Loading...
1500 Central Park Commons Dr - Hy-Vee Grease Duct Manual Non-Welded Double Wall Grease Duct/Type HT Chimney Systems Installation, Operation, and Maintenance Manual I r _ 5 }r1 C ® s C Lam ° SAFETY I TWO ,MAJOR--CAUSES flF_GREASE DUCT RELATED FIRES :(I} FAILUREi-, MAINTAINREQUIRED' ;CLEARANCE:{AIR SPACE]-0 COMBUSTIBLE MATERIALS AND(2}EAILt RE TO CLEAN GREASE:LADEN.,,", . DUCTS IT 1S :O,F UTMOST IMPORTANCE-THAT;.THIS GREASE DUCT.BE II�ISTALLEfI"ONLY;IN ACCORDANCE WITH THESE INSTRUCTIONS: -DO NOT INSTALL_GREASE I3UCT 11YITHOI,T FIRST {READING THESE INSTRUCTIONS VERY CAREFULLY - A MAJOR CAISE OF CHIMNEY RELATED--F RE S FAILURE 1 Q MAIN"CA{N IZIQUiRED CLEARANCES-, (AIR SPACES 7O COMBUSTIBLE MATERIALS Ii.IS OE UTMOST 1'MPOR't'ANCIi:'fHAf THIS CHIMNEY-BE ANSTALLED;QNLY IN ACCORDANCE WITH THESE INSTRUj:-t = - ThES.grease duc#js_ETL Its#edto s tandards UL 197 t-LIL2?_2 IASTM E2336 and`AC101, grease duct:installed per these instructions meets#hie requirements of NAPA 96. Factory bn�It°ch�rnney is LJL I�stei to standards [1L1€f3 8�UL103 HT and.Ind�cates,conforcnance to tlie;Ganadian Standards GANtULC=SI29-M87& ULCIORD-0959-1993 Grease duct4& Chi>nney systemsnstaliedn accordance wi#h #fese installation in j_ wd1 compty rnri th national safety standards ancl_bullding cones = __ A0018672 March 2015 Rev.13 i, TABLE OF CONTENTS WARRANTY.................................................................................................................................................3 LISTINGS.....................................................................................................................................................4 CLASSIFICATIONS......................................................................................................................................4 APPLICATION..............................................................................................................................................4 CLEARANCES.............................................................................................................................................6 MECHANICAL.............................................................................................................................................7 JointSealant............................................................................................................................................8 SealantFeatures..................................................................................................................................8 Table2—Sealant Usage Chart.............................................................................................................8 GreaseDuct& Chimney Joint Assembly...................................................................................................9 Adjustable Duct, Chimney&Transition Connection ................................................................................ 10 Adjustable Duct, Chimney Standard Installation...................................................................................... 11 Risers— Factory& Field (Bolted) Risers .................................................................................................13 DuctDrains............................................................................................................................................ 14 ManifoldTee .......................................................................................................................................... 14 AccessDoor(Tee Cap)Assembly.......................................................................................................... 15 FanAdapter Plate .................................................................................................................................. 16 ChimneyAdapter Plate........................................................................................................................... 16 Prevention of Grease Accumulation in Horizontal Grease Duct............................................................... 16 Alignment & Bracing of Grease Duct....................................................................................................... 17 Horizontal Support& Support Spacing................................................................................................ 17 Vertical Support&Vertical Support Spacing....................................................................................... 19 Through Penetration & Fire Stops...........................................................................................................27 AnnularDistance—Fire Stop..............................................................................................................27 Annular Distance-2R Type HT Clearance.........................................................................................28 Floor& Ceiling Fire Stop Installation...................................................................................................29 WallFire Stop Installation...................................................................................................................30 Grease Duct Assembly Examples...........................................................................................................31 METHODS USED TO TEST DUCT AFTER ASSEMBLY............................................................................36 Method 1 —Light Test per IMC 506.3.3.1 ................................................................................................36 Method2—Smoke Test..........................................................................................................................36 GENERALDUCT WEIGHTS......................................................................................................................36 Weight—DW-2R....................................................................................................................................36 Weight—DW-3R....................................................................................................................................36 Weight—DW-3Z.....................................................................................................................................36 Weight—Example..................................................................................................................................36 CLEANING & MAINTENANCE RECORD ...................................................................................................40 2 s WARRANTY This ductwork& chimney systems are warranted to be free from defects in material and workmanship, under normal use and service,for a period of 12 months from the date of shipment. This warranty shall not apply if: 1. The equipment is not installed by a qualified installer per the MANUFACTURER'S installation instructions shipped with this product (this guide should be kept.with the equipment once installation is complete), 2. The equipment is not installed in accordance with federal, state and local codes and regulations. 3. The equipment is misused or neglected. 4. The equipment is not operated within its published capacity. 5. The invoice is not paid within the terms of the sales agreement. The MANUFACTURER shall not be liable for incidental and consequential losses and damages potentially attributable to malfunctioning equipment. Should any part of the equipment prove to be defective in material or workmanship within the 12-month warranty period, upon examination by the MANUFACTURER, such parts will be repaired or replaced by the MANUFACTURER at no charge. The BUYER shall pay all labor costs incurred in connection with such repair or replacement. Equipment shall not be returned without MANUFACTURER'S prior authorization and all returned equipment shall be shipped by the BUYER, freight prepaid to a destination determined by the MANUFACTURER. 3 i LISTINGS This grease duct has been tested and is listed to UL1978 and UL2221 and testing has been extended to recognize ASTM E2336 and AC101 due to similar testing criteria. Models 2R, 3R and 3Z are used for grease duct applications when installed in accordance with these instructions and National Fire Protection Association "NFPA 96"; Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations. This factory built chimney has been tested and is listed to UL103 and UL103HT and testing has been extended to recognize CAN/ULC-S629-M87 & ULC/ORD-C959-1993. Model 2R is intended for installation within commercial / industrial applications. Model 2R is not intended for use in family dwellings. When installed in accordance with these instructions and National Fire Protection Association "NFPA 211"; Standard for chimneys. CLASSIFICATIONS UL 2221: Standard for Fire Resistive Grease Duct Enclosure Assemblies. Chapter 7 of this standard references a test labeled Internal Fire Test. Section 7.1.1 references two installation conditions, Condition A and Condition B. Condition A represents all installation conditions except for installation within non-ventilated combustible enclosures. Condition B represents installation within a non-ventilated combustible enclosure. UL 103: Standard for Factory Built Chimneys for Residential Type and Building Heating Appliances. Model 3Z is classified under UL2221 (Test of Fire Resistive Duct Enclosure Assemblies)as an alternate to 2- Hr. fire resistive shaft enclosures with a minimum zero clearance to combustibles (sizes 8" to 24" diameter). Model 3Z is listed in accordance with the requirements for duct enclosure Condition A and B. Model 3R is classified under UL2221 (Test of Fire Resistive Duct Enclosure Assemblies)as an alternate to 2- Hr. fire resistive shaft enclosures with a reduced clearance to combustibles (sizes 8"to 24" diameter). Model 3R is listed in accordance with the requirements for duct enclosure Condition B. Model 2R is classified under UL2221 (Test of Fire Resistive Duct Enclosure Assemblies)as an alternate to 2- Hr. fire resistive shaft enclosures with a reduced clearance to combustibles (sizes 8"to 16" diameter). Model 2R is listed in accordance with the requirements for duct enclosure Condition B. Model 2R Type HT is classified under UL103 (Factory Built Chimneys for Residential Type and Building Heating Appliances). Insulated double wall building heating appliance Chimney / Type HT Factory Built Chimney intended for commercial and industrial applications in sizes 8 through 16 inch ID. APPLICATION Double wall grease ducts are listed for a continuous internal temperature of 500`F and intermittent temperatures of 20007. Double wall grease duct is ideally suited for use in commercial cooking installations for the removal of smoke and grease laden vapors. Grease duct system size and capacity information may be obtained from the ASHRAE Handbook— Fundamentals or from the Air Pollution Engineering Manual of the US Environmental Protection Agency. Grease duct installations require provisions for cleaning the interior of the duct. NFPA 96 cleanout requirements are as follows: 1. A cleanout must be provided at each change of direction, except where the entire length of duct can be inspected and cleaned from either the hood or the discharge end. 2. On horizontal duct runs, at least one (1)20" diameter opening must be provided. Where the opening is smaller than 20" diameter, openings large enough to permit cleaning must be provided at intervals of no more than 12'. 3. Openings must be at the side or the top, whichever is more accessible. When the opening is on the side of the duct, the lower edge of the opening must be at least 1 '/2" above the bottom of the duct. For the listed grease duct, this is accomplished by the use of the grease manifold tee and cleanout cap. 1 4 4. On vertical duct runs where personnel entry is possible, access must be from the top of the riser. Where entry is not possible, access must be provided at each floor. NOTE: ACCESS REQUIREMENTS ARE SUBJECT TO CHANGE IN ACCORDANCE WITH LOCAL CODE. LOCAL AUTHORITIES SHOULD BE CONSULTED FOR EXACT REQUIREMENTS. GREASE DUCT MAY BE CONNECTED ONLY TO HOODS IN A SINGLE FIRE ZONE ON ONE FLOOR. DO NOT CONNECT GREASE DUCTS TO ANY OTHER PART OF THE BUILDING VENTILATION OR EXHAUST SYSTEM. When grease duct or chimney is installed in accordance with these installation instructions and the joints are sealed properly with the recommended sealant, the system will contain a fire within the duct or chimney. A fire can burn at extremely high temperatures. The system should be dismantled and inspected after any exposure to a fire. Any section that is distorted or discolored should be replaced. All joints in the system should be examined. The sealant expands to ensure a positive seal in the case of a fire, and any sealant that has been exposed to high temperature must be replaced. This will ensure that the system maintains its integrity against fire conditions in the future. The manufacturer of this grease duct or chimney cannot be responsible for grease duct or chimney systems that are not properly maintained or have been subjected to one or more fire. Factory Built Chimney model 2R Type HT is listed for continuous internal temperatures of 1000'F US & 600'F Canada, intermittent temperatures of 2100`F. Factory Built Chimney model 2R Type HT is ideally suited for commercial and industrial application for the removal of smoke and heat. Chimney system size and capacity information may be obtained from the ASHRAE Handbook — Fundamentals or from the Air Pollution Engineering Manual of the US Environmental Protection Agency. Note: Model 2R Type HT chimney does not require joints to be sealed with the recommended sealant per the listing report. When wood is burned slowly, it produces tar and other organic vapors, which combine with expelled moisture to form creosote. The creosote vapors condense in a relatively cool chimney flue of a slow burning fire. As a result, creosote residue accumulates on the flu lining. When ignited this creosote makes an extremely hot fire. Chimney installations require provisions for cleaning the interior of the chimney. Creosote and Soot formations need to be removed. The chimney should be inspected once every two months during the heating season to determine if creosote or soot buildup has occurred. If creosote or soot has accumulated, it should be removed to reduce the risk of fire. Cleanout requirements are as follows: 1. A cleanout must be provided at each change of direction, except where the entire length of chimney can be inspected and cleaned from either the equipment or the chimney cap. 2. Openings must be at the side or the top, whichever is more accessible. 3. The chimney inspection should be done every two months during the heating season. 4. If creosote or soot has accumulated it should be removed to reduce the risk of fire. 5. Insert the chimney cleaning brush and brush in a downward motion, be sure to scrub all sides of the chimney thoroughly and remove all debris. 6. Contact local building or fire officials about restriction and inspection in your area. NOTE: CHIMNEY/TYPE MODEL 211 TYPE HT FACTORY BUILT CHIMNEY IS INTENDED FOR COMMERCIAL AND INDUSTRIAL APPLICATIONS. FACTORY BUILT MODEL 2R TYPE HT CHIMNEY IS NOT INTENDED FOR FAMILY DWELLINGS. CHIMNEY SHOULD BE SIZED IN ACCORDANCE WITH THE "APPLIANCE MANUFACTURE'S INSTRUCTIONS". ti I 5 I CLEARANCES In all buildings more than one story in height and in buildings where the roof-ceiling assembly is required to have a fire resistance rating, the duct must be enclosed in a continuous enclosure from the lowest fire-rated ceiling or floor above the hood, through any concealed spaces, to or through the roof to maintain the integrity of the fire separations required by the applicable building code provisions. If the building is less than 4 stories in height, the enclosure shall have a fire resistance rating of not less than 1 hour. If the building is 4 stories or more in height, the enclosure shall have a fire resistance rating of not less than 2 hours. Single wall grease duct is primarily intended for use in non-combustible surroundings. When installed in an open room where enclosure is not required, double wall grease duct or chimney may be located at clearance to combustibles in accordance with Table 1. Table 1 — Grease Duct Clearances DUCT MODEL INNER DIAMETER OUTSIDE CLEARANCE TO CLEARANCE TO NON- ID) DIAMETER COMBUSTIBLES COMBUSTIBLES DW 8"-24" = ID 18" 0" DW-2 R 8"- 16" ID +4 3/4" 0" DW-2R TYPE HT 8"— 16" ID +4 2"** 0" DW.3R 8"-24" ID + 6 3/4"*** 0" DW-3Z 8"-24" ID + 6 0" 0" The above figures represent air space, in inches, to surrounding. NOTE:See NFPA 96, 2004 EDITION, Chapter 3, Definition of Combustible, Limited Combustible and Non-Combustible. *DW—2R: 3/" clearance to combustibles from the surface of the duct outer shell; zero inch clearance from combustibles from the tip of the outer V Band. **DW—2R TYPE HT: 2"clearance to combustibles from the surface of the duct outer shell. ***DW—3R: 3/" clearance to combustibles from the surface of the duct outer shell; zero inch clearance from combustibles from the tip of the outer V Band. NOTE: Double wall duct systems with reduced clearance"R" have been tested using Condition B—installed within non-ventilated combustible enclosure. See Fig. 1 below for representation of reduced clearance note, the V Band may be in contact with a combustible surface. DW-2R TYPE HT must maintain 2 inch clearance to combustibles. t 6 i y Fig.1 — Duct Reduced Clearance I' 39"REDUCED "1 f CLEARANCE. COMBUSTIBLE SURFACE. DOUBLE V BAND. DUCT. Fig. 1 a— 2R TYPE HT Chimney Reduced Clearance 2"REDUCED CLEARANCE. CONABUSTIBLE SURFACE. .I 2R SHELL I• O.D. FIRES T OP 1 I PLATES. 2"REDUCED CLEARANCE. ------------------------------ t 7 i I MECHANICAL Joint Sealant The joint sealant used to seal all joint assemblies is a 3M product. 3M Fire Barrier 2000+ Silicone Sealant is a ready-to-use, gun-grade, one-component silicone elastomer that cures upon exposure to atmospheric humidity to form a flexible seal. 3M Fire Barrier 2000+ Silicone Sealant, when installed properly, will control the spread of fire before, during and after exposure to open flames. It will stop the spread of noxious gas, smoke and water, and maintain the integrity of fire rated assemblies and construction. All grease ducts must be liquid tight per NFPA 96. The following steps are to be used to ensure that this requirement is met. Model 2R Type HT chimney does not require joints to be sealed with the 3M Fire Barrier 2000+ Silicone Sealant per the listing report. NO SEALANT SUBSTITUTES MAY BE USED. Sealant Features 1. Superior adhesion. 2. Capable of withstanding 2000'F +temperatures. 3. Class 25 sealant, per ASTM 920. 4. Re-enterable/repairable. 5. Provides up to 4-hours fire-rating. 6. Cures upon exposure to atmospheric humidity. 7. Working time 30 minutes. 8. Cure time 14 to 21 days. 9. Applied with a standard caulk gun. Table 2 — Sealant Usage Chart 3M FIRE BARRIER 2000 PLUS USAGE DIAMETER DUCT PERIMETER FT AVERAGE FEET NUMBER OF PER TUBE JOINTS PER TUBE 8" 2.16 30 7 10" 2.68 30 6 12" 3.21 30 5 14" 3.73 30 4 16" 4.25 30 3.5 18" 4.78 30 3 20" 5.30 30 .3 24" 6.35 30 2.5 8 Grease Duct & Chimney Joint Assembly All grease ducts are to be liquid tight per NFPA 96. The following steps are to be used to ensure that this requirement is met. Model 2R Type HT chimney does not require joints to be sealed with the 3M Fire Barrier 2000+ Silicone Sealant per the listing report. 1. Fill the V band used with inner ductwork with 3M Fire Barrier 2000+ Silicone. The bead should be continuous. See Table 2, for the number of joints per tube. 2. Place the loose V band over the duct flange. Apply a continuous bead of 2000+ Silicone 1/4"wide to the flange that will be joined. 3. Join the two flanged ends of the inner duct sections together and rotate slightly to ensure complete coverage of sealant on flanges. 4. For horizontal duct runs,the"V"clamp hardware should be located on the top side of the duct and be orientated between the 3 and 9 o'clock position on the duct. 5. NEVER install the "V" clamp with the hardware orientated on the bottom side of the duct on horizontal runs. 6. Install the V band around the duct flanges making sure the flanges are located within the V band. Tap the outside of the V band while tightening V band hardware to make sure the flanges are aligned and have been pulled together. Secure the'/-20 hardware to 85 in-Ibs. 7. Insulation must be minimum of 4'/2"wide, and the same type and number of layers as the base duct. Tightly pack and completely fill all voids between the inner duct and the outer shell. 8. Install the double V band ensuring the outer shell flanges are positively engaged in the V bands before tightening the '/-20 hardware to 85 in-Ibs. The double V band can be sealed using 3M Fire Barrier 2000+Silicone when being installed outside. Fig. 2 — Duct & Chimney Joint Assembly STEP 1 STEP 2 STEP 3 DETAIL A Y r STEP 4 'STEP 5 STEP B rte. IMPORTANT: THE HARDWARE USED TO ASSEMBLE THIS DUCTWORK IS SPECIFICALLY DESIGNED FOR THIS APPLICATION. NO SUBSTITUTE HARDWARE IS ALLOWED. ALL REPLACEMENT HARDWARE MUST BE PURCHASED FROM THE FACTORY. ,l 9 f i Adjustable Duct, Chimney & Transition Connection Adjustable duct sections may be used in conjunction with transition plates when they terminate at the fan. The adjustable duct section is fully welded to the transition plate, and then connected to the standard duct length using non-welded connections. Double wall adjustable duct sections are assembled in the field, as the exact length needed for the application is not known. Components for outer shell and insulation ship loose. Once fully assembled, the transition plate is secured to the curb using the method referenced in Fig. 8 — Fan Adapter Plate. Model 2R Type HT chimney does not require joints to be sealed with the 3M Fire Barrier 2000+ Silicone Sealant per the listing report, however, all other steps must be followed. 1. The standard duct section in the adjustable assembly is installed using the standard connection method, (see Fig. 2). Note:this is the piece with two flanges and the outer shell collar already attached 1 '/"from the duct flange. 2. Adjustable duct assemblies that are used with transition plates only have one inner duct flange protruding from the outer duct shell. This is the side that connects to the standard length duct. 3. The adjustable collar is slipped on to the adjustable duct section. Make sure the adjustable collar flanges are opposite the adjustable duct section flange. 4. The adjustable section is pushed inside the standard duct section. Make sure the minimum overlap is set correctly; see Table 3. 5. Once the overlap is set correctly, silicone the flanges of the bottom duct section and the adjustable collar using connection method referenced in Fig. 2—Joint Assembly step 1 through step 3. 6. Adjustable collars are sealed to the adjustable duct using 3M Fire Barrier 2000+ Silicone. Once the V band has been installed, tighten the adjustable collar hardware to 85 in-lbs. 7. The insulation provided is used to wrap the adjustable assembly. Ensure all voids are adequately filled. 8. Cut the outer shell cover to the length and then install using the provided sheet metal screws. Make sure the shell cover overlaps and are secured to the shell collars. Use only hardware provided as longer screws may penetrate inner duct. } 9. 3M Fire Barrier 2000+ Silicone may be used to seal the outer shell. Fig. 3 —Adjustable Duct, Chimney & Transition Plate STEP 1 TRANSITION STEP 2 STEP 3 PLATE. UTER SHELL TIGHTEN C OLLAR, 3M FIRE BARRIER 851N-LBS. - 2000 ADJUSTABLE - �, DUCT, - ADJUSTABLE _ COLLAR. =- --- TIGHTEN =. ,...- ... SS IN.LBS. - 3M FIRE BARRIER .,. 2000 PLUS, V BAND. TANDARD 3M FIRE BARRIER OUTER SHELL DUCT, 2000 PLUS. COLLAR. STEP �PLATEITION STEPS STEP6 CUM- INSULATION. t _ UTER SHELL INSULATION.- SHEET METAL COVER. " SCREWS, 1 i 10 i Adjustable Duct, Chimney Standard Installation Adjustable duct lengths are used to make up variable lengths in the duct system(s). Adjustable sections should always be installed with the overlap to the inside of the standard duct section. Overlap should always be opposite the direction of airflow. This will allow grease/water to run back to the hood when the system is shut down. If the inner adjustable section is too long to fit into the adjacent section of duct without interfering with the flow path it should be trimmed to the desired flange to flange length. Flange to flange length of adjustment can range from 4" to 26". Model 2R Type HT chimney does not require joints to be sealed with the 3M Fire Barrier 2000+ Silicone Sealant per the listing report. 1. The standard duct section in the adjustable assembly is installed using the standard connection method, (see Fig. 2). Note:this is the piece with two flanges and the outer shell collar already attached 1 '/2"from the duct flange. 2. The adjustable collar is slipped on to the adjustable duct section. Make sure the adjustable collar flanges are opposite the adjustable duct section flange. 3. The adjustable section is pushed inside the standard duct section. Make sure the minimum overlap is set correctly see Table 3. 4. Once the overlap is set correctly, silicone the flanges of the bottom duct section and the adjustable collar using connection method referenced in Fig. 2—Joint Assembly step 1 through step 3. 5. Adjustable collars are sealed to the adjustable duct using 3M Fire Barrier 2000+ Silicone. Once the V = band has been installed, tighten the adjustable collar hardware to 85 in-lbs. 6. The insulation provided is used to wrap the adjustable assembly. Ensure all voids are adequately filled. 7. Cut the outer shell cover to the length and then install using the provided sheet metal screws. Make sure the shell cover overlaps and are secured to the shell collars. Use only hardware provided as longer screws may penetrate inner duct. 8. 3M Fire Barrier 2000+Silicone may be used to seal the outer shell. Table 3 — Minimum Overlap MIN OVERLAP FOR DIAMETER ADJUSTABLE DUCT & CHIMNEY 8,1 ' 10.. 5„ 12" 6" 14" 6" 16" 6" 18" 6'$ 20" 6" 24" 6" r 11 Fig. 3a —Adjustable Duct & Chimney Overlap INSTALLED LENGTH MIN.SEE TABLE a. AIRFLOW DIRECTION ri I OUTER SHELL ADJUSTABLE COLLAR. V BAND. SECTION. DUCT SECTION. ADJUSTABLE COLLAR. Fig. 3b — Collar & Adjustable Duct, Chimney Installation STEP 1 STEP 2 STEP 3 3M FIRE BARRIER 2000 PLUS. ADJUSTABLE �"Y 2 FIRE B R.RIER DUCT, ADJUSTABIE COLLAR. TIGHTEN ` 851N-LBS. STANDARD TIGHTEN " . DUCT. : 851N LBS. STEP 4 STEP 5 INSULATION. —OUTER SHELL SHEET M ETAL tee' q COVER. SCP.EUUS, INSULATION. 4 i r 12 Risers — Factory & Field (Bolted) Risers There are two options for the riser (connection to the hood plenum); factory welded and field bolted. Factory installed risers are welded to the plenum per instructions that detail riser size and location. The instruction below covers field installed (bolted) riser(s). When field installed riser(s) are requested, they ship loose allowing the installer to decide on the location. Field installed riser(s) are preferred when the exact location is not known or when adjustments need to be made for misalignment in duct systems. 1. Locate the specific position at which the riser needs to be installed. 2. Use the riser as a guide when marking the hood. Note: Make sure the hole location is inside the plenum area before cutting any holes. 3. Since the riser is going to be bolted to the plenum, a bolt hole circle will need to be cut. Use the bottom or loose retaining ring as a template. Align the inner circles of the hole in the plenum with the retaining ring and mark the bolt hole circle. Make sure the bolt hole circle is inside the plenum area before cutting. 4. Use the 3M Fire Barrier 2000+ Silicone to seal around the riser hole. Apply sealant to the top and bottom of the hole. Make sure the silicone bead is a minimum of/"thick and is continuous inside and outside of the bolt hole circle. 5. Center the riser over the hole in the plenum and push down. Make sure the riser flange is positively sealed. Also, make sure the captured retaining ring on the riser is pushed down into the sealant. Sealant should come through the holes on the ring. 6. Align the loose retaining ring with the hole on the inside of the plenum. Push the ring up into the sealant. Align the holes in the bottom and top retaining rings and secure using '/-20 hardware. 7. Place the loose duct flange ring over the riser before installing the connecting duct section using connection method (see Fig. 2—Joint Assembly, step 1 through step 3). 8. Once the riser and connecting duct section(s) have been connected, install the insulation provided. Make sure all voids are filled. 9. Install the riser covers by pushing the two halves together around the duct flange ring and securing it using sheet metal screws provided. Use only hardware provided, as longer screws may penetrate the inner duct. 10. See Fig. 2—Joint Assembly, step 1 through step 3, to install standard duct sections to factory installed or welded risers. 11. The slots in the riser covers provide an opening for the installation of duct sensors if required. Fig. 4 — Field Installed Riser— Bolted STEP 1 STEP.2 3M FIRE BARRIER RISER. 2000 PLUS. DOUBLE WALL DUCT.: emu„ V BAND. DUCT FLANGE RING. HOOD TOP. RETAINING ,RINGS. 1!420 HARDWARE. V BAND. STEP 4 RISER COVER:. STEPS HOLE FOR _ DUCT STAT INSTALLED HERE: 'INSULATION. i. SHEET METAL ISER..COVER: SCREWS, 13 Fig. 5 — Duct Drain Duct Drains Drains are used to provide a point at which low points DUCT secTloN. in the duct system can be drained. Condensation DOUBLE v TEE. and low lying water left over from duct cleaning can BAND. be drained easily with the installation of the ball valve drain. Drains are designed to aid in duct cleaning - ADAPTER. and can be used to drain grease into an approved _ grease collection reservoir. Drains can be hard piped to an approved grease collection reservoir, remove the cap and connect to the 1-1/2" NPT threads (see Fig. 5.for details). ADAPTER. Manifold Tee DRAIN. The manifold tee is used to provide access for cleanout to comply with NFPA 96 requirements. It is equipped with an internal blank that acts as a grease dam and gasket. The access port is then closed with a cleanout cap or tee cap.The tee cap is then covered with layers of insulation that is covered in an outer shell called the access door collar. The location of the access port in the tee is dependent on the orientation of the tee in the final installation. The access port location in the manifold tee can be orientated as required (see Fig. 6). Access ports should never be located where grease can build up and fall out once the cleanout cap is removed or where the access door collar cannot be removed to gain access to the inner duct. Fig. 6 - Manifold Tee Position OUTER DUCT INNER DUCT SHELL SHELL igW _ r ACCESS DOOR ACCESS DOOR RIGHT— LEFT ACCESS DOOR TOR t-----INSULATION & CASKET 14 Access Door (Tee Cap) Assembly Access doors (tee caps)are available in diameters from 8"to 24". They work in conjunction with the manifold tee as previously shown in Fig. 6. The tee joint connection is shown in Fig. 2 — JOINT ASSEMBLY; however, the installation of the access door is slightly different so read the following instructions very carefully. Consult NFPA 96, Chapter 7, Section 7.3.1 "Openings shall be provided at the sides or at the top of the duct, whichever is more accessible, and at change of directions." 1. Select the location and the position of the access door. 2. All tee joints will be connected as shown in Fig. 2—JOINT ASSEMBLY except for the access door. 3. Apply the proper sealant to the flange of the tee that will be used for access to the duct system. 4. Apply a '/" continuous bead around the flange. 5. Center the inside blank (grease dam) over the opening of the tee and apply pressure. Pushing the inside blank down onto the tee flange sealant, securing the inside blank to the tee flange. 6. Apply enough pressure to create a positive bond between the tee flange and the inside blank. Remove excess sealant after making parts concentric(centered). 7. Apply a '/" continuous bead around the inside blank 1"from the outside edge. 8. Center the listed gasket over the inside blank and push the gasket down into the sealant securing the gasket to the inside blank. 9. Sealant will begin to cure upon exposure to atmospheric humidity. It will form a flexible seal. 10. Once the sealant is dry attach the access door using a W" clamp. Ensure flanges are in the W" before tightening '/4-20 hardware to 80 in-lbs. 11. Once the inner access door assembly is complete install the outer access door or access door shell. 12. The outer access door shell is used to seal the inner access door with insulation, (see Fig. 7 below). Fig. 7 — Access Door Assembly GASKET-1 INNER DUCT INr1E? A Icy DAM DOOR f—CCES S INSULATION DA � 1 OUTER DUCT SHELL j F = OUTER V SAND IN HER V BW'ID OUTER ' ACCESS DOOR f"t 3 LAY=RS ACCESS DGOR INISULAII CUTER SHELL 15 Fan Adapter Plate Fig. 8 — Fan Adapter Plate j The fan adapter plate (Transition Plate) is designed to connect to a roof curb. The duct section is welded to the underside of the adapter plate. The adapter plate is formed to provide a EXHAUST FAN. slope to allow grease deposits to flow back towards the duct. When connected (see Fig. 8), the plate mounts on top of the fan TRANSITION curb that supports the fan housing. The plate may be positioned CERAMIC off center within the curb provided that the minimum distance to VENTED GASKET. combustibles is maintained. In the event that the plate is CURB. positioned off center, trim off excess plate material to allow for fan placement. Secure the plate to the curb using a minimum of three fasteners per side. A suitably sized fastener provided by VERTICAL others is used. The fan adapter plate can be used to maintain ADJUSTABLE SUPPORT. distance to combustibles and also for vertical support. See Fig. DUCT SECTION. 3 for adjustable duct section assembly. The top collar is installed upside down to seal the insulation at the fan termination/transition plate. Fig. 8a — Chimney Adapter Plate Chimney Adapter Plate The Chimney adapter plate (Transition Plate) is designed to connect to a roof curb. The Chimney section is welded to the CHIMNEY CAP. underside of the adapter plate. When connected (see Fig. 8a), the TRANSITION plate mounts on top of the curb that supports the chimney cap. The PLAT. . plate may be positioned off center within the curb provided that the CERAMIC minimum distance to combustibles is maintained. In the event that v VENTED GASKET.G2KET. the plate is positioned off-center, trim off excess plate material to CURB allow for chimney cap placement. Secure the plate to the curb using a minimum of three fasteners per side. A suitably sized fastener provided by others is used. The chimney adapter plate FIRE can be used to maintain distance to combustibles and also for STOP. CHIMNEY vertical support. Ceramic gasket is used to seal the adapter plate I ,_ to the underside of the chimney cap. WARNING, clearance (air e� space)to combustibles will be free from any type of insulation. VERTICAL SUPPORT.---' Prevention of Grease Accumulation in Horizontal Grease Duct In some areas the local code authority may insist on inclusion of/" per foot slope. In such cases, a short "Slope Transition" section is available from the factory. For correct installation, two slope transitions are generally required - one at the beginning and end of the horizontal duct run. For installations with horizontal runs greater than 75 feet, some local codes demand a 1" per foot slope. Consult with local code authorities if unsure about local requirements. Offset collars have been designed to meet the above specification. The collar is used in conjunction with other accessories such as tee's and elbows to maintain the above listed slope in horizontal duct runs. The W" clamp hardware should be located on the top side of the duct and be orientated between the 3 and 9 o'clock position on the duct. Never install the W" clamp with the hardware orientated on the bottom side of the duct on horizontal runs. 16 I Alignment & Bracing of Grease Duct Grease duct has the characteristics of a continuous stainless steel pipe and it will expand and contract along its entire length with changes in temperature. For this reason, conventional methods of attaching guides and braces to the outer wall of the grease duct cannot be used. Correctly installed support rings, saddles and wall guide assemblies will serve to keep the duct aligned, provide for adequate resistance to lateral loads and allow the free axial expansion and contraction movement. A simplified rule for duct expansion is that the axial growth will be approximately 1 inch per 100 feet of pipe length for each 100 degrees Fahrenheit the exhaust vapor temperature is above the surrounding air temperature. Horizontal Support & Support Spacing Table 4— Horizontal Support Spacing Horizontal duct runs are supported using 2 X 2 X 1/8"angle, Uni-strut and or Uni-strut/saddle combination. Horizontal DIAMETER HORIZONTAL support spacing is shown in Table 4. When cutting the angle or Uni-strut to length, there must be a minimum of 2"on either side SUPPORT SPACING of the duct shell to allow for rod attachment. Once the angle (FEET) has been cut to length it is suspended using 1/2"threaded rod 8" 7' (minimum). Appropriate sized holes are drilled/ punched in 10" 7' either end of the angle. The 1/2"threaded rod is secured to the angle or Uni-strut using 1/2"grade 5 hex nuts and 1/2" hardened 12 7 washers, see Fig. 9. Note: double hex nuts are used as locking 14" 7' nuts to make sure hardware does not come loose overtime. 16" 7' 18" 5' 20" 5' 24" 5' 1 17 r Fig. 9 — Horizontal Support Details 1 IMPORTANT: VERTICAL & HORIZONTAL SUPPORTS SHOWN IN THIS MANUAL ARE RECOMMENDED. SUPPORTS BY OTHERS MUST BE APPROVED BY THE MANUFACTURER AND AHJ. SUPPORT SPACING MUST BE AS STATED IN THIS MANUAL. 1/2"THREADED DUCT SECTION. RODS, CENTER DOUBLE V BAND. DUCT _ DP USDIA. UNI STRUT. SEE TABLE 4 ►-� CENTER DUCT W"THREADED 1/2"THREADED RODS. RODS. 112'HARDENED UNI STRUT. WASHERS 2 PLC'S. SADDLE. 10 HEX NUTS GRADE 5,4 PLC'S. UNI STRUT. I DUCT DIA.� fff��� PLUS 4' UNI STRUT-BOTTOM CONNECTION 1/2"THREADED 1/2"HEX NUTS RO THREADED RODS. GRADE 5,2 PLC'S. RODS. SADDLE. (BOTTOM) 112"HARDENED WASHERS 2 PLC'S. 1/2"HARDENED SADDLE. WASHERS 2 PLC'S. (TOP) UNISTRUT. /-112"HEX NUTS GRADE 5,4 PLC'S. SADDLE-TOP CONNECTION SADDLE-BOTTOM CONNECTION I 18 Vertical Support &Vertical Support Spacing % Duct and chimney system(s) require supports along vertical runs. There are multiple vertical supports used for duct and chimney system(s). Each support assembly is designed for a specific type of installation. Review installation site before selecting supports. There are three different types of hardware supplied depending on the type of wall that the duct or chimney is being supported on. There are three types of wall construction listed below; gypsum with wooden studs, gypsum with 25 gauge steel studs and concrete/masonry. Each wall construction type requires different hardware to be used when installing the support assembly. Maximum vertical support spacing is shown in Table 5. Do not exceed this listed vertical spacing. Table 5—Vertical Support Spacing DIAMETER DUCT VERTICAL 2R Type HT CHIMNEY SUPPORT VERTICAL SUPPORT SPACING (FEET) SPACING (FEET) 8" 10' 20' 10" 10' 20' 1211 10' 20' 14" 10' 20' 16" 10' 20' 18" 10' N/A 20" 10' N/A 24" 10' N/A 19 Fig. 10 —Vertical Wall Support Kit IMPORTANT: VERTICAL & HORIZONTAL SUPPORTS SHOWN IN THIS MANUAL ARE RECOMMENDED. SUPPORTS BY OTHERS MUST BE APPROVED BY THE MANUFACTURER AND AHJ. SUPPORT SPACING MUST BE AS STATED IN THIS MANUAL. WALL SUPPORT PLATE. FLAT SUPPORT PLATE. 5116-18 WHIZ NUTS&BOLTS USED TO SECURE TO TOP PLATE TO THE SIDE PLATE, -;t}•rt �-"" . 5116-18 X I'SELF DRILLING 4 SCREWS USED TO SECURE �..� DOUBLE WALL DUCT SHELL T - = SIDE SUPPORT PLATE. WALLSUPPORT PLATE. Fig. 10a —Vertical Support Duct Details DUCT _. SYSTEM, 4 DUCT VERTICAL SUPPORTS f/—DOUBLE WALL MATERIAL HAVE SPECIFIC INSTALLATION V BAND SEE INSTALLATION INSTRUCTIONS PER THE 51 PE INSTRUCTIONS PER OF WALL CONSTRUCTION,SEE CONSTRUCTION TYPE, SPECIFIC DETAIL BELOW. DOUBLE TYPES OF WALL VERTICAL V BAND.— CONSTRUCTION: SUPPORT: 2X4WOODEN STUDS. 2X4(25)GAUGE STUDS. CON CRETE E MASONRY. DUCT SYSTEM. SEE TABLE 5 D UC T SYSTEM. V BAND INSTALLED ABOVE THE TOP PLATE. - HORIZONTAL SUPPORT. CEILING. VERTICAL -- ` SUPPORT. '• VERTICAL o• SUPPORT. $!1818 X 1" SELF DRILLING 116 WHIZ NUTS SCREWS. 2 BOLTS USED TO SECURE TOP PLATE. SEE TABLE4-- 20 Fig. 10b —Vertical Floor Support Kit for 2R Type HT Chimney 2R SHECL INSIDE Q 11 MNEY. SUPPORT FLATE. VE ICAL f 5UPPOR.RING. / CO+ABl:SD3LE I�SURFACE. 1142J W.H7 NUTS&BOLTS �5/1 TEX I-°ELFC:{i'*LING USED TO SECURE THE SCR.°WS USED TO SECURE SU"^FLT F.IhG. / CHIbANE.'2R SHEEL. Fig. 10c —Vertical Support Chimney Details VERTICAL FLOOR SUPPORT. BASE MOUNT CAP. BASE CAP. VERTICAL TRANSITION CHININEY SUPPORT PLATE. PLATE.—­, BASE CAP. FIRE STOP. VERTICAL SEE TABLE S. VENTED CERAMIC SUPPORT PING, CUP,B.-- GASKET, VERTICAL l —FLOOR. FIRE SUPPORT._ � STOP. 5/16-18X I"SELF DRILUNG CHIMNEY SCREWS USED TO SECURE CHININEY 2P,SHELL. L i VERTICAL SEE TABLE S. 1/4-20 WHIZ NUTS R BOLTS SUPPORT, USED TO SECURE THE SUPPORT RING. MAXIMUM ANGLE NOT TO EXCEED FIRE STOP 2"CLEARANCE. 30°=US 45°=CANADA INSIDE DOUBLE"V"BAND FLOOR, CHIMNEY. I/2 THREADED ABOVE SUPPORT ROD. PLATES. .-2R SHELL. VERTICAL WALL VERTICAL FLOOR a_ SUPPORT WITH SUPPORT. THREADED ROD SEE FIG 9.&HG IOG,� --WALL. FIRE PLATE 1. I TABLE 6. —FIRE PLATE 2. HARDWARE. I 8'MAXIMUM STRAIGHT LENGTH 30 DEGREES=US / 45 DEGREES=CANADA t 21 Vertical Support for Wooden Wall Construction 1. Wall must be constructed of 2 x 4 wooden studs with a max spacing of 24 inches on center and covered with 5/8 inch gypsum. 2. Install the top wall support plate so that the flat supports plates, when installed, will be under the duct v-band. See Fig 10a for details. 3. The wall support plate has specific holes that locate the side plates so that when installed, they match the duct outer shell diameter. Measure the duct diameter and then measure from the wall plate center holes the radius to locate the first side plate. Example: if the duct being installed has a 30 inch outside shell, measure from the center of the wall plate 15 inches. This will locate the inside of the side plate on the wall plate. Side support plate mounting holes should be on the outside. 4. Once the first wall support plate is located, secure to the wall using the 5/16 x 4 inch toggle bolts and washers. Use the 7/8 inch holes that are 24 inches on center from the side plate mounting holes. In some cases, mounting holes may have to be drilled to align with studs. 5. Follow the instructions above and mount the second wall support plate. Measurement will be 44 inches from the top of the first wall support to the bottom of the second wall support. 6. Install the side support plates. Measure from center and locate the first plate. One of the side plates must be installed using 5/16 x 3 1/2 inch lag bolts and washers directly into the 2 x 4 wooden stud. Fill all holes using the lag bolts and washer that line up with the stud. Lag bolts will secure the wall plates and side plates to the studs. 7. Measure 24 inches from the first stud that the side plate is secured to and install 5/16 x 3 1/2 inch lag bolts and washers. This will secure the wall support plate to the stud 24 inches on center. 8. Measure from center and install the second side plate. This plate may fall between studs and if so, secure using the 5/16 x 4 inch toggle bolts and washers. 9. Repeat the above process so that both wall supports and side plates are installed and secure. 10. Install the rear flat support plate using 5/16 nuts and bolts. Mount the duct so the v band is above the flat support plate and secure by installing the front flat support plate. 11. The v band W"should be sitting on top of the flat plate. A cut out is provided in the flat plate, align the v band bracket with the cutout so it doesn't interfere with the top of the plate. 12. Secure the side support left and right plates to the outer duct shell using the 5/16-18 x 1 inch self- drilling screws. Use the guide holes to locate the shell center and fill all holes center, center left and center right. A minimum of 18 screws must be used on each side of the duct. Figure 10d —Wooden Stud Wall Vertical Support WGYPSUM. 2 X 4 WOODED 24.000 STUDS. ALL SUPPORT PLATE. 116-18 X 1"WHIZ ALL SUPPORT PLATE. UTS&BOLTS. JJJ FLAT SUPPORT PLATE. FLAT SUPPORT PLATE SIDE SUPPORT PLATE. SIDE SUPPORT PLATE MUST BE INSTALLED USING 5h 6 X 4"TOGGLE BOLTS&WASHERS 44.000 WHEN INSTALLED OVER OPEN CAVITIES. SIDE SUPPORT PLATE-MIMIMUM OF ONE SIDE PLATE MUST BE INSTALLED DIRECTLY \� INTO ASTUD USING LAG BOLTS&WASHERS. , --WALL SUPPORT PLATE-MUST BE INSTALLED USING 5A 6 X 31 Z LAG BOLTS&WASHERS DIRECTLYINTO THE 2X 4 STUDS. 5A 6-18 X 1'SELF DRILLING SCREWS. 5116 X 4"TOGGLE BOLTS&WASHERS.. 571648 X 3112"LAG BOLTS &WASHERS INSTALLED DIRECTLY INTO THE 2 X 4 STUDS. 22 I Vertical Support for 25 Gauge Steel Stud Wall Construction 1. Wall must be constructed of 2 x 4 25 gauge (minimum)steel studs with a max spacing of 24 inches on center and covered with 5/8 inch gypsum. 2. Install the top wall support plate so that the flat supports plates, when installed, will be under the duct v-band. See Fig 10a for details. 3. The wall support plate has specific holes that locate the side plates so that when installed, they match the duct outer shell diameter. Measure the duct diameter and then measure from the wall plate center holes the radius to locate the first side plate. Example: if the duct being installed has a 30 inch outside shell, measure from the center of the wall plate 15 inches. This will locate the inside of the side plate on the wall plate. Side support plate mounting holes should be on the outside. 4. Once the first wall support plate is located, secure to the wall using the 5/16 x 4 inch toggle bolts and washers. Use the 7/8 inch holes that are 24 inches on center from the side plate mounting holes. In some cases, mounting holes may have to be drilled to align with studs. 5. Follow the instructions above and mount the second wall support plate. Measurement will be 44 inches from the top of the first wall support to the bottom of the second wall support. 6. Install the side support plates. Measure from center and locate the first plate. One of the side plates must be installed using 5/16 x 1 'h self-drilling screws and washers directly into the 2 x 4 metal studs. Fill all holes using the self-drilling screws and washer that line up with the stud. Self-drilling screws will secure the wall plates and side plates to the studs. 7. Measure 24 inches from the first stud that the side plate is secured to and install 5/16 x 1 1/Z inch self- drilling screws and washers. This will secure the wall support plate to the stud 24 inches on center. 8. Measure from center and install the second side plate. This plate may fall between studs and if so, secure using the 5/16 x 4 inch toggle bolts and washers. 9. Repeat the above process so that both wall supports and side plates are installed and secure. 10. Install the rear flat support plate using 5/16 nuts and bolts. Mount the duct so the v band is above the flat support plate and secure by installing the front flat support plate. 11. The v band W"should be sifting on top of the flat plate.A cut out is provided in the flat plate, align the v band bracket with the cutout so it doesn't interfere with the top of the plate. 12. Secure the side support left and right plates to the outer duct shell using the 5/16-18 x 1 inch self- drilling screws. Use the guide holes to locate the shell center and fill all holes center, center left and center right. A minimum of 18 screws must be used on each side of the duct. Figure 10e —Steel Stud Wall Vertical Support 5.B'GYP SLM. X4-6 GAUGE 24.0)0 STEEL STUDS, ALL SUPPORT PLATE W=LL SUPPORT PLATE FLAT SUPPORT PLATE _ FLAT SUPPORT PLATE S/18.18 X i"WHE NUTS&BOLTS. - _-. 44.000 - SIDE SUPPORT PLATE, =-" - SIDESUPPORT PLATE-MUST BEINSTPLLED USINGS/IOX 4"TO OGLE BOLTS&WASHERS WHEN INSTALLED OVER OPEN CAVITIES OR 25 GAUGE STEEL STUDS, SIDE SUPPORT PLATE-MivlMlRrf Of ONE L..�`Ni.° SIDE PLATE MUST BE INSTALLED DIRECTLY _................. + -- - INTO A STUD WING SELF DRILLING SCREWS &WASHERS. SIDE SUPPORT PLATE WALL SUPPORT PLATE-MUST BE INSTALLED USING 5116 X 1 V!2"SELF DRILLING SCREAi$ &VM HERS DIRECTLY INTO THE 2 X 4(25) AS-18 X I"SELF GAUGE STEEL STUDS. DRILLING SCREWS. /IB X 4"TOGGLE BOLTS&WASHERS_ 5118 X I ill"SELF DRILLING SCREWS &WASHERS INSTALLED DIRECTLY INTO THE X 4(25)GAUGE STEEL STUDS. 23 Vertical Support for Concrete/Masonry Wall Construction 1. These steps describe the method to attach the vertical support to a concrete and (or) masonry wall. 2. Install the top wall support plate so that the flat supports plates, when installed, will be under the duct v-band. See Fig 10a for details. 3. The wall support plate has specific holes that locate the side plates so that when installed, they match the duct outer shell diameter. Measure the duct diameter and then measure from the wall plate center holes the radius to locate the first side plate. Example: if the duct being installed has a 30 inch outside shell, measure from the center of the wall plate 15 inches. This will locate the inside of the side plate on the wall plate. Side support plate mounting holes should be on the outside. 4. Once the first wall support plate is located, secure to the wall using the 5/16 x 2 1/4 inch concrete/masonry screws and washers. Use the 7/8 inch holes that are 24 inches on center from the side plate mounting holes. Install 5/16 x 2 1/4 inch concrete/masonry screws in each end of the wall support plate. In some cases, mounting holes may need to be drilled. 5. Follow the instructions above and mount the second wall support plate. Measurement will be 44 inches from the top of the first wall support to the bottom of the second wall support. 6. Install the side support plates. Measure from center and locate the first plate. Fill all holes using the 5/16 x 2 1/4 inch concrete/masonry screws and washer. Concrete/masonry screws will secure the wall plates and side plates to the wall. 7. Measure 24 inches from the first set of holes in the side plate that is secured to the wall and install 5/16 x 2 1/inch concrete/masonry screws and washers. This will secure the wall support plate to the wall. 8. Measure from center and install the second side plate using 5/16 x 2 1/inch concrete/masonry screws and washers. 9. Repeat the above process so that both wall supports and side plates are installed and secure. 10. Install the rear flat support plate using 5/16 nuts and bolts. Mount the duct so the v band is above the flat support plate and secure by installing the front flat support plate. 11. The v band W"should be sifting on top of the flat plate. A cut out is provided in the flat plate, align the v band bracket with the cutout so it doesn't interfere with the top of the plate. 12. Secure the side support left and right plates to the outer duct shell using the 5/16-18 x 1 inch self- drilling screws. Use the guide holes to locate the shell center and fill all holes center, center left and center right. A minimum of 18 screws must be used on each side of the duct. Figure 1 Of— Concrete/Masonry Wall Vertical Support WALLSUPPORT 24.000 CONCRETEIMASONRY. PLATE. f LATSUPPORT- WALL SUPPORT PLATE. - PLATE. 5H8-18X1`WHI I�i JIIII I PLAT SU PPORT NUTS BOLTS, I� Illpp PLATE. SIDESUPPORT � PLATE. a 44.000 , {tr - SIDE SUPPORT PLATE-MUST BE INSTALLED : - USING 8118 X 2119'CON CRETE IMASONRY - = x SCREWS&WASHERS DIRECTLY IN TO THE WALL WALL SU PPOR T PLATE-MU ST BE INSTALLED USING 8118X2 114'CONCRETE 7 MASONRY SIDE SUPPORT SCREWS&WASHERS DIRECTLY PLATE. INTO THE WALL 18-18 X 1"SELF DRILLING SCREWS. WALL&SIDE SUPPORT PLATE-MUST BE INSTALLED USING U18 X2 1/4"CONCRETEI MASONRY SCREWS&WASHERS DIRECTLY INTO THE WALL. I 24 t Vertical Floor Support for Wooden Floor Construction 1. The vertical floor support is used when the wall support cannot be used or installed directly under a connecting "W band. The vertical support assembly consists of two floor plates with attached support bands. 2. Floor must be constructed of 2"x 8"wooden Joists, 16" on center and covered with 3/4" plywood. 3. The opening in the floor is sized per the outer diameter of the chimney shell and 2" clearance to combustibles per Table 6. 4. Opening example: 16" -2R chimney outer shell diameter is 20". The opening in the floor will be 24- 1/4"which allows for 2" minimum clearance to combustibles and clearance to install fire stop plates when required. 5. Once the opening has been framed, insert the chimney into the opening. 6. Mount the floor support plates onto the floor joist and bolt together using 1/4-20 nuts and bolts. 7. Rotate the floor plates so the sides are aligned with outer edge of the floor joists. 8. Secure the floor plates to the floor using zinc plated #14 x 2" Phillips Head Wood Screws with washers. 9. Slide the chimney up and down until it's in the desired position and secure using 5/16-18 x V zinc plated self-drilling screws. Use a minimum of three screws per opening in the band, see below for details. 10. WARNING, clearance (air space)to combustibles will be free from any type of insulation. Figure 10g —Vertical Floor Support -Wooden Floor Construction t #14x 2'PHILLIPS HEAD WOOD SCREWS&WASHERS INSIDE CHIMNEY. ZINC PLATE. 2R SHELL VERTICAL SUPPORI RING. `-COMBUSTIBLE SURFACE. I y VERTICAL SUPPORT PLATE_ h� rf "'. S/16-18 X I"SELF DRILLING 1/4-20 WHIZ NUTS&BOLTS ' USED TO SECURE THE SCREJJS USED TO SECURE r' CHIMNEY 2R SHEEL. SUPPORT RING. ' } 25 i Vertical Floor Support for Concrete Floor Construction 1. The steps listed below detail the vertical floor support for concrete floors. The vertical floor support is used when the wall support cannot be used or installed directly under a connecting W" band. 2. The vertical support assembly consists of two floor plates with attached support bands. 3. The opening in the floor is sized per the outer diameter of the chimney shell and 2"clearance for combustibles per Table 6. 4. There is no need to account for the 2"clearance for combustibles since the floor is concrete, however, all support plate are sized per the opening example below. 5. Opening example: 16"-2R chimney outer shell diameter is 20". The opening in the floor will be 24- 1/4"which allows for a 2" clearance to combustibles and clearance to install fire stop plates when required. 6. Once the opening has been cut, insert the chimney into the opening. 7. Mount the floor support plates onto the concrete floor and bolt together using 1/4-20 nuts and bolts. 8. Rotate the floor plates so the sides are aligned with the opening. 9. Secure the floor plates to the floor using 5/16-18 x 2 '/" concrete/masonry screws and washers. 10. Slide the chimney up and down until it's in the desired position and secure using 5/16-18 x 1"zinc plated self-drilling screws. Use a minimum of three screws per opening in the band, see below for details. Figure 10h —Vertical Floor Support - Concrete Floor Construction CONCREE SURFACE.—,. /–INSIDE CHIMNEY. - 2R SHELL.— VERTICAL SUPPORT PLATE.------ CONCRETE SURFACE. VERTICAL SUPPORT RING. 511 6-18 X 2 1/4"CONCRETE SCREWS&WASHERS. 1/4-20 WHIZ NUTS&BOLTS 5J16-16 x I"SELF DRILLING USED TO SECURE THE SCRE4'JS USED TO SECURE SUPPORT RING. CHIMNEY 2R SHELL. f 26 r I Through Penetration & Fire Stops Through floor fire stop support assemblies are used to support duct sections that penetrate a fire resistant floor(s). The full support ring is installed under the double V band; the struts are connected to the support ring with supplied 5/16-18 hardware. Once the struts have been connected they are secured to the floor using appropriate type and size fasteners supplied by others. The fire stop support is designed to support the penetrating duct section and maintain annular distance, see Fig. 10a above for details. When duct/chimney systems penetrate a fire resistance rated floor, ceiling and/or a wall, a fire stop kit is used to retain the fire resistance rating on the floor and/or wall. The double wall grease duct and chimney (2R, 2R Type HT, 3R and 3Z)and the fire stop assemblies detailed below have achieved 2-hour ratings for integrity, insulation and stability. Testing was conducted in accordance with the applicable requirements UL 2221, Test of Fire Resistive Grease Duct Enclosure Assemblies. Testing was conducted in accordance with the applicable requirements UL 103, Factory-Built Chimneys, intended for Commercial and Industrial Applications. Table 6 — Opening Size through Penetrations DUCT CHIMNEY INNER OUTER SQUARE/ ROUND SQUARE MODEL DIAMETER DIAMETER OPENING MIN/MAX OPENING 2R Type HT ONLY DW -2R/2R Type HT 8" 12" 14" - 15" 16-1/2" DW -2R/2R Type HT 10" 14" 16"- 17" 18-1/2" DW -2R/2R Type HT 12" 16" 18"- 19" 20-1/2" DW -2R/2R Type HT 14" 18" 20"-21" 22-1/2" DW-2R/2R Type HT 16" 20" 22"-23" 24-1/2" DW-3R/3Z 8" 14" 16"- 17" N/A DW - 3R/3Z 10" 16" 18" - 19" N/A DW - 3R/3Z 12" 18" 20" -21" N/A DW-3R/3Z 14" 20" 22" -23" N/A DW - 3R/3Z 16" 22" 24" -25" N/A DW-3R/3Z 18" 24" 26" -27" N/A DW-3R/3Z 20" 26" 28"-29" N/A DW-3R/3Z 24" 30" 32"- 33" N/A Annular Distance — Fire Stop Fig. 11 —Annular Distance Grease duct / chimney are to be installed eccentrically or concentrically within the fire stop system. The annular space between O.D.PLUS 3"MAX. the grease duct/ chimney and the periphery of the opening shall be a _.._ minimum of 1" to a maximum of 2"for 1 and 2 hour fire rated floor and MIS. wall assemblies. Grease duct / chimney will be rigidly supported on Z MAX. both sides of the floor and or wall assembly. The F and T rating for the fire stop systems shown below are rated for 2 hours. The fire stop ratings are applicable only when Specified Technologies Series SSS F LOO RICE ILING. Latex Intumescent (STI Triple S) Sealant is used. Annular distance is measured perpendicular from the outside of the grease duct/chimney DUCT 0.D. to the periphery of the opening (see Fig. 11 for details). 2R Type HT DUCT. chimney requires 2 inch minimum annular distances all around. i 27 Annular Distance - 2R Type HT Clearance Fig. 12 — Fire Stop Plate Chimney fire stop plates are used to maintain clearance 7-REDUCED HARD4VnPE to combustibles for 2R Type HT listed chimneys. These CLEARANCE. /— fire stop plates are not a substitute for through penetration and fire stop plates referenced above and L S of e E�sLE shown in Fig. 13 & 14. Chimney plates are designed to 1 center the chimney in the recommend opening and ! 2R SHELL maintain 2" clearance to combustibles as shown in C.D• Table 6 above. Chimney fire stop plates consist of two PvESTO \. 2'REDUCED half plates; the plates are designed so they are inserted into the opening. They are installed on the bottom side of the floor. Frame or cut the opening in the floor, see Table 6. Insert the chimney into the opening, and then 2R SHELL+41 insert one half of the fire plate. Secure the half plate using appropriate hardware for wood or concrete construction per Fig. 10g & Fig 10h. Insert the second half plate and secure. Once both plates are secure, the chimney will be centered in the opening with a 2" clearance to combustibles. WARNING, clearance (air space) to combustibles will be free from any type of insulation. Fig. 12a — Chimney Fire Stop Plates INSIDE CHIMNEY. 2R SHELL FLOOR. T 4 1/2' 2R SHELL. OPENING 2R SHELL­r' - JOIST. FLOOR. TABLE b. \—FIRE PLATE 1. + FIRE PLATE. FIRE PLATE 2. HARDWARE. HARDWARE. I 28 Floor & Ceiling Fire Stop Installation 1. Cut an opening in the floor/ceiling that is a minimum of 2" and maximum of 3" larger than the outside diameter of the duct being installed (see Table 6). 2. The grease duct can be installed eccentrically or concentrically within the opening. The distance from the outside of the grease duct to the periphery of the opening cannot exceed 2". 2" is the maximum annular distance allowed (see Fig. 12). 3. Apply a continuous 1/2" bead of STI Triple S intumescent around the fire plates. The fire plates are designed to fit around the duct and overlap by 1". 4. The fire plates are installed on the bottom side of the floor/ceiling. Push the plates up to the floor/ceiling so the intumescent seals the plates against the floor/ceiling. Then secure using '/-20 x 1 '/2" long concrete fasteners where the plates overlap, secure using '/-20 x 1"sheet metal screws. 5. Seal the topside using the intumescent seal around the duct and fire plates. Seal the edge of the opening to the fire plates. 6. Fill the cavity using (4) layers of insulation, make sure that all voids are filled. The insulation is fully compressed into the opening until it is 3/4"from the top of the opening. 7. Cover the compressed insulation with intumescent. Continue until the intumescent is level with the top of the opening. The intumescent should overlap on to the floor/ceiling, ensuring there are no gaps between the edges of the opening or the duct outer shell. 8. Wrap one layer of 1"x 12" provided insulation around the base of the duct and enclose with the half enclosure bands. The insulation and bands should be touching the intumescent, do not disturb or compromise the intumesent when installing. The enclosure bands are assembled using '/4-20 x /" hardware. 9. Install the vertical fire stop support; ensuring the full support ring is installed under the double V band. Once in place, the legs are secured to the floor/ceiling using appropriate type and size fasteners (see Fig. 12 for details). Fig. 13 — Floor & Ceiling Fire Stop Installation STEP 1 STEP 2 DUCT SECTION. DUCT SECTION. TOP SIDE. SEE TABLE 6. TOP SIDE. INTUMESCENT SEALANT. FIRE PLATES INTUMESCENT FIRE PLATES. CONCRETE SECURED. SEALANT, SCREWS, STEP 3 STEP 4 DUCT SECTION. DUCT SECTION. DOUBLE V BAND. TOP SIDE, INSULATION. INTUMESCENT- \ CONCRETE VERTICAL SUPPORT. SEALANT. ANCHORS, HALF CLOSURE HALF CLOSURE BANDS, BANDS SECURED. 29 I Wall Fire Stop Installation 1. Cut an opening in the wall that is a minimum of 2" and maximum of 3" larger than the outside diameter of the duct being installed. See Table 6. 2. The grease duct can be installed eccentrically or concentrically within the opening. The distance from the outside of the grease duct to the periphery of the opening cannot exceed 2". 2" is the maximum annular distance allowed; see Fig. 12. 3. Apply a continuous 1/2" bead of STI Triple S intumescent around the closure plates; the fire plates are designed to fit around the duct and overlap by V. 4. The fire plates are installed on the backside of the wall. Push the plates up to the wall so the intumescent seals the plates against the wall. Then secure using '/-20 x 1 '/2" long concrete fasteners where the plates overlap secure using '/4-20 x 1" sheet metal screws. 5. Apply a 3/" covering of intumescent sealant to the inside of the fire plates installed on the backside of the wall. The sealant should be smooth and without any gaps on the edges of the opening or outside of duct. 6. Fill the cavity using the insulation provided, ensuring that all voids are filled. The insulation is fully compressed into the opening until it is 3/"from the edge of the opening in the wall. 7. Cover the compressed insulation with intumescent. Continue until the intumescent is flush with the edge of the wall opening. The intumescent should overlap on to the wall, ensuring there are no gaps between the edges of the opening or the duct outer shell. 8. Install the fire plates on the front side of the wall. Push the plates up to the wall so the intumescent seals the plates against the wall. Then secure using '/-20 x 1 '/2" long concrete fasteners where the plates overlap secure using '/-20 x 1" sheet metal screws. 9. Wrap one layer of 1"x 12" provided insulation around the base of the duct and enclose with the half enclosure bands. The insulation and bands should be touching the intumescent. The enclosure bands are assembled using '/-20 x 1" hardware. This is done on the front and back of the wall. 10. Horizontal supports are used to support the duct on either side of the wall. See Fig. 9 for details. Fig. 14—Wall Fire Stop Installation STEP 1 STEP 2 WALL. FIRE PLATES. /--INSULATION. HALF CLOSURE BANDS. INSULATION. DUCT SECTION. CONCRETE , FIRE PLATES. I -INTUMESCENT. 114-20 HARDWARE, WALL. FIRE PLATES. HORIZONTAL SUPPORT EITHER,SIDE OF OPENING. INTUMESCENT. ->' HALF CLOSURE x BANDS. CONCRETE SCREWS. INSULATION. y DUCT SECTION. 114.20 HARDWARE. DETAIL 30 Grease Duct lnstallat�ort , Grease Duct Assembly Examples The illustration shown provides useful Fig. 15 - Grease Duct Installation Guide information on =the instattation of grease ituct systetns.: Each-=instalIatlon:ls specific to fhe: application and the joh: site.if you encounter"a. Adjustable duct and standard ducts are -sifuatibmhot'covered,6y this illustration, refer to used to terminate at the transition plate. the guide or cor sultthi factory 7lie grease;duct._; The duct section is fully welded to the systems illustrated in`thas1r►anual::have_"been, transition plate at the factory. tested to and:cornply-with 0 2221,'lests of Fire Resistive Grease Duct Enclosure Assernblles.- EXHAUSTFAN, VENTED CURB. ROOF. VERTICAL SUPPORT INSTALLED UNDER —ADJUSTABLE DUCT. THE DOUBLE V BAND. DOUBLE V D D. STANDARD D D U UCT LENGTH. SEE TAB LE 5. IN SU LATE D ACC ESS DOOR COVER ITEE. y_ a' + STANDARD DUCT LENGTH. t. r DOUBLE V BAND. STANDARD DUCT LENGTH. FIRSTVERTICAL SUPPORT 45 DEGREE ELBOW, /� AT J OIN T#I AFTER CHAN 0 E / IN DIRECTION INSTALLED UNDER ADJUSTABLE DUCT. L a THE DOUBLE V BAND. INSULATED ACCESS DOOR COVER/TEE. 112"THREADED ROD MINIMUM. /—ACCESS DOOR PROVIDED -, —ACCESS IN DIRECTION_ RISER COVERS, — u qq STANDARD DUCT LENGTH. EXHAUST HOOD. ��N --SEE TABLE 4. DUCT SENSOR. i l 31 Fig. 16 - Grease Duct Installation Guide Grease Quct [nsta[[at[on The ill,U§tfatlon shown provides,_ usefa[,' Adjustable duct and standard ducts are information on the ins#allation ;of. grease;iuct used to terminate at the transition plate. systems;° Eachnstaliation ,is specific to the The duct section is fully welded to the application and the fob sate,' vou`,encounter a':, transition plate at the factory. situation not covered-b this illustration, refer to: St, guide or consult ttie factory ,The grease:duc#'' systems illustrated in=this rrianual `have..been tes#ed,#a acid coinpiy with UL 2221.r Tests=of:Fire- Resistive°Grease Duct EnciosuCe Assetn}alies; EXHAUST FAN. VENTED CURB. r s ROOF. ` ADJUSTABLE DUCT. VERTICALSUPPORT INSTALLED UNDER THE DOUBLE V BAND. _ _ -»»- �—DOUBLE V BAND_ TEE-ACCESS DOORS �- ~ STANDARD DUCT LENGTH. CLEA N 0 UT P 01 NTS AFTER CHANGE IN DIRECTION, INSULATED ACCESS FIRST VERTICAL SUPPORT DOOR COYER f TEE. AT JOINT#9 AFTER CHANGE IN DIRECTION INSTALLED UNDER THE DOUBLE V BAND, SEE TABLE 5. RISER COVERS. HORIZONTAL SUPPORT, SEE TABLE 4. EXHAUST HOOD HEIGHT HOOD Haoo WIDTH +cea WNG I 32 Fig. 17 - Grease Duct Installation Guide _ Grease Duct InstaI145q0 The illustration shown pr()v des, , useful? Adjustable duct and standard ducts are mforrttatlon on the iris#atlaibn,;of`grease :duct ` used to terminate at the transition plate. systerns Eac>a "rnstaliat�on",is;s#secrf;c -to�'_the The duct section is fully welded to the app lrcafon and the job s1te: if you encounter a transition plate at the factory. situation not ctivered. Y iis Mustratiion, refdr to`- the gurde or cgnsutt the facto +-The grease ducE sys#erns alt Usti a#ed in this"-tnariva!;have`been'" fes#eri t#and comply"wr#h t11-2221, Tests,o€-Frre"'' Res�sil�e Grease Duct Erictosure Assembtles , EXHAUST FAN. =� ADJUSTABLE SECTION VENTED CURB. TERMINATES AT THE VENTED CURB. _ TRANSITION PLATE. • ROOF. \\\ ADJUSTABLE DUCT COLLAR. ADJUSTABLE INSTALLED UNDE RT 1 DUCT SECTION. - IN SULATION THE DOUBLE V BAND OUTER SHELL t } REMOVED FOR CLARITY, STANDARD DUCT LENGTH. DOUBLE V BAND, STANDARD DUCT LENGTH. DUCT SENSOR. DOUBLE V BAND. RISER COVERS, DUCTSENSOR. EXHAUST EXHAUST HOOD HOOD 33 Chimney lnsmallatlon- Fig. 18 - Chimney Installation Guide The r11 tratian sown -provides useful In ormatton on'.fhe. irsstalla#ion of=a chiit)rsey system .',Each mstaliatrcin: .is specife to_'tfae application anti the job slte. .lf you encounter a situation not covered by this ilustra#ion, refer to the guItle or cgnsult he facfory -Tle chimney;,, systems:,illus#rated rn_;this .inanua{'_have been tested to and ,cotnpty`with `.UL :1a3< Type Ti H Eac#ory Built Ghimneys for.'Bonding Heating Ajapliances UL I43 t r CAP. CAP. TOP RISER MAX 8'-ROOF COVER& SUPPORT ASSEMBLY } AIR SHAH'. Y'BAND.— WITHOUTSUPPORT uEr•e7ED MIN 2' CURB. FROM ROOF FLty IGE RING. TO P RISER END CAP. CON N CTION. 2R—I43 —--SINGLE'Y'BAND CHIMhlEY.� USED TO CONNECT RRE STOP PL E - SEE TABLE 5. CAP TO CHIMNEY. AT USED FOR 2` TO?RISER CLEARANlCE T O COM USTABLES.° COVER& TOP RISER Y'B r D. CONNECTION. ir.RNSTROt WALL PLATE.— VERTICAL COMBUSTIBLE WALL SUPPOT.—\ SURF"ACE. SEE TABLE 5. FIRE STOP PLATE USED FOR 2" CLEARANCE TO COMBUSTABLES. 2R 343 CHIMNEY. caN1NECnar1 TO , EQUIPMENT EfIHER WELDED OR BOLTED FIELD MTALL4TION1. EQUIPMENT. t 34 i Chimney Installation-- Fig. 19 - Chimney Installation Guide Tile tliustratian shown- "provides useful information on"the ii5stailatian of "a Chirrrney" :system ;Each ,instaliatton ts=specific to "=the application and the"Job site tf:you encounter a situation,not covered iby this illustratirn, refer to.,- ti►e guide or consult the factory The chimney'. systems ;tllus#rated in,thfs tianual 'have,.been; tested to and comply-with U _ G3 Type.)iT,: FO or Ghtmneys for ,;Budding Heating ;.Appliances VERTICAL FLOOR SUPPORT. BASE MOUNT CAP. BASE CAP— _r /—VERTICAL TRANSITION CHIMNEY SUPPORT PLATE. PLATE-� BASE CAP. FIRE STOP.- -VERTICAL VELD SEE TABLE 5. SUPPORT RING. GASKET. CURB.–­_ GASKET. VERTICAL FLOOR. FIRE / SUPPORT. STOPr -" I 5116-18X 1"SELF DRILLING '--CHIIv1NEY - SCRMS USED TO SECURE CHIA4NEY 2R SHELL. 1/4-20 WHIZ NUTS&BOLTS VERTICAL SEE TABLE 5. SUPPORT. USED TO SECURE THE I SUPPORT RING. MAXIMUM ANGLE NOT TO EXCEED FIRE STOP 2"CLEARANCE. 30°=US 45'=CANADA INS DE DOUBLE"V'BAND FLOOR. �CHININEY. 1(2 THP ABOVE.SUPPORT PLATES. �---2R SHELL. ROD.. VERTICAL FLOOR "—V�P,TICAL WALL SUPPORT WITH SUPPORT. THREADED ROD SEE FIG 9.B,FIG IOG.— WALL t --FIRE PLATE 1. FIRE PLATE 2 TABLE b. 8'MAXIMUM -HARDWARE. STRAIGHT LENGTH 30 DEGREES=US j 45 DEGREES=CANADA i I 35 METHODS USED TO TEST DUCT AFTER ASSEMBLY Prior to the concealment of any portion of a grease duct system, a leakage test shall be performed in the presence of the code official. Duct shall be considered to be concealed when installed in shafts, or covered by coatings or wraps that prevent the ductwork from being visually inspected on all sides. A light test or approved equivalent test method (smoke test) shall be performed to determine that all joints are liquid tight. The smoke test is used for longer duct runs while the light test is used for short duct runs; both methods are approved for use. Method 1 — Light Test per IMC 506.3.3.1 A light test shall be performed by passing a lamp having a power rating of not less than 100 watts through the entire section of ductwork to be tested. The lamp shall be open so as to emit light equally in all directions perpendicular to the duct walls. The test shall be performed for the entire duct system, including the hood-to- duct connection. The ductwork shall be permitted to be tested in sections, provided that every joint is tested. Method 2 — Smoke Test After the ductwork has been installed allow the listed sealant to cure for a minimum of 24 hours. Smoke bombs are lit and placed at the bottom of the duct system; natural upwards drafts will pull the smoke to the top of the duct system. Various length duct runs may require multiple smoke bombs. Once the smoke has reached the top of the duct run, cap the duct securely. Inspect all joints for leakage. GENERAL DUCT WEIGHTS The average weight of the duct, per foot of length, can be calculated using the following formulas below. Duct design should provide adequate support to ensure duct components are not overloaded. Weight — DW-2R r The following formula can be used to approximate the weight of total length of DW-2R double wall duct. Inner Shell + Outer Shell + Insulation or(.0327*L*D) + [.0218*L*(D+4)] + [.0364*L*(D+2)]. Weight — DW-3R The following formula can be used to approximate the weight of total lengths of DW-3R double wall duct. Inner Shell + Outer Shell + Insulation or(.0327*L*D) + [.0218*L*(D+6)] + [.0436*L*(D+3)]. Weight — DW-3Z The following formula can be used to approximate the weight of total lengths of DW-3Z double wall duct. Inner Shell + Outer Shell + Insulation or(.0327*L*D) + [.0218*L*(D+6)] + [.0491*L*(D+3)]. a Weight — Example The"D"value in the formulas above represents the inner duct diameter in inches. The"L"value in the formulas above represents the total length in inches. Duct system: DW-3Z, 12" inner duct, 100 FT long. Using the DW-3Z formula above, (.0327*1200*12) + (.0218*1200*18) + (.0491*1200*15) = 1825 lbs. 36 CLEANING & MAINTENANCE RECORD Date Service Performed Factory Service Department Phone: 1-866-784-6900 Fax: 1-919-554-9374 ,i 40