Sheave Model AK39/MB38
Fan Sheave Diam. OD 3 3/4
Fan Sheave Diam. PD 3.00
Fan Sheave Bore 3/4
Number of Belts 1
Belt Size A24
Sheave Center Line Idler
EF-02 Exhaust Inlet Summary
% Final
Diff.
InstrumentActual
Velocit
Final
Airflow
Prelim
Airflow
Design
Airflow
Size Inlet
Type
Area ServedSystem / Unit
Changing RoomEAG12x12Inlet-01 1030HOOD200205205
----- 200 205 205Totals : 103 %
* Notes
International Test & Balance, Inc. Page 6 of 7
PROJECT: ADIDAS
LOCATION: EGAN, MN
DATE: 8/6/2014
CONTACT: Charles Bruner
Fan Unit
PROJECT #: MN2687
Test Date: August 03, 2014
SYSTEM/UNIT: EF-02-2
AREA: RESTROOMS
Tested By: Charles Bruner
Unit Data
Fan Manufacturer GREENHECK
Fan Model Number SP-B110
Test Data
Actual Airflow 107 CFM
Design RPM 950 RPM
Actual RPM 950 RPM
Motor Volts T1-T2 121 Volts
Motor Data
Motor Manufacturer Fasco
Motor HP 1/4 HP
Motor RPM 950 RPM
Motor Rated Volts 115 Volts
Motor Phase 1
Motor Hertz 60 Hz
Motor FL Amps 1.50 Amps
Sheave Data
Motor Sheave MFG Direct Drive
Motor Sheave Model Direct Drive
Motor Sheave Diam.OD Direct Drive
Motor Sheave Bore Direct Drive
Fan Sheave MFG Direct Drive
Fan Sheave Model Direct Drive
Fan Sheave Diam. OD Direct Drive
Fan Sheave Diam. PD DIRECT DRIVE
Fan Sheave Bore DIRECT DRIVE
Number of Belts Direct Drive
Belt Size Direct Drive
Sheave Center Line Direct Drive
* Notes
International Test & Balance, Inc. Page 7 of 7