Loading...
3985 Eagan Outlets Pkwy Ste 510 - Reebok - Air & Balance Report17135 W. 10 Mile Road 380 Northwest Highway 8401 73rd Ave North Suite 112 Suite 210 Suite E-8 Southfield, MI 48075 Des Plaines, IL 60016 Minneapolis, MN 55428 Phone (248) 559-5864 Phone (847)759-1800 Phone (763) 533-8882 REEBOK EAGAN, MINNESOTA AIR & HYDRONIC TESTING & BALANCING REPORTS ITB PROJECT #: MN2687 JOB NAME:REEBOK LOCATION:EAGAN, MINNESOTA I.T.B. PROJECT #:MN2687 DATE:8/14 THE DATA PRESENTED IN THIS REPORT IS AN EXACT RECORD OF SYSTEM PERFORMANCE AND WAS OBTAINED IN ACCORDANCE WITH NEBB STANDARD PROCEDURES. ANY VARIANCES FROM DESIGN QUANTITIES WHICH EXCEED NEBB TOLERANCES ARE NOTED THROUGHOUT THIS REPORT. THE AIR DISTRIBUTION SYSTEMS HAVE BEEN TESTED & BALANCED AND FINAL ADJUSTMENTS HAVE BEEN MADE IN ACCORDANCE WITH NEBB "PROCEDURAL STANDARDS FOR TESTING, ADJUSTING, BALANCING OF ENVIRONMENTAL SYSTEMS" AND THE PROJECT SPECIFICATIONS. ICB/NEBB FIRM:INTERNATIONAL TEST & BALANCE INC. CERTIFIED BY:RICK YZERMANS DATE:8/6/2014 THE HYDRONIC DISTRIBUTION SYSTEMS HAVE BEEN TESTED & BALANCED AND FINAL ADJUSTMENTS HAVE BEEN MADE IN ACCORDANCE WITH NEBB "PROCEDURAL STANDARDS FOR TESTING, ADJUSTING, BALANCING OF ENVIRONMENTAL SYSTEMS" AND THE PROJECT SPECIFICATIONS. ICB/NEBB FIRM :INTERNATIONAL TEST & BALANCE INC. CERTIFIED BY: DATE: SUBMITTED & CERTIFIED BY: INTERNATIONAL TEST & BALANCE, INC. NEBB CERTIFIED: RICK YZERMANS SIGNATURE: DATE:8/16/14 CERTIFICATION EXPIRATION DATE: CERTIFICATION INTERNATIONAL TEST & BALANCE, INC. 8401 73rd Avenue, N., Suite E-8 Minneapolis, MN 55428 Voice (763) 533-8882 Fax (763) 533-8933 PROJECT: REEBOK LOCATION: EAGAN, MN DATE: 8/6/2014 CONTACT: Charles Bruner Roof Top Unit PROJECT #: MN2687 Test Date: August 05, 2014 SYSTEM/UNIT: RTU-REEBOK-01 AREA: RETAIL Tested By: Charles Bruner Unit Data Unit Manufacturer LENNOX Unit Model Number KCA092H4BX1G Type Draw-Thru Unit Serial Number 5613M02991 Blade Type FC Filter Data 4-20x25x2 Test Data Design System Total CFM 3000 CFM Actual System Total CFM 3181 CFM Design Return Air CFM 2400 CFM Actual Return Air CFM 2544 CFM Design Outdoor Air CFM 600 CFM Actual Outdoor Air CFM 636 CFM Design Outlet Total CFM 3000 CFM Actual Outlet Total CFM 2880 CFM Actual T.F.S.P.0.6491 in. wc Design T.F.S.P.1 ESP in. wc Design Fan RPM 888 RPM Actual Fan RPM 633 RPM Design Motor RPM 1755 RPM Actual Motor RPM 1768 RPM Design Voltage/Phase 460/3 VOLTS Actual Voltage/Phase 489-484-481 VOLTS Design Amperage 2.9 AMPS Actual Amperage 3.01-2.93-3.16 AMPS Design Brake Horsepower 1.60 BHP Actual Brake Horsepower 2.2 BHP Design Hertz 60 HZ Actual Hertz 60 HZ O.A. Damper Position 23 % R.A. Damper Position 77 % Motor Data Motor Manufacturer INTERLINK Frame Size 56HZ Service Factor 1.15 PF 73 % EFF 84 % Horsepower 2 Sheave Data Motor Sheave 1VP34 Motor Sheave PD 2.0 in. Motor Sheave OD 3.15 in. Motor Bore Size 7/8 in. Fan Sheave AK61 Fan Sheave PD 5.70 in. Fan Sheave OD 5.95 in. Fan Bore Size 1 in. Shaft Centers 21 1/2 in. Belt Quantity 1 Belt Number AX54 Motor Adj (Plus)1 1/2 in. Motor Adj (Minus)2 3/8 in. Test Pressures Suction SP -0.4429 in. wc Discharge SP 0.21 in. wc International Test & Balance, Inc. Page 1 of 6 PROJECT: REEBOK LOCATION: EAGAN, MN DATE: 8/6/2014 CONTACT: Charles Bruner Roof Top Unit PROJECT #: MN2687 Test Date: August 05, 2014 SYSTEM/UNIT: RTU-REEBOK-01 (Cont.) AREA: RETAIL Tested By: Charles Bruner RTU-REEBOK-01 Supply Outlet Summary AK Factor % Final Diff. Final Airflow Prelim Airflow Design Airflow InstrumentSize Outlet Type Area ServedSystem / Unit RETAIL RCD10Outlet-01 1.00250100HOOD250215 RETAIL RCD10Outlet-02 1.00250100HOOD250235 RETAIL RCD10Outlet-03 1.0024096HOOD250265 RETAIL RCD10Outlet-04 1.0024598HOOD250245 RETAIL RCD10Outlet-05 1.00255102HOOD250325 RETAIL RCD10Outlet-06 1.0024598HOOD250315 RETAIL RCD10Outlet-07 1.0023594HOOD250330 RETAIL RCD10Outlet-08 1.0023092HOOD250195 RETAIL RCD10Outlet-09 1.0023594HOOD250225 RETAIL RCD10Outlet-10 1.0024096HOOD250215 RETAIL RCD10Outlet-11 1.0022590HOOD250220 RETAIL RCD10Outlet-12 11.0023092HOOD250215 ----- 3,000 3,000 2,880Totals : 96 % * Notes International Test & Balance, Inc. Page 2 of 6 PROJECT: REEBOK LOCATION: EAGAN, MN DATE: 8/6/2014 CONTACT: Charles Bruner Roof Top Unit PROJECT #: MN2687 Test Date: August 05, 2014 SYSTEM/UNIT: RTU-REEBOK-02 AREA: RETAIL/BACKROOM Tested By: Charles Bruner Unit Data Unit Manufacturer LENNOX Unit Model Number KCA092H4BK1G Type DRAW-THRU Unit Serial Number 5613M02992 Blade Type FC Filter Data 4-20x25x2 Test Data Design System Total CFM 3000 CFM Actual System Total CFM 3093 CFM Design Return Air CFM 2400 CFM Actual Return Air CFM 2433 CFM Design Outdoor Air CFM 600 CFM Actual Outdoor Air CFM 660 CFM Design Outlet Total CFM 2670 CFM Actual Outlet Total CFM 2482 CFM Actual T.F.S.P.0.8236 in. wc Design T.F.S.P.1.00 in. wc Design Fan RPM 888 RPM Actual Fan RPM 815 RPM Design Motor RPM 1755 RPM Actual Motor RPM 1766 RPM Design Voltage/Phase 460/3 VOLTS Actual Voltage/Phase 481-482-485 VOLTS Design Amperage 2.9 AMPS Actual Amperage 2.82-2.72-2.92 AMPS Design Brake Horsepower 1.60 BHP Actual Brake Horsepower 2.04 BHP Design Hertz 60 HZ Actual Hertz 60 HZ O.A. Damper Position 22 % R.A. Damper Position 78 % Motor Data Motor Manufacturer INTERLINK Frame Size 56HZ Service Factor 1.15 PF 73 % EFF 84 % Horsepower 2 Sheave Data Motor Sheave 1VP34 Motor Sheave PD 2.6 in. Motor Sheave OD 3.15 in. Motor Bore Size 7/8 in. Fan Sheave AK61 Fan Sheave PD 5.70 in. Fan Sheave OD 5.95 in. Fan Bore Size 1 in. Shaft Centers 21 7/8 in. Belt Quantity 1 Belt Number AX54 Motor Adj (Plus)1 3/4 in. Motor Adj (Minus)2 1/8 in. Test Pressures Suction SP -0.4557 in. wc Discharge SP 0.37 in. wc International Test & Balance, Inc. Page 3 of 6 PROJECT: REEBOK LOCATION: EAGAN, MN DATE: 8/6/2014 CONTACT: Charles Bruner Roof Top Unit PROJECT #: MN2687 Test Date: August 05, 2014 SYSTEM/UNIT: RTU-REEBOK-02 (Cont.) AREA: RETAIL/BACKROOM Tested By: Charles Bruner RTU-REEBOK-02 Supply Outlet Summary AK Factor % Final Diff. Final Airflow Prelim Airflow Design Airflow InstrumentSize Outlet Type Area ServedSystem / Unit RETAIL RCD8Outlet-01 1.00200100HOOD200175 RETAIL RCD8Outlet-02 1.0018593HOOD200165 RETAIL RCD8Outlet-03 1.00205103HOOD200285 RETAIL RCD8Outlet-04 1.00215108HOOD200280 RETAIL RCD8Outlet-05 1.00205103HOOD200315 RETAIL RCD8Outlet-06 1.00200100HOOD200265 BACKROOM RCD10Outlet-07 1.0023594HOOD250315 BACKROOM RCD10Outlet-08 1.0024598HOOD250283 BACKROOM RCD10Outlet-09 1.0022590HOOD250169 BACKROOM RCD10Outlet-10 1.0022590HOOD250149 OFFICE SAD8Outlet-11 *1.0010653HOOD20075 BACKROOM RCD8Outlet-12 1.0018090HOOD200169 RESTROOM SAD8Outlet-13 *1.005680HOOD7051 ----- 2,670 2,696 2,482Totals : 93 % 31-Jul-14 DAMPER IS 100% OPEN. RTU-REEBOK-02 / Outlet-11 Charles Bruner 31-Jul-14 MOTORIZED DAMPER WAS NOT POWERED UP. RTU-REEBOK-02 / Outlet-11 Charles Bruner 31-Jul-14 DAMPER IS 100% OPEN. RTU-REEBOK-02 / Outlet-13 Charles Bruner * Notes International Test & Balance, Inc. Page 4 of 6 PROJECT: REEBOK LOCATION: EAGAN, MN DATE: 8/6/2014 CONTACT: Charles Bruner Fan Unit PROJECT #: MN2687 Test Date: July 31, 2014 SYSTEM/UNIT: EF-01 AREA: Changing Room Tested By: Charles Bruner Unit Data Fan Manufacturer LOREN COOK Fan Model Number 80 ACEB Fan Serial Number 297SF32373-00/0000701 Test Data Design Airflow 400 CFM Actual Airflow 416 CFM Design RPM 1257 RPM Actual RPM 1420 RPM Motor Volts T1-T2 121 Volts Motor Amps T1 4.34 Amps Discharge SP ATMOSPHERE in. wc Motor Data Rated Airflow Capacity 400 CFM Motor Manufacturer US motor Motor HP 1/4 HP Motor RPM 1725 RPM Motor Rated Volts 115 Volts Motor Phase 1 Motor Hertz 60 Hz Motor FL Amps 4.90 Amps Motor Service Factor 1.35 Sheave Data Motor Sheave MFG Browning Motor Sheave Model 1VP34 Motor Sheave Diam.OD 3 1/8 Motor Sheave Bore 1/2 Fan Sheave MFG Baldor Fan Sheave Model AK47/MA40 Fan Sheave Diam. OD 3.95 Fan Sheave Diam. PD 3.20 Fan Sheave Bore 3/4 Number of Belts 1 Belt Size A24 Sheave Center Line IDLER EF-01 Exhaust Inlet Summary % Final Diff. InstrumentActual Velocit Final Airflow Prelim Airflow Design Airflow Size Inlet Type Area ServedSystem / Unit MENS EAD12x12Inlet-01 1030HOOD200100205 WOMEN'S EAD12x12Inlet-02 1060HOOD200109211 ----- 400 209 416Totals : 104 % * Notes International Test & Balance, Inc. Page 5 of 6 PROJECT: REEBOK LOCATION: EAGAN, MN DATE: 8/6/2014 CONTACT: Charles Bruner Fan Unit PROJECT #: MN2687 Test Date: August 03, 2014 SYSTEM/UNIT: EF-01-1 AREA: RESTROOMS Tested By: Charles Bruner Unit Data Fan Manufacturer GREENHECK Fan Model Number SP-B110 Test Data Actual Airflow 100 CFM Design RPM 950 RPM Actual RPM 950 RPM Motor Volts T1-T2 121 Volts Motor Data Motor Manufacturer Fasco Motor HP 1/4 HP Motor RPM 950 RPM Motor Rated Volts 115 Volts Motor Phase 1 Motor Hertz 60 Hz Motor FL Amps 1.50 Amps Sheave Data Motor Sheave MFG Direct Drive Motor Sheave Model Direct Drive Motor Sheave Diam.OD Direct Drive Motor Sheave Bore Direct Drive Fan Sheave MFG Direct Drive Fan Sheave Model Direct Drive Fan Sheave Diam. OD Direct Drive Fan Sheave Diam. PD DIRECT DRIVE Fan Sheave Bore DIRECT DRIVE Number of Belts Direct Drive Belt Size Direct Drive Sheave Center Line Direct Drive * Notes International Test & Balance, Inc. Page 6 of 6