3005 Eagandale Pl - Lemay Clubhouse Air Distribution Report 2017-07-17 ALL SYSTEMS MECHANICAL PAGE__1__ of __2__ 651-493-7364 AIR DISTRIBUTION TEST REPORT PROJECT:_Lemay Clubhouse - Eagan________SYSTEM:_East Furnace - Zoned___________ DATE:_7/17/17___________________________TECHNICIAN:_Tyler E.___________________ AREA SERVED OUTLET K DESIGN PRELIMINARY FINAL NO. SIZE TYPE Factor CFM VEL CFM VEL CFM VEL Lobby 1 12/6 Reg Hood 150 133 141 Manager Suite 1 10"RND Hood 260 222 248 Work Room 1 8"RND Hood 150 123 137 Property Manager 1 8"RND Hood 110 89 102 Lodge Room North 1 12/6 REG 0.29 165 188 178 Lodge Room North 2 12/6 REG 0.29 165 202 169 Lodge Room North 3 12/6 REG 0.29 165 189 173 Lodge Room South 1 12/6 REG 0.29 165 225 161 Lodge Room South 2 12/6 REG 0.29 165 211 168 Lodge Room South 3 12/6 REG 0.29 165 196 176 *Tested per Zone* TOTAL CFM 1660 1653 ALL SYSTEMS MECHANICAL PAGE__2__ of __2__ 651-493-7364 AIR DISTRIBUTION TEST REPORT PROJECT:_Lemay Clubhouse - Eagan________SYSTEM:_West Furnace - Zoned___________ DATE:_7/17/17___________________________TECHNICIAN:_Tyler E.___________________ AREA SERVED OUTLET K DESIGN PRELIMINARY FINAL NO. SIZE TYPE Factor CFM VEL CFM VEL CFM VEL Lobby 1 12/6 REG Hood 150 166 155 Marketing 1 8"RND Hood 175 189 181 Mens RR 1 6"RND Hood 75 92 77 Womens RR 1 6"RND Hood 75 88 72 Pet Wash 1 6"RND Hood 60 89 63 Fitness Center 1 12"RND Hood 450 511 483 Fitness Center 2 12"RND Hood 450 504 471 Corridor 1 8"RND Hood 100 189 125 *Tested per Zone* TOTAL CFM 1535 1627