655 Lone Oak Dr - Building H - Balance Report 2015-04-13Michaud Cooley Erickson Engineer Shadegg Mechanical, Inc. Architectural Alliance 9534 Shadegg Mechanical, Inc. 225 Bridgepoint Drive Michael Lancette National Environmental Balancing Bureau NEBB Certification No. 2483 Eagan, MN 55121 Bal Tech, Inc 303 - 21st Street - Suite 109 - St.Paul, MN 55055 - Phone: (651) 459-2325 Fax: (651) 459-6618 Specialists in BALancing TECHnology of Environmental Systems Email: mail@Bal-Tech.net Web: http://www.Bal-Tech.net File Number prepared for Certified Test ; Adjust; Balance Report EcoLab SEL Lab 655 Lone Oak Drive - Bldg H South St. Paul, MN 55075 651-292-9933 HVAC Contractor NEBB TAB Certified Professional Prepared by: Report Date Architect April 13, 2015 Page 1 of 16 REPORT CERTIFICATION BTI FILE NUMBER: 9534 PROJECT: EcoLab SEL Lab "THE DATA PRESENTED IN THIS REPORT IS A RECORD OF SYSTEM MEASUREMENTS AND FINAL ADJUSTMENTS THAT HAVE BEEN OBTAINED IN ACCORDANCE WITH THE CURRENT ADDITION OF THE NEBB PROCEDURAL STANDARDS FOR TESTING ADJUSTING, AND BALANCING OF ENVIRONMENTAL SYSTEMS . ANY VARIANCES FROM DESIGN QUANTITIES WHICH EXCEED NEBB TOLERANCES ARE NOTED IN THE TEST- ADJUST - BALANCE REPORT PROJECT SUMMARY." SUBMITTED & CERTIFIED BY: NEBB FIRM: BAL TECH, INC. NEBB CERTIFIED PROFESSIONAL: MICHAEL L. LANCETTE SIGNATURE: REG. NO.: 2483 DATE: NEBB Certification Seal April 13, 2015 Page 2 of 16 Bal Tech, Inc.Instrument Calibration BTI File Number: 9534 Project Name: EcoLab SEL Lab Instrument Type Calibrated Monarch 200 / 1856054 05/13/14 05/13/14 To 05/13/15 Air, Immersion, Contact Shortridge ADM-860C / M07462 08/27/14 08/27/14 To 08/27/15 Air Alnor 9565-P / 9565P1450025 12/12/14 12/12/14 To 12/12/15 966 Temperature Probe Alnor 966 / P07330027 12/11/14 12/11/14 To 12/11/15 Electronic Measurement Volts, Amperes - AC, DC 12/12/14 12/12/14 To 12/12/15 Amperes - AC, DC i200 / 111587 12/12/14 12/12/14 To 12/12/15 Air Pressure, Air Velocity Measurement Shortridge ADM-860C / M07462 08/27/14 08/27/14 To 08/27/15 Air Pressure, Air Velocity Measurement Alnor 9565-P / 9565P1450025 12/12/14 12/12/14 To 12/12/15 Air Velocity Measurement Probe Alnor 966 / P07330027 12/11/14 12/11/14 To 12/11/15 Air Velocity Measurement - RVA Alnor RVA-801 / A03226 12/05/14 12/05/14 To 12/05/15 Air Volume Measurement (Direct Reading Hood) Shortridge ADM-860C / M07462 08/27/14 08/27/14 To 08/27/15 Pitot Tubes 18" Dwyer 160-18 N/A 36" Dwyer 160-36 N/A 48" Dwyer 160-48 N/A 60" Dwyer 160-60 N/A Hydronic Pressure Measurement -30InHg to 30Psi USG Solfrunt / 5348-1 12/12/14 12/12/14 To 12/12/15 0 to 100in.w.g., 100ft.w.g. Alnor HM-670 / 70748043 12/12/14 12/12/14 To 12/12/15 Hydronic Differential Pressure Measurement 0 to 100in.w.g., 100ft.w.g. Alnor HM-670 / 70748043 12/12/14 12/12/14 To 12/12/15 Fluke Temperature Measurement Fluke 179 / 21760286 Rotating Measurement Manufacturer Model / Serial No. Dates of use Page 3 of 16 Bal Tech, Inc.General Information BTI File Number:9534 Project Name:EcoLab SEL Lab Project Address: 655 Lone Oak Drive - Bldg H Eagan, MN 55121 Supervisor Review Date: Completion Date: Client information Consultants / Contractor information Technician & Professional Qualifications Shadegg Mechanical, Inc. Certified Technician: 225 Bridgepoint Drive Qualified Professional: Michael Lancette South St. Paul, MN 55075 651-292-9933 NEBB Exp. Date: Contact: Abbreviations This is a list of abbreviations and their definitions used in this report AHU Air Handling Unit LAT Leaving air Temperature BAS Building Automation System Lvg. Leaving BHP Brake Horse Power LWT Leaving Water Temperature BTI Bal Tech Inc M.A. Mixed Air CFLA Corrected Full Load Amps MAX Maximum CFM Cubic Feet per Minute MIN Minimum D.A. Discharge Air MTR Motor DB Dry Bulb N/A: Not Applicable DDC Direct Digital Control NEBB National Environmental Balancing Bureau EAT Entering air Temperature O.A. Outside Air EF Exhaust Fan OBD Opposed Blade Damper EFF Efficiency P.F. Power Factor Ent. Entering PSI Pounds per Square Inch EWT Entering Water Temp R.A. Return Air F.L. Full Load RF Return Fan FH Flow Hood RPM Revolutions Per Minute FPM Feet Per Minute RTU Roof Top Unit GPM Gallons Per Minute SF Supply Fan HP Horse Power SP Static Pressure HVAC Heating Ventilating And Air-conditioning TAB Test And Balance HZ Hertz TEMP Temperature IAQ Indoor Air Quality TSP Total Static Pressure KW Kilowatt VAV Variable Air Volume L/s Liters Per Second W.G Water Gage WB Wet Bulb April 13, 2015 Eric Hagler Architect Engineer HVAC Contractor 3/31/17 Michaud Cooley Erickson Dan McNamara Architectural Alliance April 10, 2015 Shadegg Mechanical, Inc. Page 4 of 16 Bal Tech, Inc.Table of contents BTI File Number: 9534 Project Name: EcoLab SEL Lab Item System Name Description Pages 1 All Report Summary 6 2 VAV 1-23 Supply VAV Test Data 7 3 VAV 1-24 Supply VAV Test Data 8 4 VAV 1-25 Supply VAV Test Data 9 5 VAV 1-26 Supply VAV Test Data 10 6 Ex EF-H7 Fume Hood Exhaust Fan Test Data 11 - 14 7 Ex EF-H9 Fume Hood Exhaust Fan Test Data 15 8 Heating Water VAV Heating Water Test Data 16 Page 5 of 16 Bal Tech, Inc. BTI File Number: 9534 Report Summary / Remarks Project Name: EcoLab SEL Lab The following is a summary of all systems that exceed NEBB / Contract Document Tolerances or any item that requires discussion / explanation. Item All Systems: 1.0 1.1 Each type of HVAC system is designed to meet a set of performance parameters. This usually includes maximum heating capacity and maximum cooling capacity. Bal Tech's intent is to normally set-up a system in its maximum capacity, or “full load” condition prior to the TAB process. 2.0 Discussion: System: Ex EF-H7 Report Page: 11 2.1 Existing fan CFM obtained with two hoods at maximum air volume (27" sash height) and the third at minimum. 3.0 Explanation: System: EF-H9 Report Page: 15 3.1 Duct static pressure control setpoint at -0.30 in. w.g. 3.2 Test #1 performed with canopy hoods open in what would appear to be the worst-case scenario. All canopies were open on the farthest main duct (closest to fume hoods) and canopies open at the end of the other mains. Duct static pressure at -.30 in. w.g. at the time of "test #1" readings (19 canopies open total) 3.3 Test #2 performed with every other canopy hoods open, 1/2 open per main duct. Duct static pressure at -0.15 in. w.g. at the the time of "test #2" readings (18 canopies open total). 4.0 Discussion: System: Heating Water Report Page: 16 4.1 VAV 1-26 coil was verified to be heating, however flow through the coil was reversed due to piping at the time of testing. Page 6 of 16 Bal Tech, Inc.Variable Volume Terminal Test Data (Pressure Independent) BTI File Number: 9534 Project Name: EcoLab SEL Lab System Number:AHU H-1 Start Date: Calibrated: Readings By: Design / Submittals Data VAV terminal designation: 4-23 Scheduled max airflow: 2000 Terminal type: Pressure Independent Scheduled min airflow: 500 Size: 12 Actual / Test Data Actual BAS airflow VAV Parameters: Final maximum airflow: 2006 2000 100% DDC duct area: 0.79 DDC flow calibration factor: 2.00 Outlet / Test Data Opening Location Size Factor VEL CFM VEL CFM %VEL CFM VAV#4-23 1 SEL Lab FH 1.63 245 400 301 492 123% 276 451 2 SEL Lab FH 1.63 245 400 297 485 121% 265 433 3 SEL Lab FH 1.63 245 400 265 433 108% 240 392 4 SEL Lab FH 1.63 245 400 204 333 83% 178 291 5 SEL Lab FH 1.63 245 400 156 255 64% 130 212 VAV Total: 2000 1998 100% 1779 Total CFM Traverse: FH 0.79 2548 2000 2555 2006 100% 2269 1781 Comments: #1 Final CFM achieved with AHU duct static at 1.70 in. w.c. on BAS. 4/10/2015 4/10/2015 Eric Hagler <----- Design -----> <---------- Final ----------> <-- Preliminary --> Page 7 of 16 Bal Tech, Inc.Variable Volume Terminal Test Data (Pressure Independent) BTI File Number: 9534 Project Name: EcoLab SEL Lab System Number:AHU H-1 Start Date: Calibrated: Readings By: Design / Submittals Data VAV terminal designation: 4-24 Scheduled max airflow: 2000 Terminal type: Pressure Independent Scheduled min airflow: 500 Size: 12 Actual / Test Data Actual BAS airflow VAV Parameters: Final maximum airflow: 2035 2013 101% DDC duct area: 0.79 DDC flow K-factor 2.05 Outlet / Test Data Opening Location Size Factor VEL CFM VEL CFM %VEL CFM VAV#4-24 1 SEL Lab FH 1.00 400 400 490 490 123% 395 395 2 SEL Lab FH 1.00 400 400 495 495 124% 430 430 3 SEL Lab FH 1.00 400 400 453 453 113% 403 403 4 SEL Lab FH 1.00 400 400 357 357 89% 329 329 5 SEL Lab FH 1.00 400 400 240 240 60% 205 205 VAV Total: 2000 2035 102% 1762 Total CFM Traverse: FH 0.79 2548 2000 2593 2036 102% 2245 1762 Comments: #1 Final CFM achieved with AHU duct static at 1.70 in. w.c. on BAS. 4/10/2015 4/10/2015 Eric Hagler <----- Design -----> <---------- Final ----------> <-- Preliminary --> Page 8 of 16 Bal Tech, Inc.Variable Volume Terminal Test Data (Pressure Independent) BTI File Number: 9534 Project Name: EcoLab SEL Lab System Number:AHU H-1 Start Date: Calibrated: Readings By: Design / Submittals Data VAV terminal designation: 4-25 Scheduled max airflow: 2000 Terminal type: Pressure Independent Scheduled min airflow: 500 Size: 12 Actual / Test Data Actual BAS airflow VAV Parameters: Final maximum airflow: 1997 1996 100% DDC duct area: 0.79 DDC flow K-factor: 1.97 Outlet / Test Data Opening Location Size Factor VEL CFM VEL CFM %VEL CFM VAV#4-25 1 SEL Lab FH 1.00 400 400 467 467 117% 437 437 2 SEL Lab FH 1.00 400 400 465 465 116% 421 421 3 SEL Lab 24x24 1.63 245 400 290 474 118% 247 404 4 SEL Lab FH 1.00 400 400 293 293 73% 256 256 5 SEL Lab FH 1.00 400 400 241 241 60% 217 217 VAV Total: 2000 1940 97% 1735 Total CFM Traverse: FH 0.79 2548 2000 2544 1997 100% 2214 1738 Comments: #1 Final CFM achieved with AHU duct static at 1.70 in. w.c. on BAS. 4/10/2015 4/10/2015 Eric Hagler <----- Design -----> <---------- Final ----------> <-- Preliminary --> Page 9 of 16 Bal Tech, Inc.Variable Volume Terminal Test Data (Pressure Independent) BTI File Number: 9534 Project Name: EcoLab SEL Lab System Number:AHU H-1 Start Date: Calibrated: Readings By: Design / Submittals Data VAV terminal designation: 4-26 Scheduled max airflow: 2000 Terminal type: Pressure Independent Scheduled min airflow: 500 Size: 12 Actual / Test Data Actual BAS airflow VAV Parameters: Final maximum airflow: 1831 1890 97% DDC duct area: 0.79 DDC flow calibration factor: 4.70 Outlet / Test Data Opening Location Size Factor VEL CFM VEL CFM %VEL CFM VAV#4-26 1 SEL Lab FH 1.00 400 400 451 451 113% 297 297 2 SEL Lab FH 1.00 400 400 452 452 113% 304 304 3 SEL Lab FH 1.00 400 400 431 431 108% 288 288 4 SEL Lab FH 1.00 400 400 300 300 75% 243 243 5 SEL Lab FH 1.00 400 400 197 197 49% 152 152 VAV Total: 2000 1831 92% 1284 Comments: #1 Final CFM achieved with AHU duct static at 1.70 in. w.c. on BAS. 4/10/2015 4/10/2015 Eric Hagler <----- Design -----> <---------- Final ----------> <-- Preliminary --> Page 10 of 16 Bal Tech, Inc.Fan Test Data (Belt Drive) BTI File Number: 9534 Project Name: EcoLab SEL Lab System Number: Ex EF-H7 Start Date: Test Date: Readings By: Unit /Submittal Data Other Data Unit Designation: Ex EF-H7 Motor sheave OD / bore: 5" 1 3/16" Manufacturer: Greenheck Fan sheave OD / bore: 4" 7/8" Model number: 18-AFSW-21-X Description Design /Submittal Data Actual / Test Data Total fan airflow: 3600 3042 Total SP: 1 1.30 " TSP Fan rpm: 1388 1385 Fan motor HP (kW): 2 2 Fan motor rpm: 1730 1760 Fan motor service factor / phase: 1.15 3 1.15 (SF) 3 (Phase) Fan motor rated amperage: 2.9 1.8 1.8 1.8 Fan motor voltage: 460 402 402 402 Fan motor BHP: 1.06 1.08 Fan motor operating HZ: 60 60 Static Pressure Profile In Out Total Fan: -1.20 0.10 Rise = 1.30 Air Balance Data EVAV# Size Factor VEL CFM VEL CFM EVAV 1-06 64x27 13.7 99 1360 99 1360 EVAV 1-07 64x27 13.7 98 1342 98 1342 EVAV 1-08 12"rd 0.79 433 340 433 340 Total:3042 3042 Comments: #1 Existing fan CFM obtained with two hoods at maximum air volume (27" sash height) and the third at minimum. 4/10/2015 4/10/2015 Eric Hagler <---- Final ----> <- Preliminary -> Page 11 of 16 Bal Tech, Inc.Fume Hood EV Test Data BTI File Number: 9534 Project Name: EcoLab SEL Lab System Number: Ex EF-H7 Start Date: Calibrated: Readings By: Design / Submittals Data Room Number: SEL Lab Design maximum airflow: 1290 VAV Size: 16 Actual Airflow / Test Data Final TAB maximum airflow: 1360 Actual Face Velocity: 99 Fume Hood Controller Face Velocity: 99 Hood / Test Data Opening Size Factor VEL CFM VEL CFM %VEL CFM EVAV#1-06 Hood Inflow (18" Sash Height): 64x27 13.7 94 1290 99 1360 105% 99 1360 Fume Hood Make / Model: Hamilton Fume Hood Type:Safeaire Sash Configuration 96 103 118 131 Sash test opening width: 64.0 inches 27" Sash test opening height: 27.0 inches 71 78 97 101 Final Face Velocity:99 AVG. F.P.M. Comments: #1 Face velocity calibration affected by upper sash opened above sensor port in hood. Port located 8 inches below top of sash opening. With sash fully open, air passes by sensor and actual velocity increases to 130 fpm with monitor reading 100 fpm. Monitor observed to be calibrated with sash below sensor port. Recommended action: Move sensor ports per installation instructions. 4/10/2015 4/10/2015 Eric Hagler <----- Design -----> <---------- Final ----------> <-- Preliminary --> Page 12 of 16 Bal Tech, Inc.Fume Hood EV Test Data BTI File Number: 9534 Project Name: EcoLab SEL Lab System Number: Ex EF-H7 Start Date: Calibrated: Readings By: Design / Submittals Data Room Number: SEL Lab Design maximum airflow: 1290 VAV Size: 16 Actual Airflow / Test Data Final TAB maximum airflow: 1342 Actual Face Velocity: 98 Fume Hood Controller Face Velocity: 100 Hood / Test Data Opening Size Factor VEL CFM VEL CFM %VEL CFM EVAV#1-07 Hood Inflow (27" Sash Height): 64x27 13.7 94 1290 98 1342 104% 98 1342 Fume Hood Make / Model: Hamilton Fume Hood Type:Safeaire Sash Configuration 118 113 96 95 Sash test opening width: 64.0 inches 27" Sash test opening height: 27.0 inches 100 95 85 80 Final Face Velocity:98 AVG. F.P.M. Total CFM Duct Traverse: 12"rd 0.79 1643 1290 1709 1342 104% 1709 1342 Comments: #1 Face velocity calibration affected by upper sash opened above sensor port in hood. Port located 8 inches below top of sash opening. With sash fully open, air passes by sensor and actual velocity increases to 130 fpm with monitor reading 100 fpm. Monitor observed to be calibrated with sash below sensor port. Recommended action: Move sensor ports per installation instructions. 4/10/2015 4/10/2015 Eric Hagler <----- Design -----> <---------- Final ----------> <-- Preliminary --> Page 13 of 16 Bal Tech, Inc.Fume Hood EV Test Data BTI File Number: 9534 Project Name: EcoLab SEL Lab System Number: Ex EF-H7 Start Date: Calibrated: Readings By: Design / Submittals Data Room Number: SEL Lab Design maximum airflow: 1290 VAV Size: 16 Actual Airflow / Test Data Final TAB maximum airflow: 1371 Actual Face Velocity: 100 Fume Hood Controller Face Velocity: 102 Hood / Test Data Opening Size Factor VEL CFM VEL CFM %VEL CFM EVAV#1-08 Hood Inflow (18" Sash Height): 64x27 13.7 94 1290 100 1371 106% 100 1371 Fume Hood Make / Model: Hamilton Fume Hood Type:Safeaire Sash Configuration 123 102 106 107 Sash test opening width: 64.0 inches 27" Sash test opening height: 27.0 inches 107 94 77 85 Final Face Velocity:100 AVG. F.P.M. Comments: #1 Face velocity calibration affected by upper sash opened above sensor port in hood. Port located 8 inches below top of sash opening. With sash fully open, air passes by sensor and actual velocity increases to 130 fpm with monitor reading 100 fpm. Monitor observed to be calibrated with sash below sensor port. Recommended action: Move sensor ports per installation instructions. 4/10/2015 4/10/2015 Eric Hagler <----- Design -----> <---------- Final ----------> <-- Preliminary --> Page 14 of 16 Bal Tech, Inc.Fan Test Data (Belt Drive) BTI File Number: 9534 Project Name: EcoLab SEL Lab System Number: EF-H9 Start Date: Test Date: Readings By: Unit /Submittal Data Other Data Unit Designation: EF-H9 Motor sheave OD: 5" Manufacturer: Greenheck Fan sheave OD: 3" Model number: 27-CSW-AF-21 Serial number: 14063320 Description Design /Submittal Data Actual / Test Data Total fan airflow: 7800 8611 110% Fan rpm: 1070 756 Fan motor HP (kW): 5 5 Fan motor rpm: 1750 1255 Fan motor service factor / phase: 1.15 3 1.15 (SF) 3 (Phase) Fan motor rated amperage: 6.6 3.6 3.6 3.6 Fan motor voltage: 460 329 329 329 Fan motor BHP: 3.6 1.95 Fan motor operating HZ: 60 43 Outlet / Test Data Canopy Hood Location Size Factor VEL CFM VEL CFM 1 SEL Lab FH 1.10 245 270 124 136 2 SEL Lab FH 1.10 381 419 125 138 3 SEL Lab FH 1.10 366 403 202 222 4 SEL Lab FH 1.10 395 435 207 228 5 SEL Lab FH 1.10 434 477 202 222 6 SEL Lab FH 1.10 421 463 208 229 7 SEL Lab FH 1.10 517 569 286 315 8 SEL Lab FH 1.10 507 558 283 311 9 SEL Lab FH 1.10 449 494 365 402 10 SEL Lab FH 1.10 416 458 327 360 11 SEL Lab FH 1.10 426 469 365 402 12 SEL Lab FH 1.10 289 318 412 453 13 SEL Lab FH 1.10 333 366 437 481 14 SEL Lab FH 1.10 525 578 363 399 15 SEL Lab FH 1.10 504 554 406 447 16 SEL Lab FH 1.10 557 613 396 436 17 SEL Lab FH 1.10 545 600 553 608 18 SEL Lab FH 1.10 518 570 450 495 19 SEL Lab FH 1.10 -- -- 469 516 Total Fan CFM: 8611 6798 Comments: #1 Duct static pressure control setpoint at -0.30 in. w.g. #2 Test #1 performed with canopy hoods open in what would appear to be the worst-case scenario. All canopies were open on the farthest main duct (closest to fume hoods) and canopies open at the end of the other mains. Duct static pressure at -.30 in. w.g. at the time of "test #1" readings (19 canopies open total) #3 Test #2 performed with every other canopy hoods open, 1/2 open per main duct. Duct static pressure at -0.15 in. w.g. at the the time of "test #2" readings (18 canopies open total). Eric Hagler4/9/2015 4/10/2015 <-- Test #2 --> <-- Test #1 --> Page 15 of 16 Bal Tech, Inc.Hydronic balancing valve test data BTI File Number: 9534 Fixed or adjustable orifice Project Name: EcoLab SEL Lab System Number: Heating Water Start Date: Test Date: Water Balance Test Data Station Location Size PD GPM PD GPM %PD GPM VAV 1-23 SEL Lab 3/4" 2 - 50 5.0 10.2 5.0 100% 10.2 5.0 VAV 1-24 SEL Lab 3/4" 2 - 50 5.0 9.8 5.0 100% 9.8 5.0 VAV 1-25 SEL Lab 3/4" 2 - 50 5.0 9.9 5.0 100% 9.9 5.0 VAV 1-26 SEL Lab 3/4" 2 - 50 5.0 -- -- -- -- -- Comments: #1 VAV 1-26 coil was verified to be heating, however flow through the coil was reversed due to piping at the time of testing. 4/10/2015 4/10/2015 <----- Design -----> <---------- Final ----------> <-- Preliminary --> Page 16 of 16