3325 Central Park Village Dr - Orange Theory Fitness Balance Report 2017-03-30Even Osland Date Tested March 30, 2017 Test and Balance Report OTF Eagan Eagan, MN Tested By Unit RTU-1 RTU-2 RTU-3 Manufacture Bryant Bryant Bryant Model 581JP06 581JP06 581JP06 Total CFM 1,995 1,995 1,995 Fan RPM Motor RPM Motor Volts 230/3 230/3 230/3 Motor Amps Horsepower 1.6 1.6 1.6 O.A. Damper CFM 400 400 400 Unit Manufacture Model Total CFM Fan RPM Motor RPM Motor Volts Motor Amps Horsepower O.A. Damper CFM Air Handling Unit Test OTF Eagan Eagan, MN March 30, 2017 Unit Number: Unit Manufacture: Unit Model: AREA Outlet Diffuser Neck DESIGN Actual Percent of SERVED Number TYPE SIZE CFM CFM Required Studio 1 Lay-in 10" 325 316 97% Studio 2 Lay-in 10" 325 308 95% Studio 3 Lay-in 10" 325 318 98% Studio 4 Lay-in 10" 325 315 97% Studio 5 Lay-in 10" 325 320 98% Studio 6 Lay-in 10" 325 322 99% 1950 1899 97% Bryant 581JP06 Totals OTF Eagan Eagan, MN March 30, 2017 RTU-1 REMARKS: Unit Number: Unit Manufacture: Unit Model: AREA Outlet Diffuser Neck DESIGN Actual Percent of SERVED Number TYPE SIZE CFM CFM Required Studio 1 Lay-in 10"350 350 100% Studio 2 Lay-in 10"350 351 100% Studio 3 Lay-in 10"350 354 101% Studio 4 Lay-in 10"350 358 102% Studio 5 Lay-in 10"350 352 101% Shower 6 Register 6"100 105 105% Shower 7 Register 6"100 103 103% 1950 1973 101% Bryant 581JP06 Totals REMARKS: OTF Eagan Eagan, MN March 30, 2017 RTU-2 Unit Number: Unit Manufacture: Unit Model: AREA Outlet Diffuser Neck DESIGN Actual Percent of SERVED Number TYPE SIZE CFM CFM Required Retail 1 Lay-in 10" 350 355 101% Retail 2 Lay-in 10" 350 346 99% Retail 3 Lay-in 10" 350 348 99% Retail 4 Lay-in 10" 350 358 102% Retail 5 Lay-in 10" 350 352 101% Restroom 6 Register 6" 100 107 107% Restroom 7 Register 6" 100 104 104% 1950 1970 101%Totals Bryant 581JP06 OTF Eagan Eagan, MN March 30, 2017 RTU-3 REMARKS: