1245 Trapp Rd - Test & Balance Report 2016-12-06Tyler Zachman
Date Tested
December 6, 2016
Test and Balance Report
Woodys
Eagan MN
Tested By
Unit Number:
Unit Manufacture:
Unit Model:
AREA Outlet Diffuser Neck DESIGN Actual Percent of
SERVED Number TYPE SIZE CFM CFM Required
Left Hood N/A 2250 2249 100%
2250 2249 100%Totals
Captiveaire
DU180HFA
Woodys
Eagan MN
December 6, 2016
EF1
REMARKS: with on demand VFD
Unit Number:
Unit Manufacture:
Unit Model:
AREA Outlet Diffuser Neck DESIGN Actual Percent of
SERVED Number TYPE SIZE CFM CFM Required
Right Hood 2250 2248 100%
Woodys
Eagan MN
December 6, 2016
EF2
Captiveaire
DU180HF
REMARKS: with on demand VFD
Unit Number:
Unit Manufacture:
Unit Model:
AREA Outlet Diffuser Neck DESIGN Actual Percent of
SERVED Number TYPE SIZE CFM CFM Required
Hood 1 integral 28/12 894 893 100%
Hood 2 integral 28/12 894 894 100%
Hood 3 integral 28/16 637 638 100%
Hood 4 integral 28/16 637 638 100%
Hood 5 integral 28/16 637 635 100%
Hood 6 perforated 10 400 399 100%
Hood 7 perforated 10 400 400 100%
4499 4497 100%
Woodys
Eagan MN
December 6, 2016
MAU1
Captiveaire
A2-D.500-G15
Totals
REMARKS: VFD
Unit Number:
Unit Manufacture:
Unit Model:
AREA Outlet Diffuser Neck DESIGN Actual Percent of
SERVED Number TYPE SIZE CFM CFM Required
Break Room 1 Lay-in 10 425 420 99%
Break Room 2 Lay-in 10 425 415 98%
Production 1 Lay-in 10 425 410 96%
Production 2 Lay-in 10 425 425 100%
Production 3 Lay-in 10 425 430 101%
Production 4 Lay-in 10 425 420 99%
Production 5 Lay-in 10 425 415 98%
Production 6 Lay-in 10 425 410 96%
3400 3345 98%
Bryant
580JP09D180
Totals
Woodys
Eagan MN
December 6, 2016
RTU1
REMARKS: OA set 10% 330 cfm