2930 Lone Oak Dr - White House Custom Colour Test & Balance Report 2018-04-06 Technician: Cell Phone: Email Address: Associated Mechanical Contractors, Inc. 1257 Marschall Road PO Box 237 Report Date April 6, 2018 Shakopee MN 55379 375 230th Ave, Somerset WI 54025 - Phone: (612) 834-0311 Fax: (414) 377-3349 www.Premierbalancing.com Testing, Adjusting & Balancing Report TABB TECHNICIAN CLIENT Associated Mechanical Contractors, Inc. 1257 Marschall Road PO Box 237 ENGINEER White House -Custom Colour Eagan, MN 55121 Jaime Sevre 763-639-2177 jaime@premierbalancing.com PROJECT 2930 Lone Oak Drive Shakopee MN 55379 TABB CERTIFICATION TABB certification of a Supervisor is TABB's statement that the Supervisor is able to supervise testing, adjusting and balancing of building environmental systems to produce the design objectives or optimum system performance. For TABB Certification purposes, a Supervisor is the person who, while employed by a TABB Certified Contractor, is responsible and accountable for overseeing, coordinating and ensuring that projects are performed by TABB Certified Technicians in accordance with TABB standards (including the ICB Code of Conduct and the TAB General Rules). Measurements recorded in this report are in accordance with the SMACNA / TABB HVAC Systems, Testing, Adjusting and Balancing manual. TABB Certified "The Professional's Choice" Page 2 TABB QUALITY ASSURANCE PROGRAM BACKGROUND TABB seeks to ensure the integrity of its certification program by: (a) setting eligibility criteria for TABB Certified Supervisors and TABB Certified Contractors, (b) establishing testing procedures for TABB Certified Supervisors, (c) requiring continuing education and continuous compliance with eligibility criteria for renewal of certification, and (d) periodically reviewing its recognition of technician certification. High quality work on the part of TABB Certified Technicians and TABB Certified Supervisors and TABB Certified Contractors ( TABB Professionals ) is essential to integrity of the TABB Certification Program. TABB offers this TABB Quality Assurance Program to help assure high quality work. By accepting TABB qualification or certification, every TABB Professional accepts the responsibilities or this Program. Quality Assurance Every customer of a TABB Certified Contractor shall be entitled to expect: (1) that testing, adjusting and balancing work by the contractor and its TABB Professionals will meet TABB standards; (2) that testing, adjusting and balancing reports provided to the customer will have been prepared by a TABB Certified Technician, and reviewed by a TABB Certified Supervisor; and (3) that the report(s) will include measurements taken accurately with the date and mode of operation of the systems. TABB 8403 Arlington Boulevard Fairfax, VA 22031 Phone - (703) 299-5646 Fax - (703) 683-7615 TABB Certified "The Professional's Choice" Page 3 INSTRUMENT CALIBRATION REPORT Rotating Measuring Instrument Temperature Measuring Instrument Temperature Measuring Probe Electrical Measuring Instruments Air Pressure Measuring Instrument Air Velocity Measuring Instrument Hydronic Pressure Measuring Instrument 0 to 300 psi Temperature Measuring Instrument Temperature Measuring Probe HM70 Vaisala M4820017 12/08/17 HMP75 Vaisala M5040569 12/08/17 HM-675 Alnor 71725052 11/07/17 ADM-870C Shortridge M11441 12/19/17 ADM-870C Shortridge M11441 12/19/17 117 Fluke 18561871 12/19/17 322 Fluke 17830473 12/19/17 INSTRUMENT MODEL MANUFACTURER SERIAL NUMBER CALIBRATION DATE PLT-5000 Mitchell Instruments B15985012P 12/19/17 HM70 Vaisala M4820017 12/08/17 HMP75 Vaisala M5040569 12/08/17 TABB Certified "The Professional's Choice" Page 4 Index Project:White House -Custom Colour Premier Job Number: Jaime Sevre Report Date: Page 6 RTU-1 Constant Air Volume 7 RTU-2 Constant Air Volume 8-9 RTU-3 Constant Air Volume 10-11 RTU-4 Constant Air Volume 12 RTU-5 Constant Air Volume 13 RTU-6 Constant Air Volume 14 RTU-7 Constant Air Volume 15-16 RTU-8 Constant Air Volume 17 RTU-9 Constant Air Volume 18-19 RTU-10 Constant Air Volume 20 RTU-11 Constant Air Volume 21 RTU-12 Constant Air Volume 22 RTU-13 Constant Air Volume 23 RTU-14 Constant Air Volume 24 RTU-15 Constant Air Volume 25 MUA-1 Constant Air Volume 26 EF-1 Constant Air Volume 27 EF-2A Constant Air Volume 28 EF-2B Constant Air Volume 4/4/18 4/4/18 4/3/18 4/4/18 4/3/18 4/4/18 4/4/18 4/4/18 4/5/18 4/3/18 4/3/18 4/3/18 4/5/18 4/3/18 4/3/18 2050 Technician:4/6/18 System / Equipment Completion Date 4/5/18 4/4/18 4/3/18 Description 4/4/18 Premier Test & Balance TABB Certified "The Professional's Choice" Page 5 Air Handling Unit Test Data Project:White House -Custom Colour System:RTU-1 Premier Job Number: Jaime Sevre Completion Date: Equipment Location: Motor HP:1.25 1.25 Motor RPM:1670 1670 Motor Hertz:60.0 60.0 Motor Service Factor:1.15 1.15 Motor Phase:3 3 Motor Voltage:460 460 460 460 Motor Amperage:4.9 4.3 4.3 4.3 Motor BHP:1.36 1.10 Fan RPM:601 628 Fan: Supply Air Opening Size K No.Factor Velocity CFM Velocity CFM %Velocity CFM 1 34x28 6.61 605 4000 656 4337 108%679 4489 Total 4000 4337 108%4489 Minimum Outside Air Size K Factor Velocity CFM Velocity CFM %Velocity CFM 45x25 7.81 26 200 28 219 109%56 438 Remarks:a)Traverse taken in a turbulent area. b) c) d) e) Preliminary Reading Rise / Drop Total (inches) Rise 0.35 Preliminary Reading 2050 Premier Test & Balance 4,000 Min.Outside Air CFM: 200 4/4/18 System Scheduled Data Model number: 48LCE012A2A6-0R0A0 Serial number: 1017P11605 Manufacturer:Carrier Outlet Total CFM: 4,000 Technician: Fan Static Pressure:0.5 ESP / 0.52 TSP Roof Performance Data Description Scheduled / Submittal Data Actual Field Measurements Total Design CFM: Component Static Pressure (inches of water) In Out Pressure Pressure Static Pressure Data -0.12 0.23 Airflow Measurements Area Design Final Reading Served Traverse Design Final Reading Total TABB Certified "The Professional's Choice" Page 6 Air Handling Unit Test Data Project:White House -Custom Colour System:RTU-2 Premier Job Number: Jaime Sevre Completion Date: Equipment Location: Motor HP:-- Motor RPM:1670 1670 Motor Hertz:60.0 60.0 Motor Service Factor:1.15 1.15 Motor Phase:3 3 Motor Voltage:460 460 460 460 Motor Amperage:2.9 1.6 1.6 1.6 Motor BHP:1.25 - Fan RPM:828 798 Fan: Supply Air Opening Size K No.Factor Velocity CFM Velocity CFM %Velocity CFM 1 18x18 2.25 1067 2400 1049 2360 98%986 2219 Total 2400 2360 98%2219 Minimum Outside Air Size K Factor Velocity CFM Velocity CFM %Velocity CFM 35x19 4.62 43 200 42 194 97%67 309 Remarks:a)Traverse taken in a turbulent area. b) c) d) e) Premier Test & Balance 2050 Technician:4/3/18 System Scheduled Data Model number: 48LCE007A2A6-0R0A0 Serial number: 4217P83590 Manufacturer:Carrier Outlet Total CFM: 2,400 Total Design CFM:2,400 Min.Outside Air CFM: 200 Fan Static Pressure:1.0 ESP / 1.09 TSP Roof Performance Data Description Scheduled / Submittal Data Actual Field Measurements Static Pressure Data Component Static Pressure (inches of water)Pressure Pressure In Out Rise / Drop Total (inches) -0.16 0.49 Rise 0.65 Airflow Measurements Area Design Final Reading Preliminary Reading Served Traverse Design Final Reading Preliminary Reading Total TABB Certified "The Professional's Choice" Page 7 Air Handling Unit Test Data Project:White House -Custom Colour System:RTU-3 Premier Job Number: Jaime Sevre Completion Date: Equipment Location: Motor RPM:1670 1670 Motor Hertz:60.0 60.0 Motor Service Factor:1.15 1.15 Motor Phase:3 3 Motor Voltage:460 460 460 460 Motor Amperage:3.4 3.1 3.1 3.1 Fan RPM:724 743 Fan: Supply Air Opening Size K No.Factor Velocity CFM Velocity CFM %Velocity CFM 1 24x16 2.67 759 2025 792 2112 104%683 1821 Total 2025 2112 104%1821 Minimum Outside Air Size K Factor Velocity CFM Velocity CFM %Velocity CFM 45x25 7.81 77 600 78 609 102%98 766 Remarks:a)Traverse taken in a turbulent area. b) c) d) e) Premier Test & Balance 2050 Technician:4/3/18 System Scheduled Data Model number: 48LCE008A2A6-0R0A0 Serial number: 4117P01757 Manufacturer:Carrier Outlet Total CFM: 2,025 Total Design CFM:3,000 Min.Outside Air CFM: 600 Fan Static Pressure:1.0 ESP / 1.01 TSP Roof Performance Data Description Scheduled / Submittal Data Actual Field Measurements Static Pressure Data Component Static Pressure (inches of water)Pressure Pressure In Out Rise / Drop Total (inches) -0.37 0.48 Rise 0.85 Airflow Measurements Area Design Final Reading Preliminary Reading Served Traverse Design Final Reading Preliminary Reading Total TABB Certified "The Professional's Choice" Page 8 Air Outlet Test Report Project:White House -Custom Colour System:RTU-3 (Supply)Premier Job Number: Jaime Sevre Completion Date: Opening Size K No.Factor Velocity CFM Velocity CFM %Velocity CFM 1 Flow Hood 1.00 75 75 76 76 101%76 76 2 Flow Hood 1.00 75 75 77 77 103%78 78 3 Flow Hood 1.00 100 100 98 98 98%72 72 4 Flow Hood 1.00 175 175 178 178 102%134 134 5 Flow Hood 1.00 175 175 188 188 107%141 141 6 Flow Hood 1.00 100 100 105 105 105%108 108 7 Flow Hood 1.00 100 100 106 106 106%48 48 8 Flow Hood 1.00 100 100 98 98 98%85 85 9 Flow Hood 1.00 100 100 106 106 106%105 105 10 Flow Hood 1.00 75 75 78 78 104%72 72 11 Flow Hood 1.00 150 150 158 158 105%168 168 12 Flow Hood 1.00 200 200 189 189 95%145 145 13 Flow Hood 1.00 200 200 196 196 98%170 170 14 Flow Hood 1.00 200 200 200 200 100%174 174 15 Flow Hood 1.00 200 200 210 210 105%182 182 Total 2025 2063 102%1758 Remarks:a) b) c) d) e) Premier Test & Balance 2050 Technician:4/3/18 Airflow Measurements Area Design Final Reading Preliminary Reading Served 2nd Floor Offices 2nd Floor Offices 2nd Floor Offices 2nd Floor Offices 2nd Floor Offices Womens Bathroom Hallway Hallway Mens Bathroom 2nd Floor Offices 2nd Floor Offices 2nd Floor Offices 2nd Floor Offices 2nd Floor Offices 2nd Floor Offices TABB Certified "The Professional's Choice" Page 9 Air Handling Unit Test Data Project:White House -Custom Colour System:RTU-4 Premier Job Number: Jaime Sevre Completion Date: Equipment Location: Motor RPM:1670 1670 Motor Hertz:60.0 60.0 Motor Service Factor:1.15 1.15 Motor Phase:3 3 Motor Voltage:460 460 460 460 Motor Amperage:6.4 5.7 5.7 5.7 Fan RPM:836 848 Fan: Supply Air Opening Size K No.Factor Velocity CFM Velocity CFM %Velocity CFM 1 63x27 11.81 423 5000 431 5091 102%436 5150 Total 5000 5091 102%5150 Minimum Outside Air Size K Factor Velocity CFM Velocity CFM %Velocity CFM 59x23 9.42 60 565 62 584 103%78 735 Remarks:a)Traverse taken in a turbulent area. b) c) d) e) Premier Test & Balance 2050 Technician:4/5/18 System Scheduled Data Model number: 48LCE014A2A6-0R0A0 Serial number: 1217P24100 Manufacturer:Carrier Outlet Total CFM: 5,000 Total Design CFM:5,000 Min.Outside Air CFM: 565 Fan Static Pressure:1.0 ESP / 1.05 TSP Roof Performance Data Description Scheduled / Submittal Data Actual Field Measurements Static Pressure Data Component Static Pressure (inches of water)Pressure Pressure In Out Rise / Drop Total (inches) -0.36 0.52 Rise 0.88 Airflow Measurements Area Design Final Reading Preliminary Reading Served Traverse Design Final Reading Preliminary Reading Total TABB Certified "The Professional's Choice" Page 10 Air Outlet Test Report Project:White House -Custom Colour System:RTU-4 (Supply)Premier Job Number: Jaime Sevre Completion Date: Opening Size K No.Factor Velocity CFM Velocity CFM %Velocity CFM 1 Flow Hood 1.00 50 50 52 52 104%119 119 2 Flow Hood 1.00 100 100 102 102 102%119 119 3 Flow Hood 1.00 350 350 350 350 100%334 334 4 Flow Hood 1.00 50 50 52 52 104%132 132 5 Flow Hood 1.00 115 115 118 118 103%256 256 6 Flow Hood 1.00 50 50 53 53 106%124 124 7 Flow Hood 1.00 150 150 148 148 99%265 265 8 Flow Hood 1.00 100 100 103 103 103%99 99 9 Flow Hood 1.00 175 175 176 176 101%214 214 10 Flow Hood 1.00 175 175 171 171 98%187 187 11 Flow Hood 1.00 100 100 102 102 102%118 118 12 24X18 3.00 1195 3585 1184 3552 99%1022 3066 Total 5000 4979 100%5033 Remarks:a) b) c) d) e) Premier Test & Balance 2050 Technician:4/5/18 Airflow Measurements Area Design Final Reading Preliminary Reading Served 1st Floor Offices 1st Floor Offices 1st Floor Offices 1st Floor Offices 1st Floor Offices 1st Floor Offices 1st Floor Offices Mens Bathroom Hallway Hallway Womens Bathroom 1st Floor Open area TABB Certified "The Professional's Choice" Page 11 Air Handling Unit Test Data Project:White House -Custom Colour System:RTU-5 Premier Job Number: Jaime Sevre Completion Date: Equipment Location: Motor HP:5.00 5.00 Motor RPM:1755 1755 Motor Hertz:60.0 60.0 Motor Service Factor:1.15 1.15 Motor Phase:3 3 Motor Voltage:460 460 460 460 Motor Amperage:9.7 5.2 5.2 5.2 Motor BHP:3.04 2.68 Fan RPM:904 778 Fan: Supply Air Opening Size K No.Factor Velocity CFM Velocity CFM %Velocity CFM 1 63x27 11.81 508 6000 549 6485 108%621 7336 Total 6000 6485 108%7336 Minimum Outside Air Size K Factor Velocity CFM Velocity CFM %Velocity CFM 59x23 9.42 58 550 63 594 108%83 782 Remarks:a)Traverse taken in a turbulent area. b) c) d) e) Premier Test & Balance 2050 Technician:4/4/18 System Scheduled Data Model number: 48LCE017A2A6-0R0A0 Serial number: 4217P16693 Manufacturer:Carrier Outlet Total CFM: 6,000 Total Design CFM:6,000 Min.Outside Air CFM: 550 Fan Static Pressure:1.0 ESP / 1.06 TSP Roof Performance Data Description Scheduled / Submittal Data Actual Field Measurements Static Pressure Data Component Static Pressure (inches of water)Pressure Pressure In Out Rise / Drop Total (inches) -0.17 0.52 Rise 0.69 Airflow Measurements Area Design Final Reading Preliminary Reading Served Traverse Design Final Reading Preliminary Reading Total TABB Certified "The Professional's Choice" Page 12 Air Handling Unit Test Data Project:White House -Custom Colour System:RTU-6 Premier Job Number: Jaime Sevre Completion Date: Equipment Location: Motor RPM:1670 1670 Motor Hertz:60.0 60.0 Motor Service Factor:1.15 1.15 Motor Phase:3 3 Motor Voltage:460 460 460 460 Motor Amperage:6.4 5.4 5.4 5.4 Fan RPM:836 823 Fan: Supply Air Opening Size K No.Factor Velocity CFM Velocity CFM %Velocity CFM 1 18"1.77 941 1666 887 1570 94%828 1466 2 22"2.64 1262 3332 1212 3200 96%1266 3342 Total 4998 4770 95%4808 Minimum Outside Air Size K Factor Velocity CFM Velocity CFM %Velocity CFM 59x23 9.42 58 550 61 575 105%76 716 Remarks:a)Traverse taken in a turbulent area. b) c) d) e) Premier Test & Balance 2050 Technician:4/3/18 System Scheduled Data Model number: 48LCE014A2A6-0R0A0 Serial number: 1217P24094 Manufacturer:Carrier Outlet Total CFM: 4,998 Total Design CFM:5,000 Min.Outside Air CFM: 550 Fan Static Pressure:1.0 ESP / 1.05 TSP Roof Performance Data Description Scheduled / Submittal Data Actual Field Measurements Static Pressure Data Component Static Pressure (inches of water)Pressure Pressure In Out Rise / Drop Total (inches) -0.18 0.57 Rise 0.75 Airflow Measurements Area Design Final Reading Preliminary Reading Served Traverse Traverse Design Final Reading Preliminary Reading Total TABB Certified "The Professional's Choice" Page 13 Air Handling Unit Test Data Project:White House -Custom Colour System:RTU-7 Premier Job Number: Jaime Sevre Completion Date: Equipment Location: Motor RPM:1670 1670 Motor Hertz:60.0 60.0 Motor Service Factor:1.15 1.15 Motor Phase:3 3 Motor Voltage:460 460 460 460 Motor Amperage:4.9 3.2 3.2 3.2 Fan RPM:601 580 Fan: Supply Air Opening Size K No.Factor Velocity CFM Velocity CFM %Velocity CFM 1 34x28 6.61 605 4000 656 4337 108%778 5143 Total 4000 4337 108%5143 Minimum Outside Air Size K Factor Velocity CFM Velocity CFM %Velocity CFM 45x25 7.81 70 550 73 570 104%84 656 Remarks:a)Traverse taken in a turbulent area. b) c) d) e) Technician:4/5/18 System Scheduled Data Premier Test & Balance 2050 Model number: 48LCE012A2A6-0R0A0 Serial number: 1017P11606 Outlet Total CFM: 4,000 Roof Performance Data Description Scheduled / Submittal Data Actual Field Measurements Total Design CFM:4,000 Min.Outside Air CFM: 550 Fan Static Pressure:0.5 ESP / 0.52 TSP Manufacturer:Carrier Static Pressure Data Component Static Pressure (inches of water)Pressure Pressure In Out Rise / Drop Total (inches) -0.15 0.55 Rise 0.70 Airflow Measurements Design Final Reading Preliminary Reading Design Final Reading Preliminary Reading Total Area Served Traverse TABB Certified "The Professional's Choice" Page 14 Air Handling Unit Test Data Project:White House -Custom Colour System:RTU-8 Premier Job Number: Jaime Sevre Completion Date: Equipment Location: Motor RPM:1670 1670 Motor Hertz:60.0 60.0 Motor Service Factor:1.15 1.15 Motor Phase:3 3 Motor Voltage:460 460 460 460 Motor Amperage:4.9 3.6 3.6 3.6 Fan RPM:601 574 Fan: Supply Air Opening Size K No.Factor Velocity CFM Velocity CFM %Velocity CFM 1 22x22 3.36 1190 4000 1289 4332 108%1434 4820 Total 4000 4332 108%4820 Minimum Outside Air Size K Factor Velocity CFM Velocity CFM %Velocity CFM 45x25 7.81 26 200 25 195 98%39 305 Remarks:a)Traverse taken in a turbulent area. b) c) d) e) Premier Test & Balance 2050 Technician:4/3/18 System Scheduled Data Model number: 48LCE012A2A6-0R0A0 Serial number: 1017P11604 Manufacturer:Carrier Outlet Total CFM: 4,000 Total Design CFM:4,000 Min.Outside Air CFM: 200 Fan Static Pressure:0.5 ESP / 0.52 TSP Roof Performance Data Description Scheduled / Submittal Data Actual Field Measurements Static Pressure Data Component Static Pressure (inches of water)Pressure Pressure In Out Rise / Drop Total (inches) -0.16 0.51 Rise 0.67 Airflow Measurements Area Design Final Reading Preliminary Reading Served Traverse Design Final Reading Preliminary Reading Total TABB Certified "The Professional's Choice" Page 15 Air Outlet Test Report Project:White House -Custom Colour System:RTU-8 (Supply)Premier Job Number: Jaime Sevre Completion Date: Opening Size K No.Factor Velocity CFM Velocity CFM %Velocity CFM 1 28x11 2.14 468 1000 493 1054 105%545 1166 2 28x11 2.14 468 1000 489 1046 105%563 1204 3 28x11 2.14 468 1000 491 1050 105%571 1221 4 28x11 2.14 468 1000 500 1069 107%552 1181 Total 4000 4220 106%4772 Remarks:a) b) c) d) e) Premier Test & Balance 2050 Technician:4/3/18 Airflow Measurements Area Design Final Reading Preliminary Reading Served 1st Floor Area A 1st Floor Area A 1st Floor Area A 1st Floor Area A TABB Certified "The Professional's Choice" Page 16 Air Handling Unit Test Data Project:White House -Custom Colour System:RTU-9 Premier Job Number: Jaime Sevre Completion Date: Equipment Location: Motor RPM:1670 1670 Motor Hertz:60.0 60.0 Motor Service Factor:1.15 1.15 Motor Phase:3 3 Motor Voltage:460 460 460 460 Motor Amperage:2.9 1.7 1.7 1.7 Fan RPM:828 798 Fan: Supply Air Opening Size K No.Factor Velocity CFM Velocity CFM %Velocity CFM 1 18x18 2.25 1151 2590 1115 2509 97%1115 2509 Total 2590 2509 97%2509 Minimum Outside Air Size K Factor Velocity CFM Velocity CFM %Velocity CFM 35x19 4.62 65 300 68 314 105%82 379 Remarks:a)Traverse taken in a turbulent area. b) c) d) e) Premier Test & Balance 2050 Technician:4/3/18 System Scheduled Data Model number: 48LCE007A2A6-0R0A0 Serial number: 4217P83589 Manufacturer:Carrier Outlet Total CFM: 2,590 Total Design CFM:2,400 Min.Outside Air CFM: 300 Fan Static Pressure:1.0 ESP / 1.09 TSP Roof Performance Data Description Scheduled / Submittal Data Actual Field Measurements Static Pressure Data Component Static Pressure (inches of water)Pressure Pressure In Out Rise / Drop Total (inches) -0.21 0.67 Rise 0.88 Airflow Measurements Area Design Final Reading Preliminary Reading Served Traverse Design Final Reading Preliminary Reading Total TABB Certified "The Professional's Choice" Page 17 Air Handling Unit Test Data Project:White House -Custom Colour System:RTU-10 Premier Job Number: Jaime Sevre Completion Date: Equipment Location: Motor RPM:1670 1670 Motor Hertz:60.0 60.0 Motor Service Factor:1.15 1.15 Motor Phase:3 3 Motor Voltage:460 460 460 460 Motor Amperage:4.9 3.8 3.8 3.8 Fan RPM:601 654 Fan: Supply Air Opening Size K No.Factor Velocity CFM Velocity CFM %Velocity CFM 1 22x22 3.36 1190 4000 1266 4255 106%1266 4255 Total 4000 4255 106%4255 Minimum Outside Air Size K Factor Velocity CFM Velocity CFM %Velocity CFM 45x25 7.81 26 200 27 211 105%44 344 Remarks:a)Traverse taken in a turbulent area. b) c) d) e) Premier Test & Balance 2050 Technician:4/3/18 System Scheduled Data Model number: 48LCE012A2A6-0R0A0 Serial number: 1317P11974 Manufacturer:Carrier Outlet Total CFM: 4,000 Total Design CFM:4,000 Min.Outside Air CFM: 200 Fan Static Pressure:0.5 ESP / 0.52 TSP Roof Performance Data Description Scheduled / Submittal Data Actual Field Measurements Static Pressure Data Component Static Pressure (inches of water)Pressure Pressure In Out Rise / Drop Total (inches) -0.18 0.63 Rise 0.81 Airflow Measurements Area Design Final Reading Preliminary Reading Served Traverse Design Final Reading Preliminary Reading Total TABB Certified "The Professional's Choice" Page 18 Air Outlet Test Report Project:White House -Custom Colour System:RTU-10 (Supply)Premier Job Number: Jaime Sevre Completion Date: Opening Size K No.Factor Velocity CFM Velocity CFM %Velocity CFM 1 28x11 2.14 468 1000 478 1022 102%478 1022 2 28x11 2.14 468 1000 483 1033 103%483 1033 3 28x11 2.14 468 1000 489 1046 105%489 1046 4 28x11 2.14 468 1000 501 1072 107%501 1072 Total 4000 4173 104%4173 Remarks:a) b) c) d) e) Area Design Final Reading Preliminary Reading Served 1st Floor Area A 1st Floor Area A 1st Floor Area A 1st Floor Area A Premier Test & Balance 2050 Technician:4/3/18 Airflow Measurements TABB Certified "The Professional's Choice" Page 19 Air Handling Unit Test Data Project:White House -Custom Colour System:RTU-11 Premier Job Number: Jaime Sevre Completion Date: Equipment Location: Motor HP:5.00 5.00 Motor RPM:1755 1755 Motor Hertz:60.0 60.0 Motor Service Factor:1.15 1.15 Motor Phase:3 3 Motor Voltage:460 460 460 460 Motor Amperage:9.7 4.6 4.6 4.6 Motor BHP:3.04 2.37 Fan RPM:904 788 Fan: Supply Air Opening Size K No.Factor Velocity CFM Velocity CFM %Velocity CFM 1 63x27 11.81 508 6000 534 6308 105%564 6662 Total 6000 6308 105%6662 Minimum Outside Air Size K Factor Velocity CFM Velocity CFM %Velocity CFM 59x23 9.42 58 550 57 537 98%71 669 Remarks:a)Traverse taken in a turbulent area. b) c) d) e) Premier Test & Balance 2050 Technician:4/5/18 System Scheduled Data Model number: 48LCE017A2A6-0R0A0 Serial number: 4217P16694 Manufacturer:Carrier Outlet Total CFM: 6,000 Total Design CFM:6,000 Min.Outside Air CFM: 550 Fan Static Pressure:1.0 ESP / 1.06 TSP Roof Performance Data Description Scheduled / Submittal Data Actual Field Measurements Static Pressure Data Component Static Pressure (inches of water)Pressure Pressure In Out Rise / Drop Total (inches) -0.16 0.56 Rise 0.72 Airflow Measurements Area Design Final Reading Preliminary Reading Served Traverse Design Final Reading Preliminary Reading Total TABB Certified "The Professional's Choice" Page 20 Air Handling Unit Test Data Project:White House -Custom Colour System:RTU-12 Premier Job Number: Jaime Sevre Completion Date: Equipment Location: Motor RPM:1670 1670 Motor Hertz:60.0 60.0 Motor Service Factor:1.15 1.15 Motor Phase:3 3 Motor Voltage:460 460 460 460 Motor Amperage:3.4 2.3 2.3 2.3 Fan RPM:742 726 Fan: Supply Air Opening Size K No.Factor Velocity CFM Velocity CFM %Velocity CFM 1 20x20 2.78 1224 3400 1161 3225 95%1161 3225 Total 3400 3225 95%3225 Minimum Outside Air Size K Factor Velocity CFM Velocity CFM %Velocity CFM 45x25 7.81 19 150 20 156 104%32 250 Remarks:a)Traverse taken in a turbulent area. b) c) d) e) Premier Test & Balance 2050 Technician:4/3/18 System Scheduled Data Model number: 48LCE009A2A6-0R0A0 Serial number: 4117P01756 Manufacturer:Carrier Outlet Total CFM: 3,400 Total Design CFM:3,400 Min.Outside Air CFM: 150 Fan Static Pressure:1.0 ESP / 1.02 TSP Roof Performance Data Description Scheduled / Submittal Data Actual Field Measurements Static Pressure Data Component Static Pressure (inches of water)Pressure Pressure In Out Rise / Drop Total (inches) -0.11 0.49 Rise 0.60 Airflow Measurements Area Design Final Reading Preliminary Reading Served Traverse Design Final Reading Preliminary Reading Total TABB Certified "The Professional's Choice" Page 21 Air Handling Unit Test Data Project:White House -Custom Colour System:RTU-13 Premier Job Number: Jaime Sevre Completion Date: Equipment Location: Motor RPM:1670 1670 Motor Hertz:60.0 60.0 Motor Service Factor:1.15 1.15 Motor Phase:3 3 Motor Voltage:460 460 460 460 Motor Amperage:3.4 2.1 2.1 2.1 Fan RPM:1441 1409 Fan: Supply Air Opening Size K No.Factor Velocity CFM Velocity CFM %Velocity CFM 1 19x13 1.72 1166 2000 1135 1947 97%1135 1947 Total 2000 1947 97%1947 Minimum Outside Air Size K Factor Velocity CFM Velocity CFM %Velocity CFM 28x14 2.72 55 150 53 144 96%68 185 Remarks:a)Traverse taken in a turbulent area. b) c) d) e) Premier Test & Balance 2050 Technician:4/3/18 System Scheduled Data Model number: 48LCE006A2A6-0R0A0 Serial number: 4117C87707 Manufacturer:Carrier Outlet Total CFM: 2,000 Total Design CFM:2,000 Min.Outside Air CFM: 150 Fan Static Pressure:1.0 ESP / 1.12 TSP Roof Performance Data Description Scheduled / Submittal Data Actual Field Measurements Static Pressure Data Component Static Pressure (inches of water)Pressure Pressure In Out Rise / Drop Total (inches) -0.15 0.55 Rise 0.70 Airflow Measurements Area Design Final Reading Preliminary Reading Served Traverse Design Final Reading Preliminary Reading Total TABB Certified "The Professional's Choice" Page 22 Air Handling Unit Test Data Project:White House -Custom Colour System:RTU-14 Premier Job Number: Jaime Sevre Completion Date: Equipment Location: Motor HP:5.00 5.00 Motor RPM:1755 1755 Motor Hertz:60.0 60.0 Motor Service Factor:1.15 1.15 Motor Phase:3 3 Motor Voltage:460 460 460 460 Motor Amperage:9.7 5.1 5.1 5.1 Motor BHP:4.73 2.63 Fan RPM:978 763 Fan: Supply Air Opening Size K No.Factor Velocity CFM Velocity CFM %Velocity CFM 1 63x27 11.81 610 7200 623 7359 102%756 8930 Total 7200 7359 102%8930 Minimum Outside Air Size K Factor Velocity CFM Velocity CFM %Velocity CFM 59x23 9.42 58 550 57 537 98%73 688 Remarks:a)Traverse taken in a turbulent area. b) c) d) e) Premier Test & Balance 2050 Technician:4/4/18 System Scheduled Data Model number: 48LCE020A2A6-0R0A0 Serial number: 4217P16696 Manufacturer:Carrier Outlet Total CFM: 7,200 Total Design CFM:7,200 Min.Outside Air CFM: 550 Fan Static Pressure:1.0 ESP / 1.08 TSP Roof Performance Data Description Scheduled / Submittal Data Actual Field Measurements Static Pressure Data Component Static Pressure (inches of water)Pressure Pressure In Out Rise / Drop Total (inches) -0.14 0.47 Rise 0.61 Airflow Measurements Area Design Final Reading Preliminary Reading Served Traverse Design Final Reading Preliminary Reading Total TABB Certified "The Professional's Choice" Page 23 Air Handling Unit Test Data Project:White House -Custom Colour System:RTU-15 Premier Job Number: Jaime Sevre Completion Date: Equipment Location: Motor HP:5.00 5.00 Motor RPM:1755 1755 Motor Hertz:60.0 60.0 Motor Service Factor:1.15 1.15 Motor Phase:3 3 Motor Voltage:460 460 460 460 Motor Amperage:9.7 5.0 5.0 5.0 Motor BHP:4.73 2.58 Fan RPM:978 778 Fan: Supply Air Opening Size K No.Factor Velocity CFM Velocity CFM %Velocity CFM 1 63x27 11.81 610 7200 632 7466 104%765 9037 Total 7200 7466 104%9037 Minimum Outside Air Size K Factor Velocity CFM Velocity CFM %Velocity CFM 59x23 9.42 58 550 61 575 105%73 688 Remarks:a)Traverse taken in a turbulent area. b) c) d) e) Total Traverse -0.14 0.43 Rise 0.57 Preliminary Reading Design Final Reading Preliminary Reading In Out Rise / Drop Total (inches) Premier Test & Balance 2050 Technician:4/4/18 System Scheduled Data Manufacturer:Carrier Outlet Total CFM: 7,200 Total Design CFM:7,200 Min.Outside Air CFM: 550 Fan Static Pressure:1.0 ESP / 1.08 TSP Roof Model number: 48LCE020A2A6-0R0A0 Serial number: 4217P16695 Performance Data Description Scheduled / Submittal Data Actual Field Measurements Static Pressure Data Component Static Pressure (inches of water)Pressure Pressure Served Airflow Measurements Area Design Final Reading TABB Certified "The Professional's Choice" Page 24 Fan Test Data Project:White House -Custom Colour System:MUA-1 Premier Job Number: Jaime Sevre Completion Date: Equipment Location: Motor HP:5.00 5.00 Motor RPM:1725 1725 Motor Hertz:60.0 60.0 Motor Service Factor:1.15 1.15 Motor Phase:3 3 Motor Voltage:208 206 206 206 Motor Amperage:6.6 5.3 5.3 5.3 Motor BHP:2.68 3.98 Fan RPM:886 823 Fan: Fan Total Opening Size K No.Factor Velocity CFM Velocity CFM %Velocity CFM 1 22x18 2.75 1818 5000 1934 5319 106%2132 5863 Total 5000 5319 106%5863 Remarks:a)Traverse taken in a turbulent area. b) c) d) e) Premier Test & Balance 2050 Technician:4/4/18 System Scheduled Data Model number: DG-115-H20 Serial number: 15220650 Manufacturer:Greenheck Outlet Total CFM: 5,000 Total Design CFM:5,000 Roof Fan Static Pressure:0.25 ESP / 1.311 TSP Performance Data Description Scheduled / Submittal Data Actual Field Measurements Static Pressure Data Component Static Pressure (inches of water)Pressure Pressure In Out Rise / Drop Total (inches) -0.03 0.14 Rise 0.17 Airflow Measurements Area Design Final Reading Preliminary Reading Served Traverse TABB Certified "The Professional's Choice" Page 25 Fan Test Data Project:White House -Custom Colour System:EF-1 Premier Job Number: Jaime Sevre Completion Date: Equipment Location: Motor HP:0.75 0.75 Motor RPM:1725 1725 Motor Hertz:60.0 60.0 Motor Service Factor:1.15 1.15 Motor Phase:1 1 Motor Voltage:120 120 Motor Amperage:10.1 9.4 Motor BHP:-0.70 Fan RPM:-1650 Fan: Fan Total Opening Size K No.Factor Velocity CFM Velocity CFM %Velocity CFM 1 Flow Hood 1.00 210 210 228 228 109%195 195 2 Flow Hood 1.00 210 210 223 223 106%188 188 3 Flow Hood 1.00 75 75 76 76 101%92 92 4 Flow Hood 1.00 75 75 78 78 104%92 92 5 Flow Hood 1.00 280 280 302 302 108%380 380 6 Flow Hood 1.00 75 75 74 74 99%63 63 7 Flow Hood 1.00 280 280 273 273 98%420 420 8 Flow Hood 1.00 75 75 78 78 104%62 62 Total 1280 1332 104%1492 Remarks:a) b) c) d) e) Premier Test & Balance 2050 Technician:4/4/18 System Scheduled Data Model number: G-133-VG7X-QD Serial number: 15156579 Manufacturer:Greenheck Outlet Total CFM: 1,280 Total Design CFM:1,350 Roof Fan Static Pressure:0.50 Performance Data Description Scheduled / Submittal Data Actual Field Measurements Static Pressure Data Component Static Pressure (inches of water)Pressure Pressure In Out Rise / Drop Total (inches) -0.32 0.01 Rise 0.33 Airflow Measurements Area Design Final Reading Preliminary Reading Served 1st Level Womens 1st Level Mens Next to Mens Bathroom Across from Mens Bathroom 2nd Level Womens Between Batrooms 2nd Level Mens Next to Mens Bathroom TABB Certified "The Professional's Choice" Page 26 Fan Test Data Project:White House -Custom Colour System:EF-2A Premier Job Number: Jaime Sevre Completion Date: Equipment Location: Motor HP:Frac.Frac. Motor RPM:1050 1050 Motor Hertz:60.0 60.0 Motor Service Factor:1.15 1.15 Motor Phase:1 1 Motor Voltage:120 118 Fan RPM:Direct Drive Direct Drive Fan: Fan Total Opening Size K No.Factor Velocity CFM Velocity CFM %Velocity CFM 1 Flow Hood 1.10 91 100 86 95 95%86 95 Total 100 95 95%95 Remarks:a) b) c) d) e) Premier Test & Balance 2050 Technician:4/4/18 System Scheduled Data Model number: Sig110 Serial number: 81B21H Manufacturer:Delta Outlet Total CFM: 100 Total Design CFM:100 108 Fan Static Pressure:0.25 Performance Data Description Scheduled / Submittal Data Actual Field Measurements Static Pressure Data Component Static Pressure (inches of water)Pressure Pressure In Out Rise / Drop Total (inches) Served Women's Bathroom -0.01 0.23 Rise 0.24 Airflow Measurements Area Design Final Reading Preliminary Reading TABB Certified "The Professional's Choice" Page 27 Fan Test Data Project:White House -Custom Colour System:EF-2B Premier Job Number: Jaime Sevre Completion Date: Equipment Location: Motor HP:Frac.Frac. Motor RPM:1050 1050 Motor Hertz:60.0 60.0 Motor Service Factor:1.15 1.15 Motor Phase:1 1 Motor Voltage:120 118 Fan RPM:Direct Drive Direct Drive Fan: Fan Total Opening Size K No.Factor Velocity CFM Velocity CFM %Velocity CFM 1 Flow Hood 1.10 91 100 92 101 101%92 101 Total 100 101 101%101 Remarks:a) b) c) d) e) Served Men's Bathroom -0.01 0.21 Rise 0.22 Airflow Measurements Area Design Final Reading Preliminary Reading Description Scheduled / Submittal Data Actual Field Measurements Static Pressure Data Component Static Pressure (inches of water)Pressure Pressure In Out Rise / Drop Total (inches) Total Design CFM:100 123 Fan Static Pressure:0.25 Performance Data System Scheduled Data Model number: Sig110 Serial number: 81A16H Manufacturer:Delta Outlet Total CFM: 100 Premier Test & Balance 2050 Technician:4/4/18 TABB Certified "The Professional's Choice" Page 28 For Office UyefC o e Permit#: / (1C7 73 i C B B BE AGAN / 'C'') ��J 1 Permit Fee: Staff: 3830 PILOT KNOB ROAD I EAGAN, MN 55122-1810 Payment Recvd: Yes No (651)675-5675 I TDD: (651)454-8535 I FAX:(651)675-5694 Email:buildinginsoections(cr�citvofeagan.com I Plans: Electronic Paper Plan Submittal: eplans(a�citvofeanan.com L 2018 COMMERCIAL PLUMBING PERMIT APPLICATION ❑ Please submit two(2)sets of paper plans with all commercial applications as well as an electronic set of the submittal, submitted via email,CD or flash drive / Date: _ cc Site Address: d 50 �n (7 k c / Tenant: VLJ Ji` lo c ' C ( $1-0 (A Co ite#: Property Owner Name: Phone: Name: a(}( ef y\ ./i1((`iflvj c.j License#:Q 700 5 0 Contractor Address: r ! ! S t'ff)CC°'• (ed City: �q,�� 1 State:k/VZip: 5 .5 (�p Phone: 6r/ 74227c Email:s "C1- d , oy 1r> ty4 T e of Work ?C New _ Replacement Repair Rebuild Modify Space _Work in R.O.W. yp Description of work: COMMERCIAL `F New Construction Modify Space / ii /77/6 S, Irrigation System( P' yes/ no)( )t RPZ/ PVB) • Rain sensors required on irrigation systems /424-4_5-6‘,/(A2--(/de Permit Type • Avg.GPM (2"turbo required unless smaller size allowed by Public Works) _Meters Call(651)675-5646 to verity that tests passed prior to picking up meter. Domestic:Size&Type Fire: 1 Avg.GPM High demand devices?_Yes_No Flushometers Yes_No COMMERCIAL FEES Contract Value$ m 't x.01 $60.00 Permit Fee Minimum / O 00 $60.00 PVB/RPZ Permit(includes State Surcharge) $ (� Permit Fee Surcharge=Contract Value x$0.0005 = Surcharge If the project valuation is over$1 million,please call for Surcharge =$ TOTAL FEE Following fees apply when installing a new lawn irrigation system $ (7 S`0 U Water Permit Contact the City's Engineering Department,(651)675-5646,for required fee amounts. $ -376,o?) �'fi $ Water Supply&Storage $ State Surcharge =$ T 95. CYD TOTAL FEE You may subscribe to receive an electronic notification from the City of proposed ordinances by signing up for an email update on the City's website at www,cityofeagan.comisubscri be. CALL BEFORE YOU DIG. Call Gopher State One Call at(651)454-0002 for protection against underground utility damage. I hereby acknowledge that this information is complete and accurate;that the work will be in conformance with the ordinances and codes of the City of Eagan;that I understand this is not a permit,but only an application for a permit,and work is not to start without a permit;that the work will be in accordance with the approved plan in the c.n? .rk which requires a review and approval of plans. 77��t X (��tJ FCIge/4 x Applicant's Printed Name App' ant's Signature FOR OFFICE USE Approved By:. Date: Required Inspections: Under Ground _ Rough-In Air Test Gas Test Final PRV Required: Yes %No Meter Related Items: Meter Size Radio Read. Manometer Staff: Page 1 of 3 Peggy Fleck /L79 ? Ilitm: Abby Decker t: Monday, March 12, 2018 2:55 PM To: Peggy Fleck Cc: Brent Massmann Subject: irrigation meter 2840 Lone Oak Pkwy Peggy, White House Custom Color was approved by Brent for the following: 1" irrigation meter Housed: INSIDE Contact: Kevin @ Metro west 763-658-3016 Address: wy 30 Z--pr1ID/2- ' 6 � tc— Permit: EA-078622 Have a good day! Abby Decker $ , ;, , -7 Clerical Tech -Utilities .' m , 3419 Coachman Pt I Eagan, MN 55122 Office:651-675-5210 • 0 (7ik III 1