Loading...
4600 Slater Rd - Kwik Trip HVAC Balance ReportGREAT LAKES BALANCING, INC. d/b/a HVAC Systems Analysis Gordon Rupkalvis, Owner 1630 8th Street SE AIR & WATER BALANCING Pine Island, MN 55963 NEBB CERTIFIED SINCE 1988 Cell (507) 951-2823 Fax (507) 356-2096 Email: hvacsystems2004@yahoo.com Page 1 of 12 PROJECT #16-029 NEBB CERTIFIED TEST, ADJUST, AND BALANCE REPORT DATE DECEMBER 6, 2016 PROJECT KWIK TRIP STORE #179 CLIFF ROAD & SLATER ROAD ADDRESS EAGAN, MN ARCHITECT VANTAGE ARCHITECTS ENGINEER JDR ENGINEERING, INC. DATE OF PLANS MARCH 22, 2016 HVAC CONTRACTOR TONNA MECHANICAL TEMP. CONTROL CONTRACTOR TONNA MECHANICAL TESTING & BALANCING SUPERVISOR GREAT LAKES BALANCING, INC. d/b/a HVAC Systems Analysis Gordon Rupkalvis, Owner 1630 8th Street SE AIR & WATER BALANCING Pine Island, MN 55963 NEBB CERTIFIED SINCE 1988 Cell (507) 951-2823 Fax (507) 356-2096 Email: gordy@glb2004.com TABLE OF CONTENTS DOCUMENT PAGE CERTIFICATION..................................................................................................................................3 INSTRUMENTS....................................................................................................................................4 UNIT DATA SHEETS........................................................................................................................5-8 FAN TEST REPORT.............................................................................................................................9 OUTLET SHEETS..........................................................................................................................10-11 WATER REPORT................................................................................................................................12 ABBREVIATIONS.................................................................................................................appendix i CERTIFICATION PROJECT KWIK TRIP STORE #179 ADDRESS CLIFF ROAD & SLATER ROAD EAGAN, MN The data presented in this report is an exact record of system performance and was obtained in accordance with NEBB standard procedures. Any variances from design quantities which exceed NEBB tolerances are noted throughout this report. The air distribution systems have been tested and balanced and final adjustments have been made in accordance with NEBB “Procedural Standards for Testing, Adjusting, Balancing of Environmental Systems” and the project specifications. NEBB TAB FIRM GREAT LAKES BALANCING, INC. d/b/a HVAC Systems Analysis________ Reg. No. 2618 Certified by: Gordon Rupkalvis Date December 6, 2016 (Air TAB Supervisor) The hydronic distribution systems have been tested and balanced and final adjustments have been made in accordance with NEBB “Procedural Standards for Testing, Adjusting, Balancing of Environmental Systems” and the project specifications. NEBB TAB FIRM GREAT LAKES BALANCING, INC. d/b/a HVAC Systems Analysis________ Reg. No. 2618 Certified by: Gordon Rupkalvis Date December 6, 2016 (Water TAB Supervisor) SUBMITTED & CERTIFIED BY: NEBB TAB FIRM GREAT LAKES BALANCING, INC. d/b/a HVAC Systems Analysis________ TAB SUPERVISOR Gordon Rupkalvis REG. NO. 2618 DATE December 6, 2016 CERTIFICATION EXP. DATE 03/31/17 GREAT LAKES BALANCING, INC. d/b/a HVAC Systems Analysis Gordon Rupkalvis, Owner Pine Island, MN 55963 AIR & WATER BALANCING Cell (507) 951-2823 NEBB CERTIFIED SINCE 1988 Fax (507) 356-2096 Email: gordy@glb2004.com page 4 of 12 Instrument Ownership for Firm HVAC Systems Analysis NEBB Certificate No. 2618 Date: 12-6-2016 Minimum Minimum Minimum Calibration Function Range Accuracy Resolution Instrument Information Interval/Date Humidity 10 to 90 % RH 2% of reading 1%Exteck Psychrometer 12 Months Measurement RH-390 Date Serial No. 11118575 3/30/2016 Air Volume 100 to 2000 5% reading Digital 1 cfm Shortridge 12 Months Measurement cfm ADM 870 Date Flow Hood Serial No. M88490 3/15/2016 Rotation 0 to 5000 rpm 2% of reading 30 rpm Nova Stobe dbx 12 Months Measurement Date Serial No. 2568465 4/1/2016 Temperature minus 40 to 1% of reading .2 deg. F (US)Extech Dual K Thermocouple 12 Months Measurement 240 deg. F Thermometer EA 10 Date Air Serial No. 120701154 3/25/2016 Temperature minus 40 to 1% of reading .2 deg. F (US)Extech Dual K Thermocouple 12 Months Measurement 240 deg. F Thermometer EA 10 Date Immersion Serial No. 120701154 3/25/2016 Temperature minus 40 to 1% of reading .2 deg. F (US)Davis Instruments Angle 12 Months Measurement 240 deg. F Surface Probe Type K Date Contact Serial No. BN215704 3/30/2016 Electrical 0 to 600 VAC 2% of reading 1.0 Volt Fluke True RMS Clamp 12 Months Measurement 0 to 100 Amps .1 Amperage Meter 324 Date True RMS Serial No. 26860058WS 3/25/2016 Air Pressure 0 to 10" WG 5% of reading .01" WG Shortridge 12 Months Measurement ADM 870 Date Serial No. M88490 3/15/2016 Air Velocity 50 to 2500 fpm 5% of reading 1 fpm TSI Hotwire 12 Months Measurement 8384A Date Serial No. 55040646 3/23/2016 Hydronic 0 to 100" WG 2% of reading 1" WG Shortridge 12 Months Differential 0 to 100' WG 2% of reading 1.0 ft WG HDM-250 Date Measurement Serial No. W95093 4/12/2016 Air Velocity 50 to 2500 fpm 1% of reading 1 fpm TSI Alnor 12 Months Measurement RVA801 Date Rotating Vane Serial # A03116 4/5/2016 All or some of these instruments were used on this project. Copies of calibration certificates for each instrument will be made available upon request. All instruments are owned by HVAC Systems Analysis, NEBB Certification number 2618. Copies of all company's certifications available on request. 1630 8th Street SE HVAC SYSTEMS ANALYSIS, INC. NEBB UNIT DATA SHEET PAGE 5 of 12 12/6/2016 PROJECT KWIK TRIP EAGAN, MN #179 LOCATION EAGAN, MN 16-029 SYSTEM NO.RTU-1 MAKE Trane MODEL NO.YHD180G3RLA1YHF SERIAL NO.163610256D DESIGN 5640 CFM @1.5" ESP with 1125 OA CFM Minimum MOTOR Marathon HP 5 PH 3 FR 182T SF 1.15 VOLTS 208 FL AMPS 13.4 MOTOR RPM 3450 MOTOR ROTATION CCW STARTER Control System SHEAVE X BORE DRIVEN 1BK140 / 1.1875" SHEAVE X BORE DRIVER 1VP34 / .875" BELTS NO. & SIZE 1 / BX-71 DRIVE CHANGE Yes BELT CHANGE No FILTERS (8) 20"/20"/2" MERV 13, (4) 16"/20"/2" MERV 13 TEST MODE Tested under Normal Operation, OA 30° RETURN DAMPER 100% Estimated OUTSIDE AIR DAMPER 0% COOLING COIL Dry CONDENSATE LINE TRAPPED Yes STATICS FAN IN 0.60 OUT 0.85 RISE 1.45 FILTERS - COOLING COIL IN 0.43 OUT 0.60 DROP 0.17 EXTERNAL SP IN 0.43 OUT 0.85 RISE 1.28 PRELIMINARY FINAL CFM 6414 5615 MINIMUM O/A ERU 1566 1196 MOTOR RPM 3428 3429 FAN RPM 829 744 VOLTS 210 210 AMPS 8.66 7.85 REMARKS:Return outlets are filtered. HVAC SYSTEMS ANALYSIS, INC. NEBB UNIT DATA SHEET PAGE 6 of 12 12/6/2016 PROJECT KWIK TRIP EAGAN, MN #179 LOCATION EAGAN, MN 16-029 SYSTEM NO.RTU-2 MAKE Trane MODEL NO.YHC048E3RLA1JKA SERIAL NO.163712540L DESIGN 1600 CFM @ 1.2" ESP with 240 CFM OA Minimum MOTOR Marathon HP 1 PH 3 FR 56 SF 1.15 VOLTS 208 FL AMPS 3.4 MOTOR RPM 1725 MOTOR ROTATION CCW STARTER Control System SHEAVE X BORE DRIVEN 1AK54 / .75" SHEAVE X BORE DRIVER 1VP34 / .875" BELTS NO. & SIZE 1 / AX-29 DRIVE CHANGE Adjusted BELT CHANGE No FILTERS (4) 25"/16"/2" MERV 13 TEST MODE Tested under Normal Operation, OA 30° RETURN DAMPER 100% Estimated OUTSIDE AIR DAMPER 0% COOLING COIL Dry CONDENSATE LINE TRAPPED Yes STATICS FAN IN 0.37 OUT 0.26 RISE 0.63 FILTERS - COOLING COIL IN 0.24 OUT 0.37 DROP 0.13 EXTERNAL SP IN 0.24 OUT 0.26 RISE 0.50 PRELIMINARY FINAL CFM 1709 1604 MINIMUM O/A 364 286 MOTOR RPM 1777 1777 FAN RPM 822 790 VOLTS 209 209 AMPS 2.19 2.15 REMARKS:Return outlet filtered. HVAC SYSTEMS ANALYSIS, INC. NEBB UNIT DATA SHEET PAGE 7 of 12 12/6/2016 PROJECT KWIK TRIP EAGAN, MN #179 LOCATION EAGAN, MN 16-029 SYSTEM NO.MAU-1 MAKE CaptiveAire MODEL NO.A-1 D.250 G10D SERIAL NO.2740320-2 DESIGN 1760 CFM @ .7" ESP MOTOR Emerson HP 1 PH 1 FR 48 SF NA VOLTS 115 FL AMPS 10.2 MOTOR RPM 1800 Varies MOTOR ROTATION CW STARTER Wall Switch HEATERS Set to 10.2 Amps SHEAVE X BORE DRIVEN Direct Drive SHEAVE X BORE DRIVER Direct Drive BELTS NO. & SIZE Direct Drive DRIVE CHANGE Adjusted to Design CFM BELT CHANGE Direct Drive FILTERS (3) 20"/16"/2" Washable TEST MODE Tested under Normal Operation, OA Temperature 30° OUTSIDE AIR DAMPER 100% STATICS FAN IN 0.48 OUT 0.22 RISE 0.70 FILTERS IN 0.00 OUT 0.24 DROP 0.24 BURNER SP IN 0.24 OUT 0.48 DROP 0.24 PRELIMINARY FINAL CFM 1431 1779 MOTOR RPM 890 966 FAN RPM 890 966 VOLTS 120 120 AMPS 2.1 2.56 REMARKS:Speed controller set to design CFM flow. CFM measured at hood grilles. NEBB UNIT DATA SHEET PAGE 8 of 12 12/6/2016 PROJECT KWIK TRIP EAGAN, MN #179 LOCATION EAGAN, MN 16-029 SUPPLY EXHAUST SYSTEM NO.ERV-1 MAKE Renewaire MODEL NO.HE2XRT SERIAL NO.I162911C DESIGN 1125 925 MOTOR Baldor Baldor HP 1.5 1.5 PH 3 3 FR 145T 145T SF 1.15 1.15 VOLTS 208 208 FL AMPS 4.4 4.4 MOTOR RPM 1750 1750 MOTOR ROTATION CW CW STARTER Control System Control System HEATERS Set 4.5 Set 4.5 SHEAVE X BORE DRIVEN 1BK50 / 1"1AK64 / 1" SHEAVE X BORE DRIVER 1VP40 / .875"1VP40 / .875" BELTS NO. & SIZE 1 / A-35 1 / A-38 DRIVE CHANGE Adjusted Yes BELT CHANGE No No FILTERS (2) 20"/20"/2" Plus HX (2) 20"/20"/2" Plus HX TEST MODE Tested under Normal Operation OUTSIDE AIR TEMP. FRESH AIR TEMP. EXHAUST AIR TEMP RELIEF AIR TEMP. STATICS FAN SUPPLY IN 0.60 OUT 0.09 RISE 0.69 FILTERS ERV IN 0.11 OUT 0.60 DROP 0.49 FAN EXHAUST IN 0.58 OUT 0.10 RISE 0.68 FILTERS ERV IN 0.16 OUT 0.58 DROP 0.42 SUPPLY EXHAUST CFM 1196 925 MOTOR RPM 1777 1778 FAN RPM 1150 962 VOLTS 210 210 AMPS 2.15 2.26 REMARKS:Interlocked with RTU-1. 31.5° 58.4° 70.2° 48.7° HVAC SYSTEMS ANALYSIS, INC. NEBB FAN TEST REPORT PAGE 9 of 12 16-029 PROJECT KWIK TRIP EAGAN, MN #179 EAGAN, MN FAN DATA FAN NO. EF-1 Location Roof Service Hood Manufacturer CaptiveAire Model Number DU85HFA Serial Number 2740320-1 Type/Class Upblast Motor Make US Electric Motor Style Open Motor HP/RPM/Frame .75 / 1800 Varies / 56 Volts/Phase/Hertz *115 / 1 / 60 FL Amps/S.F.8.8 / 1.0 Motor Sheave Make Direct Drive Motor Sheave Diam/Bore Direct Drive Fan Sheave Make Direct Drive Fan Sheave Diam/Bore Direct Drive No. Belts/Size Direct Drive Sheave CL Distance Direct Drive Drive Condition - Motor New Rotation CCW Starter Wall Switch * Wired Voltage TEST DATA DESIGN ACTUAL CFM 2200 2256 Fan RPM 1366 1269 Motor RPM 1366 1269 Total SP 1" NA Voltage 115 120 Amperage 8.8 3.5 REMARKS:EF-1 interlocked with MAU-1. CFM measured in duct opening on hood. Speed controller set to design CFM. DATE:6-Dec-16 TESTED BY:RUPKALVIS HVAC SYSTEMS ANALYSIS, INC. NEBB OUTLET AIR BALANCE REPORT PAGE 10 of 12 PROJECT KWIK TRIP EAGAN, MN #179 JOB NO.16-029 Date 12/6/2016 LOCATION EAGAN, MN System RTU-1 INSTRUMENTS SHORTRIDGE AIR DATA METER # M99549 Tested By RUPKALVIS ROOM OPENING REQUIRED PRELIMINARY FINAL AREA SERVED NO.MODEL SIZE AK VEL CFM VEL CFM %VEL CFM RTU-1 TOTAL 5640 6414 1.00 5615 100 Vestibule 1 CD-2 8" Dia.160 249 165 101 Sales 1 CD-2 8" Dia.175 155 181 101 Sales 2 CD-2 8" Dia.175 190 177 101 Sales 3 CD-3 10" Dia.350 375 350 102 Checker 1 CD-2 8" Dia.175 212 181 102 Checker 2 CD-2 8" Dia.175 230 183 103 Coffee 1 CD-4 12" Dia.445 496 440 103 Coffee 2 CD-4 12" Dia.445 421 429 103 Coffee 3 CD-4 12" Dia.445 549 435 103 Coffee 4 CD-4 12" Dia.445 401 449 103 Coffee 5 CD-4 12" Dia.445 397 429 103 Coffee 6 CD-4 12" Dia.445 465 440 103 Coffee 7 CD-4 12" Dia.445 459 445 103 Coffee 8 CD-4 12" Dia.445 391 400 112A Data 1 CD-1 8" Dia.150 347 155 109 Mens 1 CD-1 6" Dia.100 150 104 108 Women's 1 CD-1 6" Dia.100 149 99 112 Office 1 CD-2 8" Dia.110 159 109 111 Delivery 1 CD-2 8" Dia.160 224 171 117 Family 1 CD-1 6" Dia.50 159 51 115 Utility 1 SG-1 6" Dia.100 98 124 116 Storage 1 SG-1 6" Dia.100 138 98 RETURN TOTAL 4365 3856 0.90 3915 101 Sales 1 RG-1 24"/24"790 586 687 101 Sales 2 RG-1 24"/24"790 730 804 101 Sales 3 RG-1 24"/24"785 690 790 101 Sales 4 RG-1 24"/24"785 687 700 101 Sales 5 RG-1 24"/24"785 510 534 112 Office 1 RG-2 10"/10"110 89 90 100 Vestibule 1 RG-1 24"/24"160 410 158 111 Stairs 1 RG-2 8"/8"160 154 152 ERV FRESH 1 DUCT 16" Dia.1.40 805 1125 1122 1566 1.06 857 1196 REMARKS: HVAC SYSTEMS ANALYSIS, INC. NEBB OUTLET AIR BALANCE REPORT PAGE 11 of 12 PROJECT KWIK TRIP EAGAN, MN #179 JOB NO.16-029 Date 12/6/2016 LOCATION EAGAN, MN System AIR SYSTEMS INSTRUMENTS SHORTRIDGE AIR DATA METER # M99549 Tested By RUPKALVIS ROOM OPENING REQUIRED PRELIMINARY FINAL AREA SERVED NO.MODEL SIZE AK VEL CFM VEL CFM %VEL CFM RTU-2 TOTAL 1600 1709 1.00 1604 105 Kitchen 1 CD-5 14"/14"400 590 399 105 Kitchen 2 CD-5 14"/14"400 434 389 105 Kitchen 3 CD-5 14"/14"400 330 411 105 Kitchen 4 CD-5 14"/14"400 355 405 RETURN 1 RG-1 24"/24"680 690 673 2 RG-1 24"/24"680 655 645 MAU-1 TOTAL 1760 1431 1.01 1779 MAIN DUCT 1 GRILLE 124”/14”12.44 141 1760 115 1431 143 1779 EF-1 Hood Opening 1 OED 18" Dia.1.77 1250 2200 1148 2029 1.03 1277 2256 ERV-1 TOTAL 925 1358 1.00 925 110 Mop 1 EG-1 10”/6”125 118 118 109 Mens 1 EG-1 8"/8"75 150 71 109 Mens 2 EG-1 8"/8"75 111 77 109 Mens 3 EG-1 8"/8"150 167 153 108 Women's 1 EG-1 8"/8"75 139 75 108 Women's 2 EG-1 8"/8"75 129 74 108 Women's 3 EG-1 8"/8"75 139 81 116 Family 1 EG-1 8"/8"75 114 77 115 Utility 2 EG-1 8"/8"200 291 199 ERV FRESH 1 DUCT 16" Dia.1.40 805 1125 1122 1566 1.06 857 1196 TF-1 112A Data 1 CF 24"/24"150 204 204 REMARKS: TF-1: No adjustment possible. HVAC SYSTEMS ANALYSIS, INC. NEBB WATER BALANCE REPORT PAGE 12 of 12 PROJECT KWIK TRIP EAGAN, MN #179 JOB #16-029 Date 12/6/16 LOCATION EAGAN, MN System WATER SYSTEMS INSTRUMENTS SHORTRIDGE HYDRO-METER # W95097 Tested By RUPKALVIS TAG REQUIRED FULL OPEN SETTING FINAL NO.ITEM SIZE P*GPM P*GPM %NO.% P*GPM BC-1 Sales 1" B&G 5.6 1.8 0.5 0.0 1.8 5.5 BC-2 Coffee 1.5" B&G 8.3 0.2 NA 20.0 1.0 8.5 BC-3 Toilets .75" B&G 1.2 0.4 NA 40.0 4.0 1.2 BC-4 CBT .75" B&G 0.9 0.4 NA 50.0 8.8 0.9 BC-5 Thaw .75" B&G 2.6 1.7 2.9 0.0 1.7 2.9 UH-1 Delivery .75" B&G 1.9 0.7 NA 10.0 1.0 1.9 UH-3 Storage .75" B&G 1.9 0.9 NA 20.0 2.4 2.0 P-1 Boiler Pump 2" NIBCO 19.0 0.5 22.0 5.0 0.8 19.0 P-4 Infloor .75" B&G 1.9 0.7 NA 15.0 1.5 1.9 * Can represent flow station differential or pressure drop across item. REMARKS:Heating water system tested under a full flow condition. Set point 7 PSI. P-1: Pump set to medium speed. P-4: Pump set to high speed. ABBREVIATIONS AC Air Conditioning HP Horsepower ACT Actual HRU Heat Recovery Unit AHU Air Handling Unit HTG Heating AMP Ampere HZ Hertz (Cycles per Second) BDD Back-draft Damper KW Kilowatt BHP Brake Horsepower LAT Leaving Air Temperature BI Backwards Inclined LB Pound BTU British Thermal Unit LF Linear Feet BTUH BTU per Hour LWT Leaving Water Temperature CC Clockwise MAU Make-Up Air Unit CCW Counter Clockwise MAX Maximum CF Cubic Feet MBH 1000 BTUH CFM Cubic Feet per Minute MECH Mechanical CH Chilled or Chiller MIN Minimum CHW Chilled Water MUA Make-Up Air Unit CHWR Chilled Water Return OA Outside Air CHWS Chilled Water Supply PD Pressure Drop CL Centerline PH Phase CUH Cabinet Unit Heater PRESS Pressure CWR Condenser Water Return PRV Pressure Reducing Valve CWS Condenser Water Supply PSI Pounds per Square Inch DB Dry Bulb RA Return Air DEG Degree RPM Revolutions per Minute DDC Direct Digital Control RTU Roof-Top Unit DIA Diameter SA Supply Air DIFF Differential SP Static Pressure DIM Dimension SF Square Feet DISCHG Discharge SUP Supply DP/ P Differential Pressure TEMP Temperature EAT Entering Air Temperature TSTAT Thermostat EF Exhaust Fan V Volts EMS Energy Management System VAV Variable Air Volume ERU Energy Recovery Unit VEL Velocity ESP External Static Pressure VFD Variable Frequency Drive EUH Electrical Unit Heater WPD Water Pressure Drop EWT Entering Water Temperature WTD Water Temperature Drop EXH Exhaust EX Exhaust B&G Bell & GossettEXTExternal F Fahrenheit GE General Electric FCU Fan Coil Unit SQ D Square D FL Full Load (Amps)TA Victaulic Circuit Setter FR Frame GRUV Armstrong Gruvlock FT Feet FTR Fin Tube Radiation GPM Gallons per Minute Appendix i