Loading...
3344 Promenade Ave - Crumb Deli HVAC Balance ReportAIR CONDITIONING ASSOCIATES INC 55 WEST IVY AVENUE ST PAUL, MN 55117 (651) 488-0291 Page 1 OF 3 PERMIT#EA130856 Air Outlet Test Report (Flow Hood) JOB NAME CRUMB DELI LOCATION 3344 PROMENADE AVE SYSTEM MUA, RTU'S AND EXH. CITY, STATE EAGAN, MN55121 TEST APPARATUS ALNOR ELECTRONIC BAL. & FLOW HOOD EQUIP ROOM #DESIGN FINAL PERCENT OF NO.OR AREA NO.TYPE SIZE AIRFLOW CFM (I/s) AIRFLOW CFM (I/s)OF DESIGN PRV-1 KITCHEN HOOD #1 1 B.I. DUCT 18"X8"1800 1750 97.2 EF-1 WOMENS ROOM 1 6" DIFF 6"100 100 100.0 EF-2 MENS ROOM 1 6" DIFF 6"100 100 100.0 TOTAL EXH 2000 1950 97.5 TOT MUA 1,800 1,825 103.1 DIFFERENCE -200 -125 Test Date 9/2/2015 Readings By BOB BONNELL Hvac Systems Testing, Adjusting & Balancing. Third Edition 16.15 OUTLET AIR CONDITIONING ASSOCIATES INC 55 WEST IVY AVENUE ST PAUL, MN 55117 (651) 488-0291 Page 2 OF 3 PERMIT#EA130856 Air Outlet Test Report (Flow Hood) JOB NAME CRUMB DELI LOCATION 3344 PROMENADE AVE SYSTEM MUA, RTU'S AND EXH. CITY, STATE EAGAN, MN55121 TEST APPARATUS ALNOR ELECTRONIC BAL. & FLOW HOOD EQUIP ROOM #DESIGN FINAL PERCENT OF NO.OR AREA NO.TYPE SIZE AIRFLOW CFM (I/s) AIRFLOW CFM (I/s)OF DESIGN MUA-1 KITCHEN HOOD #1 1 PSP 12"720 720 100 MUA-1 KITCHEN HOOD #1 2 PSP 12"720 725 101 MUA-1 KITCHEN HOOD #1 3 2'X2' PERF 12"360 380 106 TOT CFM'S 1800 1825 101.4 RTU-1 OSA 1 600 600 100.0 OSA RA=74 OSA=82 MA=75.6 (RAXOSA=MA) (74x.80=59.2)+(82x.20=16.4)=75.6 RTU-2 OSA 1 375 375 100.0 OSA RA=74 OSA=82 MA=75.0 (RAXOSA=MA) (74x.875=64.75)+(82x.125=10.25)=75.0 TOT MUA 2,775 2,800 100.9 TOTAL EXH 2,000 1,950 97.5 DIFFERENCE +775 +850 BLD PRESS .0125".02" Test Date 9/2/2015 Readings By BOB BONNELL Hvac Systems Testing, Adjusting & Balancing. Third Edition 16.15 OUTLET AIR CONDITIONING ASSOCIATES INC 55 WEST IVY AVENUE ST PAUL, MN 55117 (651) 488-0291 Page 3 OF 3 PERMIT#EA130856 Air Outlet Test Report (Flow Hood) JOB NAME CRUMB DELI LOCATION 3344 PROMENADE AVE SYSTEM MUA, RTU'S AND EXH. CITY, STATE EAGAN, MN55121 TEST APPARATUS ALNOR ELECTRONIC BAL. & FLOW HOOD EQUIP ROOM #DESIGN FINAL PERCENT OF NO.OR AREA NO.TYPE SIZE AIRFLOW CFM AIRFLOW OF DESIGN RTU-1 DINING ROOM 1 12"X6" DUCT DIFF 250 230 93 RTU-1 DINING ROOM 2 12"X6" DUCT DIFF 250 235 95 RTU-1 DINING ROOM 3 12"X6" DUCT DIFF 250 240 97 RTU-1 DINING ROOM 4 12"X6" DUCT DIFF 250 250 100 RTU-1 DINING ROOM 5 12"X6" DUCT DIFF 250 250 100 RTU-1 DINING ROOM 6 12"X6" DUCT DIFF 250 250 100 RTU-1 DINING ROOM 7 12"X6" DUCT DIFF 250 250 100 RTU-1 DINING ROOM 8 12"X6" DUCT DIFF 250 265 105 RTU-1 DINING ROOM 9 12"X6" DUCT DIFF 250 265 105 RTU-1 DINING ROOM 10 12"X6" DUCT DIFF 250 260 105 RTU-1 DINING ROOM 11 12"X6" DUCT DIFF 250 255 103 RTU-1 DINING ROOM 12 12"X6" DUCT DIFF 250 250 100 TOT CFM'S 3000 3000 100.0 RTU-2 KITCHEN 1 2'X2' LAY IN DIFF 10"410 400 97 RTU-2 KITCHEN 2 2'X2' LAY IN DIFF 10"410 400 97 RTU-2 KITCHEN 3 2'X2' LAY IN DIFF 10"410 420 102 RTU-2 OFFICE 4 2'X2' LAY IN DIFF 6"100 100 100 RTU-2 STORAGE 5 2'X2' LAY IN DIFF 6"100 100 100 RTU-2 HALLWAY 6 2'X2' LAY IN DIFF 8"190 190 100 RTU-2 WOMENS ROOM 7 2'X2' LAY IN DIFF 6"50 50 100 RTU-2 MENS ROOM 8 2'X2' LAY IN DIFF 6"100 100 100 RTU-2 KITCHEN 9 2'X2' LAY IN DIFF 10"410 415 101 RTU-2 KITCHEN 10 2'X2' LAY IN DIFF 10"410 415 101 RTU-2 KITCHEN 11 2'X2' LAY IN DIFF 10"410 410 100 TOT CFM'S 3000 3000 100.0 Test Date 9/2/2015 Readings By BOB BONNELL Hvac Systems Testing, Adjusting & Balancing. Third Edition 16.15 OUTLET