3985 Eagan Outlets Pkwy Ste 510 - Reebok - Air & Balance Report17135 W. 10 Mile Road 380 Northwest Highway 8401 73rd Ave North
Suite 112 Suite 210 Suite E-8
Southfield, MI 48075 Des Plaines, IL 60016 Minneapolis, MN 55428
Phone (248) 559-5864 Phone (847)759-1800 Phone (763) 533-8882
REEBOK
EAGAN, MINNESOTA
AIR & HYDRONIC TESTING & BALANCING REPORTS
ITB PROJECT #: MN2687
JOB NAME:REEBOK
LOCATION:EAGAN, MINNESOTA
I.T.B. PROJECT #:MN2687
DATE:8/14
THE DATA PRESENTED IN THIS REPORT IS AN EXACT RECORD OF SYSTEM PERFORMANCE AND WAS
OBTAINED IN ACCORDANCE WITH NEBB STANDARD PROCEDURES. ANY VARIANCES FROM DESIGN
QUANTITIES WHICH EXCEED NEBB TOLERANCES ARE NOTED THROUGHOUT THIS REPORT.
THE AIR DISTRIBUTION SYSTEMS HAVE BEEN TESTED & BALANCED AND FINAL ADJUSTMENTS HAVE BEEN
MADE IN ACCORDANCE WITH NEBB "PROCEDURAL STANDARDS FOR TESTING, ADJUSTING, BALANCING
OF ENVIRONMENTAL SYSTEMS" AND THE PROJECT SPECIFICATIONS.
ICB/NEBB FIRM:INTERNATIONAL TEST & BALANCE INC.
CERTIFIED BY:RICK YZERMANS DATE:8/6/2014
THE HYDRONIC DISTRIBUTION SYSTEMS HAVE BEEN TESTED & BALANCED AND FINAL ADJUSTMENTS HAVE
BEEN MADE IN ACCORDANCE WITH NEBB "PROCEDURAL STANDARDS FOR TESTING, ADJUSTING, BALANCING
OF ENVIRONMENTAL SYSTEMS" AND THE PROJECT SPECIFICATIONS.
ICB/NEBB FIRM :INTERNATIONAL TEST & BALANCE INC.
CERTIFIED BY: DATE:
SUBMITTED & CERTIFIED BY:
INTERNATIONAL TEST & BALANCE, INC.
NEBB CERTIFIED: RICK YZERMANS
SIGNATURE:
DATE:8/16/14 CERTIFICATION EXPIRATION DATE:
CERTIFICATION
INTERNATIONAL TEST & BALANCE, INC.
8401 73rd Avenue, N., Suite E-8
Minneapolis, MN 55428
Voice (763) 533-8882 Fax (763) 533-8933
PROJECT: REEBOK
LOCATION: EAGAN, MN
DATE: 8/6/2014
CONTACT: Charles Bruner
Roof Top Unit
PROJECT #: MN2687
Test Date: August 05, 2014
SYSTEM/UNIT: RTU-REEBOK-01
AREA: RETAIL
Tested By: Charles Bruner
Unit Data
Unit Manufacturer LENNOX
Unit Model Number KCA092H4BX1G
Type Draw-Thru
Unit Serial Number 5613M02991
Blade Type FC
Filter Data 4-20x25x2
Test Data
Design System Total CFM 3000 CFM
Actual System Total CFM 3181 CFM
Design Return Air CFM 2400 CFM
Actual Return Air CFM 2544 CFM
Design Outdoor Air CFM 600 CFM
Actual Outdoor Air CFM 636 CFM
Design Outlet Total CFM 3000 CFM
Actual Outlet Total CFM 2880 CFM
Actual T.F.S.P.0.6491 in. wc
Design T.F.S.P.1 ESP in. wc
Design Fan RPM 888 RPM
Actual Fan RPM 633 RPM
Design Motor RPM 1755 RPM
Actual Motor RPM 1768 RPM
Design Voltage/Phase 460/3 VOLTS
Actual Voltage/Phase 489-484-481 VOLTS
Design Amperage 2.9 AMPS
Actual Amperage 3.01-2.93-3.16 AMPS
Design Brake Horsepower 1.60 BHP
Actual Brake Horsepower 2.2 BHP
Design Hertz 60 HZ
Actual Hertz 60 HZ
O.A. Damper Position 23 %
R.A. Damper Position 77 %
Motor Data
Motor Manufacturer INTERLINK
Frame Size 56HZ
Service Factor 1.15
PF 73 %
EFF 84 %
Horsepower 2
Sheave Data
Motor Sheave 1VP34
Motor Sheave PD 2.0 in.
Motor Sheave OD 3.15 in.
Motor Bore Size 7/8 in.
Fan Sheave AK61
Fan Sheave PD 5.70 in.
Fan Sheave OD 5.95 in.
Fan Bore Size 1 in.
Shaft Centers 21 1/2 in.
Belt Quantity 1
Belt Number AX54
Motor Adj (Plus)1 1/2 in.
Motor Adj (Minus)2 3/8 in.
Test Pressures
Suction SP -0.4429 in. wc
Discharge SP 0.21 in. wc
International Test & Balance, Inc. Page 1 of 6
PROJECT: REEBOK
LOCATION: EAGAN, MN
DATE: 8/6/2014
CONTACT: Charles Bruner
Roof Top Unit
PROJECT #: MN2687
Test Date: August 05, 2014
SYSTEM/UNIT: RTU-REEBOK-01 (Cont.)
AREA: RETAIL
Tested By: Charles Bruner
RTU-REEBOK-01 Supply Outlet Summary
AK
Factor
% Final
Diff.
Final
Airflow
Prelim
Airflow
Design
Airflow
InstrumentSize Outlet
Type
Area ServedSystem / Unit
RETAIL RCD10Outlet-01 1.00250100HOOD250215
RETAIL RCD10Outlet-02 1.00250100HOOD250235
RETAIL RCD10Outlet-03 1.0024096HOOD250265
RETAIL RCD10Outlet-04 1.0024598HOOD250245
RETAIL RCD10Outlet-05 1.00255102HOOD250325
RETAIL RCD10Outlet-06 1.0024598HOOD250315
RETAIL RCD10Outlet-07 1.0023594HOOD250330
RETAIL RCD10Outlet-08 1.0023092HOOD250195
RETAIL RCD10Outlet-09 1.0023594HOOD250225
RETAIL RCD10Outlet-10 1.0024096HOOD250215
RETAIL RCD10Outlet-11 1.0022590HOOD250220
RETAIL RCD10Outlet-12 11.0023092HOOD250215
----- 3,000 3,000 2,880Totals : 96 %
* Notes
International Test & Balance, Inc. Page 2 of 6
PROJECT: REEBOK
LOCATION: EAGAN, MN
DATE: 8/6/2014
CONTACT: Charles Bruner
Roof Top Unit
PROJECT #: MN2687
Test Date: August 05, 2014
SYSTEM/UNIT: RTU-REEBOK-02
AREA: RETAIL/BACKROOM
Tested By: Charles Bruner
Unit Data
Unit Manufacturer LENNOX
Unit Model Number KCA092H4BK1G
Type DRAW-THRU
Unit Serial Number 5613M02992
Blade Type FC
Filter Data 4-20x25x2
Test Data
Design System Total CFM 3000 CFM
Actual System Total CFM 3093 CFM
Design Return Air CFM 2400 CFM
Actual Return Air CFM 2433 CFM
Design Outdoor Air CFM 600 CFM
Actual Outdoor Air CFM 660 CFM
Design Outlet Total CFM 2670 CFM
Actual Outlet Total CFM 2482 CFM
Actual T.F.S.P.0.8236 in. wc
Design T.F.S.P.1.00 in. wc
Design Fan RPM 888 RPM
Actual Fan RPM 815 RPM
Design Motor RPM 1755 RPM
Actual Motor RPM 1766 RPM
Design Voltage/Phase 460/3 VOLTS
Actual Voltage/Phase 481-482-485 VOLTS
Design Amperage 2.9 AMPS
Actual Amperage 2.82-2.72-2.92 AMPS
Design Brake Horsepower 1.60 BHP
Actual Brake Horsepower 2.04 BHP
Design Hertz 60 HZ
Actual Hertz 60 HZ
O.A. Damper Position 22 %
R.A. Damper Position 78 %
Motor Data
Motor Manufacturer INTERLINK
Frame Size 56HZ
Service Factor 1.15
PF 73 %
EFF 84 %
Horsepower 2
Sheave Data
Motor Sheave 1VP34
Motor Sheave PD 2.6 in.
Motor Sheave OD 3.15 in.
Motor Bore Size 7/8 in.
Fan Sheave AK61
Fan Sheave PD 5.70 in.
Fan Sheave OD 5.95 in.
Fan Bore Size 1 in.
Shaft Centers 21 7/8 in.
Belt Quantity 1
Belt Number AX54
Motor Adj (Plus)1 3/4 in.
Motor Adj (Minus)2 1/8 in.
Test Pressures
Suction SP -0.4557 in. wc
Discharge SP 0.37 in. wc
International Test & Balance, Inc. Page 3 of 6
PROJECT: REEBOK
LOCATION: EAGAN, MN
DATE: 8/6/2014
CONTACT: Charles Bruner
Roof Top Unit
PROJECT #: MN2687
Test Date: August 05, 2014
SYSTEM/UNIT: RTU-REEBOK-02 (Cont.)
AREA: RETAIL/BACKROOM
Tested By: Charles Bruner
RTU-REEBOK-02 Supply Outlet Summary
AK
Factor
% Final
Diff.
Final
Airflow
Prelim
Airflow
Design
Airflow
InstrumentSize Outlet
Type
Area ServedSystem / Unit
RETAIL RCD8Outlet-01 1.00200100HOOD200175
RETAIL RCD8Outlet-02 1.0018593HOOD200165
RETAIL RCD8Outlet-03 1.00205103HOOD200285
RETAIL RCD8Outlet-04 1.00215108HOOD200280
RETAIL RCD8Outlet-05 1.00205103HOOD200315
RETAIL RCD8Outlet-06 1.00200100HOOD200265
BACKROOM RCD10Outlet-07 1.0023594HOOD250315
BACKROOM RCD10Outlet-08 1.0024598HOOD250283
BACKROOM RCD10Outlet-09 1.0022590HOOD250169
BACKROOM RCD10Outlet-10 1.0022590HOOD250149
OFFICE SAD8Outlet-11 *1.0010653HOOD20075
BACKROOM RCD8Outlet-12 1.0018090HOOD200169
RESTROOM SAD8Outlet-13 *1.005680HOOD7051
----- 2,670 2,696 2,482Totals : 93 %
31-Jul-14 DAMPER IS 100% OPEN. RTU-REEBOK-02 /
Outlet-11
Charles Bruner
31-Jul-14 MOTORIZED DAMPER WAS NOT POWERED UP. RTU-REEBOK-02 /
Outlet-11
Charles Bruner
31-Jul-14 DAMPER IS 100% OPEN. RTU-REEBOK-02 /
Outlet-13
Charles Bruner
* Notes
International Test & Balance, Inc. Page 4 of 6
PROJECT: REEBOK
LOCATION: EAGAN, MN
DATE: 8/6/2014
CONTACT: Charles Bruner
Fan Unit
PROJECT #: MN2687
Test Date: July 31, 2014
SYSTEM/UNIT: EF-01
AREA: Changing Room
Tested By: Charles Bruner
Unit Data
Fan Manufacturer LOREN COOK
Fan Model Number 80 ACEB
Fan Serial Number 297SF32373-00/0000701
Test Data
Design Airflow 400 CFM
Actual Airflow 416 CFM
Design RPM 1257 RPM
Actual RPM 1420 RPM
Motor Volts T1-T2 121 Volts
Motor Amps T1 4.34 Amps
Discharge SP ATMOSPHERE in. wc
Motor Data
Rated Airflow Capacity 400 CFM
Motor Manufacturer US motor
Motor HP 1/4 HP
Motor RPM 1725 RPM
Motor Rated Volts 115 Volts
Motor Phase 1
Motor Hertz 60 Hz
Motor FL Amps 4.90 Amps
Motor Service Factor 1.35
Sheave Data
Motor Sheave MFG Browning
Motor Sheave Model 1VP34
Motor Sheave Diam.OD 3 1/8
Motor Sheave Bore 1/2
Fan Sheave MFG Baldor
Fan Sheave Model AK47/MA40
Fan Sheave Diam. OD 3.95
Fan Sheave Diam. PD 3.20
Fan Sheave Bore 3/4
Number of Belts 1
Belt Size A24
Sheave Center Line IDLER
EF-01 Exhaust Inlet Summary
% Final
Diff.
InstrumentActual
Velocit
Final
Airflow
Prelim
Airflow
Design
Airflow
Size Inlet
Type
Area ServedSystem / Unit
MENS EAD12x12Inlet-01 1030HOOD200100205
WOMEN'S EAD12x12Inlet-02 1060HOOD200109211
----- 400 209 416Totals : 104 %
* Notes
International Test & Balance, Inc. Page 5 of 6
PROJECT: REEBOK
LOCATION: EAGAN, MN
DATE: 8/6/2014
CONTACT: Charles Bruner
Fan Unit
PROJECT #: MN2687
Test Date: August 03, 2014
SYSTEM/UNIT: EF-01-1
AREA: RESTROOMS
Tested By: Charles Bruner
Unit Data
Fan Manufacturer GREENHECK
Fan Model Number SP-B110
Test Data
Actual Airflow 100 CFM
Design RPM 950 RPM
Actual RPM 950 RPM
Motor Volts T1-T2 121 Volts
Motor Data
Motor Manufacturer Fasco
Motor HP 1/4 HP
Motor RPM 950 RPM
Motor Rated Volts 115 Volts
Motor Phase 1
Motor Hertz 60 Hz
Motor FL Amps 1.50 Amps
Sheave Data
Motor Sheave MFG Direct Drive
Motor Sheave Model Direct Drive
Motor Sheave Diam.OD Direct Drive
Motor Sheave Bore Direct Drive
Fan Sheave MFG Direct Drive
Fan Sheave Model Direct Drive
Fan Sheave Diam. OD Direct Drive
Fan Sheave Diam. PD DIRECT DRIVE
Fan Sheave Bore DIRECT DRIVE
Number of Belts Direct Drive
Belt Size Direct Drive
Sheave Center Line Direct Drive
* Notes
International Test & Balance, Inc. Page 6 of 6