3925 Eagan Outlets Pkwy - Ste 805 - Robert Graham17135 W. 10 Mile Road 380 Northwest Highway 8401 73rd Ave North
Suite 112 Suite 210 Suite E-8
Southfield, MI 48075 Des Plaines, IL 60016 Minneapolis, MN 55428
Phone (248) 559-5864 Phone (847)759-1800 Phone (763) 533-8882
ROBERT GRAHAM
EAGAN, MINNESOTA
AIR TESTING & BALANCING REPORTS
ITB PROJECT #: MN2771
JOB NAME:ROBERT GRAHAM
LOCATION:EAGAN, MINNESOTA
I.T.B. PROJECT #:MN2771
DATE:9/14
THE DATA PRESENTED IN THIS REPORT IS AN EXACT RECORD OF SYSTEM PERFORMANCE AND WAS
OBTAINED IN ACCORDANCE WITH NEBB STANDARD PROCEDURES. ANY VARIANCES FROM DESIGN
QUANTITIES WHICH EXCEED NEBB TOLERANCES ARE NOTED THROUGHOUT THIS REPORT.
THE AIR DISTRIBUTION SYSTEMS HAVE BEEN TESTED & BALANCED AND FINAL ADJUSTMENTS HAVE BEEN
MADE IN ACCORDANCE WITH NEBB "PROCEDURAL STANDARDS FOR TESTING, ADJUSTING, BALANCING
OF ENVIRONMENTAL SYSTEMS" AND THE PROJECT SPECIFICATIONS.
ICB/NEBB FIRM:INTERNATIONAL TEST & BALANCE INC.
CERTIFIED BY:CHARLES BRUNER DATE:9/18/2014
THE HYDRONIC DISTRIBUTION SYSTEMS HAVE BEEN TESTED & BALANCED AND FINAL ADJUSTMENTS HAVE
BEEN MADE IN ACCORDANCE WITH NEBB "PROCEDURAL STANDARDS FOR TESTING, ADJUSTING, BALANCING
OF ENVIRONMENTAL SYSTEMS" AND THE PROJECT SPECIFICATIONS.
ICB/NEBB FIRM :INTERNATIONAL TEST & BALANCE INC.
CERTIFIED BY: DATE:
SUBMITTED & CERTIFIED BY:
INTERNATIONAL TEST & BALANCE, INC.
NEBB CERTIFIED: CHARLES BRUNER
SIGNATURE:
DATE:9/18/14 CERTIFICATION EXPIRATION DATE:
CERTIFICATION
INTERNATIONAL TEST & BALANCE, INC.
8401 73rd Avenue, N., Suite E-8
Minneapolis, MN 55428
Voice (763) 533-8882 Fax (763) 533-8933
PROJECT: ROBERT GRAHAM
LOCATION: EAGAN, MN
DATE: 9/18/2014
CONTACT: Charles Bruner
Roof Top Unit
PROJECT #: MN2771
Test Date: September 17, 2014
SYSTEM/UNIT: RTU-01
AREA: SPACE #805
Tested By: Charles Bruner
Unit Data
Unit Manufacturer LENNOX
Type DRAW-THRU
Blade Type FC
Class NOT LISTED
Filter Data 4-20x25x2
Starter Data
Starter Size N/A
Heater Size N/A
Heater Rating N/A Amps
Test Data
Design System Total CFM 3400 CFM
Actual System Total CFM 3371 CFM
Design Return Air CFM N/A CFM
Actual Return Air CFM 2744 CFM
Design Outdoor Air CFM 680 CFM
Actual Outdoor Air CFM 627 CFM
Design Outlet Total CFM 3400 CFM
Actual Outlet Total CFM 3371 CFM
Design T.F.S.P.1" wc ESP in. wc
Design Fan RPM N/A RPM
Design Motor RPM 1755 RPM
Design Voltage/Phase 460/3 VOLTS
Actual Voltage/Phase 482-482-483 VOLTS
Design Amperage 2.9 AMPS
Actual Amperage 3.3-3.3-3.2 AMPS
Design Brake Horsepower 3.75 BHP
Actual Brake Horsepower 2.36 BHP
Design Hertz 60 HZ
Actual Hertz 60 HZ
O.A. Damper Position 15 %
R.A. Damper Position 85 %
S.P. Set Point N/A
Motor Data
Motor Manufacturer INTERLINK
Motor Serial #N/A
Frame Size 56HZ
Service Factor 1.15
Horsepower 2
Sheave Data
Motor Sheave 1VP34
Motor Sheave OD 3.15 in.
Motor Bore Size 7/8 in.
Fan Sheave MA58
Fan Sheave PD 5.50 in.
Fan Sheave OD 5.75 in.
Fan Bore Size 1 in.
Shaft Centers 21 1/2 in.
Belt Quantity 1
International Test & Balance, Inc. Page 1 of 4
PROJECT: ROBERT GRAHAM
LOCATION: EAGAN, MN
DATE: 9/18/2014
CONTACT: Charles Bruner
Roof Top Unit
PROJECT #: MN2771
Test Date: September 17, 2014
SYSTEM/UNIT: RTU-01 (Cont.)
AREA: SPACE #805
Tested By: Charles Bruner
RTU-01 Supply Outlet Summary
AK
Factor
% Final
Diff.
Final
Airflow
Prelim
Airflow
Design
Airflow
InstrumentSize Outlet
Type
Area ServedSystem / Unit
RETAIL SAD12x12Outlet-01 1.00191109HOOD1750
RETAIL SAG18x6Outlet-02 0.54357110RVA3250
RETAIL SAG8x8Outlet-03 0.31163109RVA1500
RETAIL SAG18x6Outlet-04 0.54349107RVA3250
RETAIL SAG16x6Outlet-05 0.47245109RVA2250
RETAIL SAG8x8Outlet-06 0.31156104RVA1500
RETAIL SAG18x6Outlet-07 0.5429390RVA3250
RETAIL SAG16x6Outlet-08 0.4720390RVA2250
RETAIL SAG18x6Outlet-09 0.5431095RVA3250
RETAIL SAG16x6Outlet-10 0.4722399RVA2250
BACK STORAGESAG18x6Outlet-11 0.5428796RVA3000
BACK STORAGESAG18x6Outlet-12 0.5427391RVA3000
BACK STORAGESAG8x6Outlet-13 0.2313590RVA1500
FITTING ROOMSSAG8x6Outlet-14 0.2318693RVA2000
----- 3,400 - 3,371Totals : 99 %
17-Sep-14 THE FILTERS HAD TO BE TAKEN OUT BECAUSE
OF BEING DIRTY AND PLUGGED
RTU-01 Charles Bruner* Notes
International Test & Balance, Inc. Page 2 of 4
PROJECT: ROBERT GRAHAM
LOCATION: EAGAN, MN
DATE: 9/18/2014
CONTACT: Charles Bruner
Fan Unit
PROJECT #: MN2771
Test Date: September 17, 2014
SYSTEM/UNIT: EF-01
AREA: RESTROOM
Tested By: Charles Bruner
Unit Data
Fan Manufacturer GREENHECK
Fan Model Number SP-B110
Starter Data
Starter Manufacturer N/A
Starter Model No.N/A
Starter Size N/A
Rated Amps N/A Amps
Required Amps N/A Amps
Test Data
Design Airflow 100 CFM
Actual Airflow 122 CFM
Design RPM 950 RPM
Actual RPM 950 RPM
Motor Volts T1-T2 120 Volts
Motor Volts T2-T3 N/A Volts
Motor Volts T1-T3 N/A Volts
Motor Amps T1 N/A Amps
Motor Amps T2 N/A Amps
Motor Amps T3 N/A Amps
Suction SP N/A in. wc
Discharge SP N/A in. wc
Motor Data
Rated Airflow Capacity 100 CFM
Motor Manufacturer Fasco
Motor Frame Not Listed
Motor RPM 950 RPM
Motor Rated Volts 115 Volts
Motor Phase 1
Motor Hertz 60 Hz
Motor FL Amps 1.00 Amps
Motor Service Factor N/A
Brake Horse Power ? BHP
Corrected FL Amps ? Amps
Nominal Efficiency Not listed %
Power Factor Not Listed
Sheave Data
Motor Sheave MFG Direct Drive
Motor Sheave Model Direct Drive
Motor Sheave Diam.OD Direct Drive
Motor Sheave Bore Direct Drive
Fan Sheave MFG Direct Drive
Fan Sheave Model Direct Drive
Fan Sheave Diam. OD Direct Drive
Fan Sheave Diam. PD DIRECT DRIVE
Fan Sheave Bore DIRECT DRIVE
Number of Belts Direct Drive
Belt Size Direct Drive
Sheave Center Line Direct Drive
17-Sep-14 COULDN'T FIND A SPEED CONTROLLER AND
NO ACCESS TO TAKE AMPS AND VOLTS
EF-01 Charles Bruner
17-Sep-14 TOOK A READING ON A PLASTIC GRILLE WITH A
HOOD
EF-01 Charles Bruner
* Notes
International Test & Balance, Inc. Page 3 of 4
PROJECT: ROBERT GRAHAM
LOCATION: EAGAN, MN
DATE: 9/18/2014
CONTACT: Charles Bruner
Fan Coil
PROJECT #: MN2771
Test Date: September 17, 2014
SYSTEM/UNIT: ACU-01
AREA: DOOR CURTAIN
Tested By: Charles Bruner
Unit Data
Unit Manufacturer REDD-I
Filter Manufacturer NONE INSTALLED
Filter Type N/A
Filter Qty - S1 N/A
Filter Size - S1 N/A
Test Data
Design Airflow 750 CFM
Actual Airflow 862 CFM
Design RPM NOT LISTED RPM
Actual RPM N/A RPM
Motor Volts T1-T2 287 Volts
Motor Volts T2-T3 N/A Volts
Motor Volts T1-T3 N/A Volts
Motor Amps T2 N/A Amps
Motor Amps T3 N/A Amps
Design O/A N/A CFM
Actual O/A N/A CFM
Motor Data
Motor Manufacturer Not Listed
Motor Type Direct Drive
Motor Frame N/A
Motor HP Not Listed HP
Motor RPM Not Listed RPM
Motor Rated Volts 277 Volts
Motor Phase 1
Motor Hertz 60 Hz
Nominal Efficiency NOT LISTED %
Power Factor NOT LISTED
Sheave Data
Motor Sheave MFG Direct Drive
Motor Sheave Model Direct Drive
Motor Sheave Diam.Direct Drive in.
Motor Sheave Bore Direct Drive in.
Fan Sheave MFG Direct Drive
Fan Sheave Model Direct Drive
Fan Sheave Diam.Direct Drive in.
Fan Sheave Bore Direct Drive in.
Number of Belts Direct Drive
Belt Size Direct Drive
Sheave Center Line DIRECT DRIVE in.
17-Sep-14 COULDN'T LOCATE A SPEED CONTROLLER ACU-01 Charles Bruner
17-Sep-14 WE HAVE TAKEN A VELGRID READING ON THE
OPEN END DUCT 16x12 FOR 1.333 SQFT x 647
AFPM = 862 CFM
ACU-01 Charles Bruner
* Notes
International Test & Balance, Inc. Page 4 of 4