Loading...
1245 Trapp Rd - Test & Balance Report 2016-12-06Tyler Zachman Date Tested December 6, 2016 Test and Balance Report Woodys Eagan MN Tested By Unit Number: Unit Manufacture: Unit Model: AREA Outlet Diffuser Neck DESIGN Actual Percent of SERVED Number TYPE SIZE CFM CFM Required Left Hood N/A 2250 2249 100% 2250 2249 100%Totals Captiveaire DU180HFA Woodys Eagan MN December 6, 2016 EF1 REMARKS: with on demand VFD Unit Number: Unit Manufacture: Unit Model: AREA Outlet Diffuser Neck DESIGN Actual Percent of SERVED Number TYPE SIZE CFM CFM Required Right Hood 2250 2248 100% Woodys Eagan MN December 6, 2016 EF2 Captiveaire DU180HF REMARKS: with on demand VFD Unit Number: Unit Manufacture: Unit Model: AREA Outlet Diffuser Neck DESIGN Actual Percent of SERVED Number TYPE SIZE CFM CFM Required Hood 1 integral 28/12 894 893 100% Hood 2 integral 28/12 894 894 100% Hood 3 integral 28/16 637 638 100% Hood 4 integral 28/16 637 638 100% Hood 5 integral 28/16 637 635 100% Hood 6 perforated 10 400 399 100% Hood 7 perforated 10 400 400 100% 4499 4497 100% Woodys Eagan MN December 6, 2016 MAU1 Captiveaire A2-D.500-G15 Totals REMARKS: VFD Unit Number: Unit Manufacture: Unit Model: AREA Outlet Diffuser Neck DESIGN Actual Percent of SERVED Number TYPE SIZE CFM CFM Required Break Room 1 Lay-in 10 425 420 99% Break Room 2 Lay-in 10 425 415 98% Production 1 Lay-in 10 425 410 96% Production 2 Lay-in 10 425 425 100% Production 3 Lay-in 10 425 430 101% Production 4 Lay-in 10 425 420 99% Production 5 Lay-in 10 425 415 98% Production 6 Lay-in 10 425 410 96% 3400 3345 98% Bryant 580JP09D180 Totals Woodys Eagan MN December 6, 2016 RTU1 REMARKS: OA set 10% 330 cfm