4200 Dodd Rd - Test & Balance Report 2016-01-11 111MDC
Mechanical Data Corporalion
January 11, 2016
Trace Plumbing & Heating
Attn: Trace
5005 90th Ave. N.E.
Spicer, MN 56288
RE: Eagan Fire Station
Trace,
Please find attached a copy of the test and balance report for the above
referenced project.
If you have any questions, please don't hesitate to call me.
Sincerely,
So&'Wo#Wou (1r)
Scott Hoffman
MECHANICAL DATA CORPORATION
SH/jt
cc: MDC File — 16040
6407 Cecilia Circle • Bloomington, MN 55439 • 952-473-1176 • Fax 952-473-2630
111MDC
Mechanical Data Corporation
"Test and Balancing"
The air distribution system(s) have
been tested and balanced to be totally
operational and within design tolerance by
Mechanical Data Corporation
Eagan Fire Station
for
Mechanical Contractor
Trace Plumbing & Heating
by
Mechanical Data Corporation
Bloomington, Minnesota
Test Engineer
Scott Hoffman
Certificate of Professional Independence
Associated Air Balance Council
TBE #05-04-32
Date
January 11, 2016
111MDC
Mechanical Data Corporation
CONCEPT THE
The prime definition of air conditioning, as stated in the American Society
of Heating, Refrigeration and Air Conditioning Engineers Guide, is the
process of treating air so as to control simultaneously its temperature,
humidity, movement, cleanliness, and final distribution to meet the
requirements of the space to be conditioned.
While each of the preceding air treatment processes individually contribute
a specific function of producing human comfort or space conditioning, in
practical application it is the coordinated action of all of these processes,
each related to and influencing the others, that produces the final desired
conditions.
It is easy to see that if one or the other of these coordinated functions is
not performing as it should, the final results of all will be affected. To
produce this coordinated function is the basic and scientific function of the
"Test and Balance Agency".
Associated Air Balance Council
1518 K Street N.W.
Washington, D.C. 20005
202-429-9440
Mechanical Data Corporation has been certified by the Associated Air
Balance Council to be a true, independent testing and balancing agency.
Mechanical Data Corporation has no financial ties or interplay with
contractors, suppliers or designers. This enables us to remain unbiased
professionals at all times.
Mechanical Data Corporation has been certified under certification number
112146. Branden Johnson is a registered test engineer under certification
number 05-04-32.
6407 Cecilia Circle - Bloomington, MN 55439 - 952-473-1176 - Fax 952-473-2630
—-.xxv,+ *v v' ': Pr s,«y;••n; „,y rx„ ,a• t�. ,�,••,P a �,oe+, " •«+ A b
LA
rgu� �'�,.! w} .�;yy•:*�+„y � r � Ai��i"t'4"� * 6a,.tt't rd 6 at m '+r '�' ,ff� #Y+a� Y� i '
£t, O��i �"d � �q'.y • y�1y$` ♦ 1 1 , 4 ..} , C' F Y , � r 1 � " p .•y, !: �e 11
f,
r3�r,rte +
r +
f
+
U t{
• R-4 L+ rs
fld
f�
''`"
Cd
Cd
4�f
{iP•,��y�N4 �•r� �jy C3 tj
f f
e ..+e'. C1 tier M4
+r
1 f f � + � f ♦ a ♦ .� e •� ♦ ,a•�:e. +#' +, .5'� •'+'��.,,!j �r" � a e .e � ,tea �.r�''
#� +• Yk • .,t+' ',' t4y�� ••�,�,•w,"•�4 �'m .f�,,,'4'+!, �� iw` ? 4r't %�9`���.� �/ =�"'.`s''��-...y"�.,. -.i.%\,. � �.z,�,.!'h`=rem%
'i d ti'c'das ':.•q ar'r'}j``, r��=4�✓ �v """..r�.;�,�`i"F`4., ;� ,,.�;, �. ``�"r' `�'Y`�'''
Mechanical Data 001paratlon
Test and Balance Report Review
The following report wa produc d by:
Scott Hoffman (Project Technician Signature)
The following report w s review y:
Branden Johnson (TBE Signature and stamp)
6
V �
777 7-
'j n . 0
d el n-
MENIL
111MDC
Mechanical Data corporation
INSTRUMENTATION
TEST EQUIPMENT
INSTRUMENT MODEL SERIAL NO CAL DATE
Fluke RMS DVM 8922A 4921050 NA
Airdata ADM-860 M 011024 8/20/15
Multimeter
Differential Barton 0 to 100" 12-0908 8/22/13
Water Meter
Capture Hood EBT731 EBT731308009 2/17/15
Balometer
Rotating Vane RVA801, A03168 10/14/14
Anemometer
Rotating Vane RVA801 A03169 10/15/14
Anemometer
ALL INSTRUMENTATION IS CALIBRATED PER THE
MANUFACTURES RECOMMENDATIONS
Page No. 1 of 10
Date: 1/11/2016
Mochanlca Data Oorparallon
Member of
Associated Air Balance Council
CONSTANT VOLUME SUPPLY FAN TEST
JOB NAME: EAGAN FIRE STATION
SYSTEM: RTU -1
MAKE AAON
I
I
MODEL RN-009
REQUIRED PRELIMINARY FINAL
CFM 2,975 3,192 2,980
VFD 60 Hz 53 Hz 53 Hz
FAN IN/OUT/TSP -/-/NA -.89/+.37/1.26 -.91/+.41/1.32
EXTERNAL S.P. 441.50 -.56/+.37/.93 -.58/+.41/.99
FILTER -/-/NA -.56/-.89/.33 (1) -.58/.91/.33 (1)
COOLING COIL -/-/NA -.56/-.89/.33 (1) -.58/.91/.33 (1)
FAN RPM Direct Drive Direct Drive Direct Drive
MOTOR RPM 1,760 1,555 1,555
MOTOR VOLTAGE 230 230 230
MOTOR AMPERAGE 6,8 3.8 3.8
MOTOR HORSEPOWER 2 2 2
OUTSIDE AIR DAMPER 360 CFM (20% @) 744 CFM (14% @) 389 CFM
POSITION
NOTES: (1) SP taken across filter and coil.
Page No. 2 of 10
Date: 1/11/2016
Meahanlap Dala CO/POIpiIOn
Member of
Associated Air Balance Council
DIFFUSER AND GRILL TEST
JOB NAME: EAGAN FIRE STATION
SYSTEM: RTU - 1
ROOM OUTLET OUTLET REQUIRED PRELIMINARY FINAL
NO. NO. SIZE VEL CFM VEL CFM VEL CFM
106 1-1 LD 1.0 500 500 322 322 507 507
105 1-2 LD 1.0 275 275 257 257 299 299
103 1-3 CD 1.0 375 375 469 469 392 392
103 1-4 CD 1.0 375 375 568 568 396 396
103 1-5 CD 1.0 375 375 599 599 357 357
103 1-6 CD 1.0 375 375 538 538 368 368
i
101 1-7 SD 1.0 600 600 344 344 552 552
102 1-8 CD 1.0 100 100 95 95 109 109
2975 3192 2980
i
I
i
i
I
i
I
NOTES:
I
i
i
Page No. 3 of 10
AdIft Date: 1/11/2016
Mechanical Data Corporation
Member of
Associated Air Balance Council
CONSTANT VOLUME SUPPLY FAN TEST
JOB NAME: EAGAN FIRE STATION
SYSTEM: RTU -2
MAKE AAON
MODEL RQ-004
REQUIRED PRELIMINARY FINAL
CFM 1,350 1,334 1,316
FAN IN/OUT/TSP -/-/NA -1.32/+.47/1.79 -1.40/+.59/1.99
EXTERNAL S.P. 441.25 -.86/+.47/1.33 -.90/+.59/1.49
FILTER -/-/NA -.86/-1.32/.46 (1) -.90/-1.40/.50 (1)
COOLING COIL -/-/NA -.86/-1.32/.46 (1) -.90/-1.40/.50 (1)
FAN RPM Direct Drive Direct Drive Direct Drive
MOTOR RPM 1,760 1,503 1,503
MOTOR VOLTAGE 230 230 230
MOTOR AMPERAGE 7 4.6 4.5
MOTOR HORSEPOWER 1 1 1
OUTSIDE AIR DAMPER 200 CFM (20% @) 274 CFM (15% @) 202 CFM
POSITION
NOTES: (1) SP taken across filter and coil.
111MDC Page No. 4 of 10
Date; 1/11/2016
Mechanical Dafa corporation
Member of
Associated Air Balance Council
DIFFUSER AND GRILL TEST
JOB NAME: EAGAN FIRE STATION
SYSTEM: RTU -2
ROOM OUTLET OUTLET REQUIRED PRELIMINARY FINAL
NO. NO. SIZE VEL CFM VEL CFM VEL CFM
112 2-1 CD 1.0 215 215 343 343 226 226
112 2-2 CD 1.0 215 215 309 309 206 206
E
101 2-3 CD 1.0 360 360 216 216 332 332 (l)
101 2-3A CD 1.0 360 360 200 200 305 305 (l)
113 2-4 CD 1.0 100 100 125 125 104 104
111 2-5 CD 1.0 100 100 141 141 107 107
1350 1334 1316
i
I
i
I
I
NOTES: (1) Due to space limitation, installed diffusers differ from HVAC layout. Diffusers delivering 88%of original
design CFM.
I
i
i
I
I
i
Page No. 5 of 10
111MD Date: 1/11/2016
Mechanical Data Corporation
Member of
Associated Air Balance Council
EXHAUST FAN TEST
JOB NAME: EAGAN FIRE STATION
FAN NO. EF-1 EF-2 EF-3 EF-4
MANUFACTURER Cook Cook Cook Cook
MODEL No. 165 ACE2 90 ACEH 90 ACEH 90 ACEH
MOTOR HP 2.0 1/4 1/4 1/4
VOLTAGE 230 120 120 120
RATED AMPS 6.7 3.4 3.4 3.4
ACTUAL AMPS 4.9 .51 .60 .54
REQUIRED FAN RPM Variable Variable Variable Variable
ACTUAL FAN RPM 1800 Direct Drive Direct Drive Direct Drive
REQUIRED CFM 3520 200 200 200
ACTUAL CFM 3647 186 185 196
LOCATION App Bay 102 111 110
NOTES:
Page No. 6 of 10
Date: 1/11/2016
iiii.WD. a Corporation
Member of
Associated Air Balance Council
DIFFUSER AND GRILL TEST
JOB NAME: EAGAN FIRE STATION
SYSTEM: EXHAUST
ROOM OUTLET OUTLET „K„ REQUIRED PRELIMINARY FINAL
NO. NO. SIZE VEL CFM VEL CFM VEL CFM
EF-1
108 1-1 11x11 .84 435 365 403 339 446 375
108 1-2 11x11 .84 435 365 583 490 461 387
108 1-3 11x11 .84 435 365 715 601 475 399
108 1-4 11X11 .84 435 365 384 323 420 353
107 1-5 11 x17 1.30 396 515 (1) (1) 400 520
107 1-6 11x17 1.30 396 515 (1) (1) 421 547
107 1-7 11x17 1.30 396 515 (2) (2) 430 559
107 1-8 11x17 1.30 396 515 (2) 390 507
3520 3920 3647
E F-2
102 2-1 EG 1.0 200 200 186 18 6 186 186
EF-3
111 3-1 EG 1.0 200 200 238 238 185 185
EF-4
110 4-1 3.5x13.5 .33 606 200 945 312 595 196
NOTES: (1) D- 16 RND, K- 1.40, AV-812, CFM - 1137
(2) D - 16" RND, K- 1.40, AV-736 CFM - 1030
Page No. 7 of 10
Date: 1/11/2016
Maahanlcal Data Gorporallon
Member of
Associated Air Balance Council
TRANSFER FAN TEST
JOB NAME: EAGAN FIRE STATION
FAN NO. TF-1 TF-2
MANUFACTURER Cook Cook
MODEL NO. 100 SQN 100 SQN
MOTOR HP 1/4 1/4
VOLTAGE 120 120
RATED AMPS 3.4 3.4
ACTUAL AMPS .55 1.13
REQUIRED FAN RPM Variable Variable
ACTUAL FAN RPM Direct Drive Direct Drive
REQUIRED CFM 500 700
ACTUAL CFM 506 746
LOCATION 104 109
NOTES:
i
f
Page No. 8 of 10
Date: 1/11/2016
Machoniccl Dcic Corporoilon
Member of
Associated Air Balance Council
DIFFUSER AND GRILL TEST
JOB NAME: EAGAN FIRE STATION
SYSTEM: TRANSFER FANS
ROOM OUTLET OUTLET „K„ REQUIRED PRELIMINARY FINAL
NO. NO. SIZE VEL CFM VEL CFM VEL CFM
TF-1
104 1-1 SD 1.0 500 500 680 680 506 506
2
TF-
109 F- SD 1.0 700 700 746 746 746 746
NOTES:
Page No. 9 of 10
lddllllllh Date: 1/11/2016
Mechanical Data Corporation
Member of
Associated Air Balance Council
MAKE UP AIR TEST
JOB NAME: EAGAN FIRE STATION
FAN NO. MAU - 1
MANUFACTURER AAON
MODEL NO. RN-009
MOTOR HP 2.0
VOLTAGE 230
RATED AMPS 6.8
ACTUAL AMPS 4.8
REQUIRED FAN RPM 1170
ACTUAL FAN RPM Direct Drive
REQUIRED SP 44.75
ACTUAL SP -.57/+.11/.68
REQUIRED CFM 3520
ACTUAL CFM 3405 (l)
LOCATION App Bay
NOTES: (1) Fan operating at 85% speed setting.
111MD Page No. 10 of 10
Aoft Date: 1/11/2016
Nleohanlaat Data Corporation
Member of
Associated Air Balance Council
DIFFUSER AND GRILL TEST
JOB NAME: EAGAN FIRE STATION
SYSTEM: MAU -1
ROOM OUTLET OUTLET REQUIRED PRELIMINARY FINAL
NO. NO. SIZE VEL CFM VEL CFM VEL CFM
108 M-1 13.25x13.25 1.22 598 730 823 1004 569 694
108 M-2 13.25x13.25 1.22 598 730 881 1075 580 708
107 M-3 13.25x17.25 1.59 648 1030 744 1183 621 987
107 M-4 13.25x17.25 1.59 648 1030 770 1224 639 1016
3520 4486 3405
NOTES: