3255 Neil Armstrong Blvd - Databank Test & Balance Reports 2017-11-15FIRM:
SMB of Minnesot a
4 255 Pheasant Ridge Drive NE
Suit e 4 01
Blaine MN 554 4 9
PHO NE:
(763) 398-3284
FA X:
(763) 398-3286
C UST O MER:
Schadegg Mechanical
PRO JEC T #:
1704 26
PRO JEC T A D DRESS:
3255 NEIL ARMST RONG BLVD.
EAGAN MN 55121
D AT E:
2017-11-13
C O NT ACT :
Craig Johnson
DAT A BANK MSP2 - PH3
3
3
5
7
T able of C ont e nt s
INDIRECT EVAP CO O LERS
ID EC -13
ID EC -14
ID EC -17
PR O JEC T N U MB ER :
170 4 26
C O N T AC T :
Cra ig Jo hnso n
LO CAT IO N :
DATABANK MSP2 - PH3
3255 NEIL ARMSTRONG BLVD.
EAGAN MN 55121
Pa g e 2 o f 8 20 17-11-13
D e s ig n Ac t ua l %D e s ig n Ac t ua l %
Supply Fan
INDIRECT EVAP COOLERS
IDEC-13
SU PPLY FAN
U NIT MFG MUNTERS ACT UAL AMPS 25 .8
U NIT MO D EL NO PV-W25 -5 0-PVT+MAU MO T O R PHASE 3
U NIT SER IAL NO -B HP 19 .9 6
T O T AL CFM 4 8 6 80 4 4 90 6 9 2 MO T O R NO M EFF %9 3.0 0
MIN O A CFM 70 0 750 10 7 MO T O R PO WER FACT O R %78 .0 0
T O T AL SP IN WC -3.0 70 MO T O R FRAME 326
EXT SP IN WC 1.75 0 FAN RPM 10 20
MO T O R MFG BALDO R MO T O R SHEAVE X BO R E D IRECT DRIVE
MO T O R HP (2)30 .0 (2)30 .0 FAN SH EAVE X B O R E D IRECT DRIVE
MO T O R RPM 10 20 D RIVE BELT S D IRECT DRIVE
N AMEPLAT E VO LT S 460 C EN T ER T O CENT ER IN D IRECT DRIVE
ACT UAL VO LT S 460 LO C AT IO N RO O F
N AMEPLAT E FLA 39 .0
IMAGES:
PR O JEC T N U MB ER :
170 4 26
C O N T AC T :
Cra ig Jo hnso n
LO CAT IO N :
DATABANK MSP2 - PH3
3255 NEIL ARMSTRONG BLVD.
EAGAN MN 55121
ID EC -13 Pa g e 3 o f 8 20 17-11-13
NOTES:
Supply Fan
T OT AL CFM
TO TAL SUPPLY AIR DETERMINED BY VELGRID . VFD AT 5 1.8 HERTZ
ACT UAL A MPS
AMPS READ AT VFD AT 5 1.8 HERTZ
IDEC-13 / Sum m ary
SU MMAR Y
N a me T O T AL FPM AVG FPM SIZ E D U CT AREA C FM LO CAT IO N
D UC T TRAVERSE 3169 5 5 8 7 136 X8 1 76 .5 0 44 9 0 6 RO O F
T o t a ls 4 4 9 0 6
PR O JEC T N U MB ER :
170 4 26
C O N T AC T :
Cra ig Jo hnso n
LO CAT IO N :
DATABANK MSP2 - PH3
3255 NEIL ARMSTRONG BLVD.
EAGAN MN 55121
ID EC -13 Pa g e 4 o f 8 20 17-11-13
D e s ig n Ac t ua l %D e s ig n Ac t ua l %
Supply Fan
IDEC-14
SU PPLY FAN
U NIT MFG MUNTERS ACT UAL AMPS 26 .0
U NIT MO D EL NO PV-W25 -5 0 -PVT MO T O R PHASE 3
U NIT SER IAL NO -B HP 20 .12
T O T AL CFM 4 8 6 80 47124 9 7 MO T O R NO M EFF %9 3.0 0
MIN O A CFM 0 0 MO T O R PO WER FACT O R %78 .0 0
T O T AL SP IN WC -2.9 10 MO T O R FRAME 326
EXT SP IN WC 1.6 10 FAN RPM 10 35
MO T O R MFG BALDO R MO T O R SHEAVE X BO R E D IRECT DRIVE
MO T O R HP (2)30 .0 (2)30 .0 FAN SH EAVE X B O R E D IRECT DRIVE
MO T O R RPM 10 35 D RIVE BELT S D IRECT DRIVE
N AMEPLAT E VO LT S 460 C EN T ER T O CENT ER IN D IRECT DRIVE
ACT UAL VO LT S 460 LO C AT IO N RO O F
N AMEPLAT E FLA 39 .0
IMAGES:
PR O JEC T N U MB ER :
170 4 26
C O N T AC T :
Cra ig Jo hnso n
LO CAT IO N :
DATABANK MSP2 - PH3
3255 NEIL ARMSTRONG BLVD.
EAGAN MN 55121
ID EC -14 Pa g e 5 o f 8 20 17-11-13
NOTES:
Supply Fan
T OT AL CFM
TO TAL SUPPLY AIR DETERMINED BY VELGRID . VFD AT 5 2.8 HERTZ
NAMEPLAT E FLA
THERE ARE 2 FANS AND 2 VFD S. EAC H FAN FLA=39 .0
ACT UAL A MPS
O NE VFD READ 26 .0 AMPS AND THE O THER READ 25.8 AMPS.
IDEC-14 / Sum m ary
SU MMAR Y
N a me T O T AL FPM AVG FPM SIZ E D U CT AREA C FM LO CAT IO N
D UC T TRAVERSE 33264 6 16 136 X8 1 76 .5 0 4 7124 RO O F
T o t a ls 4 7 1 2 4
PR O JEC T N U MB ER :
170 4 26
C O N T AC T :
Cra ig Jo hnso n
LO CAT IO N :
DATABANK MSP2 - PH3
3255 NEIL ARMSTRONG BLVD.
EAGAN MN 55121
ID EC -14 Pa g e 6 o f 8 20 17-11-13
D e s ig n Ac t ua l %D e s ig n Ac t ua l %
Supply Fan
IDEC-17
SU PPLY FAN
U NIT MFG MUNTERS ACT UAL AMPS 26 .6
U NIT MO D EL NO PV-W25 -5 0-PVT+MAU MO T O R PHASE 3
U NIT SER IAL NO -B HP 20 .5 8
T O T AL CFM 4 8 6 80 4 674 2 9 6 MO T O R NO M EFF %9 3.0 0
MIN O A CFM 70 0 730 10 4 MO T O R PO WER FACT O R %78 .0 0
T O T AL SP IN WC -2.76 0 MO T O R FRAME 326
EXT SP IN WC 1.30 0 FAN RPM 10 4 5
MO T O R MFG BALDO R MO T O R SHEAVE X BO R E D IRECT DRIVE
MO T O R HP (2)30 .0 (2)30 .0 FAN SH EAVE X B O R E D IRECT DRIVE
MO T O R RPM 10 4 5 D RIVE BELT S D IRECT DRIVE
N AMEPLAT E VO LT S 460 C EN T ER T O CENT ER IN D IRECT DRIVE
ACT UAL VO LT S 460 LO C AT IO N RO O F
N AMEPLAT E FLA 39 .0
IMAGES:
PR O JEC T N U MB ER :
170 4 26
C O N T AC T :
Cra ig Jo hnso n
LO CAT IO N :
DATABANK MSP2 - PH3
3255 NEIL ARMSTRONG BLVD.
EAGAN MN 55121
ID EC -17 Pa g e 7 o f 8 20 17-11-13
NOTES:
Supply Fan
T OT AL CFM
TO TAL SUPPLY AIR DETERMINED BY VELGRID . VFD AT 5 3 HERTZ
NAMEPLAT E FLA
THERE ARE 2 FANS AND 2 VFD S. EAC H FAN FLA=39 .0
ACT UAL A MPS
O NE VFD READ 26 .6 AMPS AND THE O THER 26 .1 AMPS.
IDEC-17 / Sum m ary
SU MMAR Y
N a me T O T AL FPM AVG FPM SIZ E D U CT AREA C FM LO CAT IO N
D UC T TRAVERSE 3300 1 6 11 136 X8 1 76 .5 0 4 6 74 2 RO O F
T o t a ls 4 6 7 4 2
PR O JEC T N U MB ER :
170 4 26
C O N T AC T :
Cra ig Jo hnso n
LO CAT IO N :
DATABANK MSP2 - PH3
3255 NEIL ARMSTRONG BLVD.
EAGAN MN 55121
ID EC -17 Pa g e 8 o f 8 20 17-11-13
Mark A. Cotroneo
SMB of Minnesota
MVJMQJPS=
Actual Field Measured Value RA Return Air
BAS Building Automation System RPM Revolutions Per Minute
BHP Brake Horsepower SA Supply Air (CFM)
CFM Cubic Feet per Minute SF Square Feet
DCFM Design CFM SOH Shut Off Head (feet of water)
DDC Direct Digital Control SP Static Pressure (inches wc)
Des Design Value TDH Total Dynamic Head (feet of water)
Design Based on Plans / Specifications TSP Total Static Pressure (inches wc)
DP Differential Pressure (feet of water) Vel Velocity (FPM)
DVel Design Velocity (FPM) wc water column (inches)
EA Exhaust Air (CFM)
ESP External Static Pressure (inches wc)
FLA Full Load Amps CD Ceiling Diffuser
FMD Flow Measuring Device EG Exhaust Grill
FPM Feet Per Minute ER Exhaust Register
GPM Gallons Per Minute FD Floor Diffuser
HP Horsepower LC Light Can
Max Maximum LD Linear Diffuser (Slot)
Min Minimum LT Light Troffer
Nom NomInal RD Round Diffuser
OA Outside Air (CFM) RG Return Grill
OED Open End Duct RR Return Register
PD Pressure Drop SG Supply Grille
Pre FPM Preliminary FPM SR Supply Register
Prelim. Preliminary
Grilles, Registers, and Diffusers
ABBREVIATIONS