Loading...
1992 Rahncliff Ct - Nothing Bundt Cakes TAB Report 2015-08-31 ` Technician: Cell Phone: Email Address: Peter Leptuch Report Date August 31, 2015 Allan Mechanical Contractors 7875 Fuller Road Eden Prairie, MN 55344 ENGINEER pete@premierbalancing.com PROJECT Nothing Bundt Cakes 1992 Rahncliff Court Eagan MN 55122 CLIENT 375 230th Ave, Somerset WI 54025 - Phone: (612) 834-0311 Fax: (414) 377-3349 www.Premierbalancing.com Testing, Adjusting & Balancing Report TABB TECHNICIAN Pete Korzenowski 612-834-0311 TABB CERTIFICATION TABB certification of a Supervisor is TABB's statement that the Supervisor is able to supervise testing, adjusting and balancing of building environmental systems to produce the design objectives or optimum system performance. For TABB Certification purposes, a Supervisor is the person who, while employed by a TABB Certified Contractor, is responsible and accountable for overseeing, coordinating and ensuring that projects are performed by TABB Certified Technicians in accordance with TABB standards (including the ICB Code of Conduct and the TAB General Rules). Measurements recorded in this report are in accordance with the SMACNA / TABB HVAC Systems, Testing, Adjusting and Balancing manual. TABB Certified "The Professional's Choice" Page 2 TABB QUALITY ASSURANCE PROGRAM BACKGROUND TABB seeks to ensure the integrity of its certification program by: (a) setting eligibility criteria for TABB Certified Supervisors and TABB Certified Contractors, (b) establishing testing procedures for TABB Certified Supervisors, (c) requiring continuing education and continuous compliance with eligibility criteria for renewal of certification, and (d) periodically reviewing its recognition of technician certification. High quality work on the part of TABB Certified Technicians and TABB Certified Supervisors and TABB Certified Contractors ( TABB Professionals ) is essential to integrity of the TABB Certification Program. TABB offers this TABB Quality Assurance Program to help assure high quality work. By accepting TABB qualification or certification, every TABB Professional accepts the responsibilities or this Program. Quality Assurance Every customer of a TABB Certified Contractor shall be entitled to expect: (1) that testing, adjusting and balancing work by the contractor and its TABB Professionals will meet TABB standards; (2) that testing, adjusting and balancing reports provided to the customer will have been prepared by a TABB Certified Technician, and reviewed by a TABB Certified Supervisor; and (3) that the report(s) will include measurements taken accurately with the date and mode of operation of the systems. TABB 8403 Arlington Boulevard Fairfax, VA 22031 Phone - (703) 299-5646 Fax - (703) 683-7615 TABB Certified "The Professional's Choice" Page 3 INSTRUMENT CALIBRATION REPORT Rotating Measuring Instrument Temperature Measuring Instrument Electrical Measuring Instruments Air Pressure Measuring Instrument Air Velocity Measuring Instrument Hydronic Pressure Measuring Instrument 0 to 300 psi Humidity Measuring Instrument MITCT917 Mitchell Instruments 100610809 01/19/15 HM-670 Alnor 71133088 01/21/15 ADM-870C Shortridge M12418 01/22/15 ADM-870C Shortridge M12418 01/22/15 322 Fluke 17830473 01/21/15 117 Fluke 18561871 01/21/15 ADM-870C Shortridge M12418 01/22/15 DATE PLT-5000 Mitchell Instruments B1488503 11/19/14 INSTRUMENT MODEL MANUFACTURER SERIAL NUMBER CALIBRATION TABB Certified "The Professional's Choice" Page 4 Index Project:Nothing Bundt Cakes Premier Job Number: Pete Korzenowski Report Date: Page 6 RTU-1 Constant Air Volume 7 RTU-2 Constant Air Volume 8 EF-1 Constant Air Volume 9 EF-2 Constant Air Volume 8/28/15 8/28/15 8/28/15 8/28/15 System / Equipment Description Completion Date Technician:8/31/15 Premier Test & Balance 4338 TABB Certified "The Professional's Choice" Page 5 Air Handling Unit Test Data Project:Nothing Bundt Cakes System:RTU-1 Premier Job Number: Pete Korzenowski Completion Date: Equipment Location: Motor HP:NA NA Motor RPM:1750 1750 Motor Hertz:60 60.0 Motor Service Factor:1.15 1.15 Motor Phase:3 3 Motor Voltage:208 205 205 207 Motor Amperage:9.4 4.9 4.9 5.1 Motor BHP:-- Fan RPM:-1290 Supply Total Opening Size K No.Factor Velocity CFM Velocity CFM %Velocity CFM 1 Flow Hood 1.00 200 200 324 324 162%475 475 2 Flow Hood 1.00 310 310 526 526 170%468 468 3 Flow Hood 1.00 250 250 372 372 149%473 473 4 Flow Hood 1.00 200 200 325 325 163%446 446 Total 960 1547 161%1862 Minimum Outside Air Size K Factor Velocity CFM Velocity CFM %Velocity CFM 28x14 2.72 64 175 71 189 108%45 123 Remarks:a)Fan sheave is set to lowest setting. b)Diffusers are not noisy so no problems anticipated. c) d) e) Design Final Reading Total Sales Sales Sales Sales Area Design Final Reading Served Total Design CFM:920 Min.Outside Air CFM: 175 Fan Static Pressure:Roof Premier Test & Balance System Scheduled Data Model number: 48KCEB04 Serial number: 2815C86776 Manufacturer:Carrier Preliminary Reading Preliminary Reading Airflow Measurements Performance Data Description Scheduled / Submittal Data Actual Field Measurements Outlet Total CFM: 960 4338 Technician:8/28/15 TABB Certified "The Professional's Choice" Page 6 Air Handling Unit Test Data Project:Nothing Bundt Cakes System:RTU-2 Premier Job Number: Pete Korzenowski Completion Date: Equipment Location: Motor HP:NA NA Motor RPM:1750 1750 Motor Hertz:60 60.0 Motor Service Factor:1.15 1.15 Motor Phase:3 3 Motor Voltage:208 205 205 203 Motor Amperage:9.4 6.2 6.2 6.5 Motor BHP:-- Fan RPM:-1355 Opening Size K No.Factor Velocity CFM Velocity CFM %Velocity CFM 1 Flow Hood 1.00 200 200 281 281 141%215 221 2 Flow Hood 1.00 250 250 343 343 137%372 372 3 Flow Hood 1.00 150 150 198 198 132%313 313 4 Flow Hood 1.00 300 300 389 389 130%386 386 5 Flow Hood 1.00 200 200 245 245 123%326 326 6 Flow Hood 1.00 300 300 370 370 123%312 321 7 Flow Hood 1.00 150 150 188 188 125%353 353 8 Flow Hood 1.00 50 50 63 63 126%89 89 Total 1600 2077 130%2381 Minimum Outside Air Size K Factor Velocity CFM Velocity CFM %Velocity CFM 28x14 2.72 119 325 128 348 107%70 191 Remarks:a)Fan sheave is set to lowest setting. b)Diffusers are not noisy so no problems anticipated. c) d) e) Preliminary Reading Total Design Final Reading Kitchen Kitchen Kitchen Kitchen Served Kitchen Kitchen Kitchen Kitchen Airflow Measurements Area Design Final Reading Preliminary Reading Fan Static Pressure:Roof Performance Data Description Scheduled / Submittal Data Actual Field Measurements Manufacturer:Carrier Outlet Total CFM: 1,600 Total Design CFM:1,600 Min.Outside Air CFM: 325 Premier Test & Balance 4338 Technician:8/28/15 System Scheduled Data Model number: 48KCEB06 Serial number: 2815C86867 TABB Certified "The Professional's Choice" Page 7 Fan Test Data Project:Nothing Bundt Cakes System:EF-1 Premier Job Number: Pete Korzenowski Completion Date: Motor HP:0.50 0.50 Motor RPM:1750 1750 Motor Hertz:60 60.0 Motor Service Factor:1.15 1.15 Motor Phase:1 1 Motor Voltage:120 117 Motor Amperage:6.2 5.1 Motor BHP:-0.40 Fan RPM:Direct Drive Direct Drive Fan: Fan Total Opening Size K No.Factor Velocity CFM Velocity CFM %Velocity CFM 1 8"0.35 1074 375 1095 382 102%1593 556 Total 375 382 102%556 Remarks:a)Speed controller was used to reduce flow. b) c) d) e) Served Various Airflow Measurements Area Design Final Reading Preliminary Reading In Out Rise / Drop Total -0.34 0.03 Rise 0.37 Performance Data Description Scheduled / Submittal Data Actual Field Measurements Static Pressure Data Component Static Pressure Pressure Pressure Fan Static Pressure:1.0 ESP Manufacturer:Greenheck Outlet Total CFM: 375 Total Design CFM:325 Equipment Location:Roof Technician:8/28/15 System Scheduled Data Model number: CUE-141HP-VG Serial number: 14218517 Premier Test & Balance 4338 TABB Certified "The Professional's Choice" Page 8 Fan Test Data Project:Nothing Bundt Cakes System:EF-2 Premier Job Number: Pete Korzenowski Completion Date: Motor HP:0.25 0.25 Motor RPM:1725 1725 Motor Hertz:60 60.0 Motor Service Factor:1.15 1.15 Motor Phase:1 1 Motor Voltage:120 118 Motor Amperage:3.4 2.8 Motor BHP:-0.20 Fan RPM:Direct Drive Direct Drive Fan: Fan Total Opening Size K No.Factor Velocity CFM Velocity CFM %Velocity CFM 1 Flow Hood 1.00 75 75 82 82 109%145 145 Total 75 82 109%145 Remarks:a)Speed controller was used to reduce flow. b) c) d) e) Served Various Airflow Measurements Area Design Final Reading Preliminary Reading -0.23 0.03 Rise 0.26 Static Pressure Data Component Static Pressure Pressure Pressure In Out Rise / Drop Total Performance Data Description Scheduled / Submittal Data Actual Field Measurements Total Design CFM:75 Equipment Location:Roof Fan Static Pressure:.5 ESP System Scheduled Data Model number: G-097-A Serial number: 14218518 Manufacturer:Greenheck Outlet Total CFM: 75 Premier Test & Balance 4338 Technician:8/28/15 TABB Certified "The Professional's Choice" Page 9