3325 Central Park Village Dr - Orange Theory Fitness Balance Report 2017-03-30Even Osland
Date Tested
March 30, 2017
Test and Balance Report
OTF Eagan
Eagan, MN
Tested By
Unit RTU-1 RTU-2 RTU-3
Manufacture Bryant Bryant Bryant
Model 581JP06 581JP06 581JP06
Total CFM 1,995 1,995 1,995
Fan RPM
Motor RPM
Motor Volts 230/3 230/3 230/3
Motor Amps
Horsepower 1.6 1.6 1.6
O.A. Damper CFM 400 400 400
Unit
Manufacture
Model
Total CFM
Fan RPM
Motor RPM
Motor Volts
Motor Amps
Horsepower
O.A. Damper CFM
Air Handling Unit Test
OTF Eagan
Eagan, MN
March 30, 2017
Unit Number:
Unit Manufacture:
Unit Model:
AREA Outlet Diffuser Neck DESIGN Actual Percent of
SERVED Number TYPE SIZE CFM CFM Required
Studio 1 Lay-in 10" 325 316 97%
Studio 2 Lay-in 10" 325 308 95%
Studio 3 Lay-in 10" 325 318 98%
Studio 4 Lay-in 10" 325 315 97%
Studio 5 Lay-in 10" 325 320 98%
Studio 6 Lay-in 10" 325 322 99%
1950 1899 97%
Bryant
581JP06
Totals
OTF Eagan
Eagan, MN
March 30, 2017
RTU-1
REMARKS:
Unit Number:
Unit Manufacture:
Unit Model:
AREA Outlet Diffuser Neck DESIGN Actual Percent of
SERVED Number TYPE SIZE CFM CFM Required
Studio 1 Lay-in 10"350 350 100%
Studio 2 Lay-in 10"350 351 100%
Studio 3 Lay-in 10"350 354 101%
Studio 4 Lay-in 10"350 358 102%
Studio 5 Lay-in 10"350 352 101%
Shower 6 Register 6"100 105 105%
Shower 7 Register 6"100 103 103%
1950 1973 101%
Bryant
581JP06
Totals
REMARKS:
OTF Eagan
Eagan, MN
March 30, 2017
RTU-2
Unit Number:
Unit Manufacture:
Unit Model:
AREA Outlet Diffuser Neck DESIGN Actual Percent of
SERVED Number TYPE SIZE CFM CFM Required
Retail 1 Lay-in 10" 350 355 101%
Retail 2 Lay-in 10" 350 346 99%
Retail 3 Lay-in 10" 350 348 99%
Retail 4 Lay-in 10" 350 358 102%
Retail 5 Lay-in 10" 350 352 101%
Restroom 6 Register 6" 100 107 107%
Restroom 7 Register 6" 100 104 104%
1950 1970 101%Totals
Bryant
581JP06
OTF Eagan
Eagan, MN
March 30, 2017
RTU-3
REMARKS: