2930 Lone Oak Dr - White House Custom Colour Test & Balance Report 2018-04-06
Technician:
Cell Phone:
Email Address:
Associated Mechanical Contractors, Inc.
1257 Marschall Road
PO Box 237
Report Date
April 6, 2018
Shakopee MN 55379
375 230th Ave, Somerset WI 54025 - Phone: (612) 834-0311 Fax: (414) 377-3349
www.Premierbalancing.com
Testing, Adjusting & Balancing Report
TABB TECHNICIAN
CLIENT
Associated Mechanical Contractors, Inc.
1257 Marschall Road
PO Box 237
ENGINEER
White House -Custom Colour
Eagan, MN 55121
Jaime Sevre
763-639-2177
jaime@premierbalancing.com
PROJECT
2930 Lone Oak Drive
Shakopee MN 55379
TABB CERTIFICATION
TABB certification of a Supervisor is TABB's statement that the Supervisor is able to
supervise testing, adjusting and balancing of building environmental systems to produce the
design objectives or optimum system performance. For TABB Certification purposes, a
Supervisor is the person who, while employed by a TABB Certified Contractor, is
responsible and accountable for overseeing, coordinating and ensuring that projects are
performed by TABB Certified Technicians in accordance with TABB standards (including the
ICB Code of Conduct and the TAB General Rules).
Measurements recorded in this report are in accordance with the SMACNA / TABB HVAC Systems,
Testing, Adjusting and Balancing manual.
TABB Certified "The Professional's Choice" Page 2
TABB QUALITY ASSURANCE PROGRAM
BACKGROUND
TABB seeks to ensure the integrity of its certification program by: (a) setting eligibility criteria for TABB
Certified Supervisors and TABB Certified Contractors, (b) establishing testing procedures for TABB
Certified Supervisors, (c) requiring continuing education and continuous compliance with eligibility criteria
for renewal of certification, and (d) periodically reviewing its recognition of technician certification. High
quality work on the part of TABB Certified Technicians and TABB Certified Supervisors and TABB Certified
Contractors ( TABB Professionals ) is essential to integrity of the TABB Certification Program. TABB offers
this TABB Quality Assurance Program to help assure high quality work. By accepting TABB qualification or
certification, every TABB Professional accepts the responsibilities or this Program.
Quality Assurance
Every customer of a TABB Certified Contractor shall be entitled to expect: (1) that testing, adjusting and
balancing work by the contractor and its TABB Professionals will meet TABB standards; (2) that testing,
adjusting and balancing reports provided to the customer will have been prepared by a TABB Certified
Technician, and reviewed by a TABB Certified Supervisor; and (3) that the report(s) will include
measurements taken accurately with the date and mode of operation of the systems.
TABB
8403 Arlington Boulevard
Fairfax, VA 22031
Phone - (703) 299-5646
Fax - (703) 683-7615
TABB Certified "The Professional's Choice" Page 3
INSTRUMENT
CALIBRATION REPORT
Rotating Measuring Instrument
Temperature Measuring Instrument
Temperature Measuring Probe
Electrical Measuring Instruments
Air Pressure Measuring Instrument
Air Velocity Measuring Instrument
Hydronic Pressure Measuring Instrument
0 to 300 psi
Temperature Measuring Instrument
Temperature Measuring Probe
HM70 Vaisala M4820017 12/08/17
HMP75 Vaisala M5040569 12/08/17
HM-675 Alnor 71725052 11/07/17
ADM-870C Shortridge M11441 12/19/17
ADM-870C Shortridge M11441 12/19/17
117 Fluke 18561871 12/19/17
322 Fluke 17830473 12/19/17
INSTRUMENT MODEL MANUFACTURER SERIAL NUMBER CALIBRATION
DATE
PLT-5000 Mitchell Instruments B15985012P 12/19/17
HM70 Vaisala M4820017 12/08/17
HMP75 Vaisala M5040569 12/08/17
TABB Certified "The Professional's Choice" Page 4
Index
Project:White House -Custom Colour Premier Job Number:
Jaime Sevre Report Date:
Page
6 RTU-1 Constant Air Volume
7 RTU-2 Constant Air Volume
8-9 RTU-3 Constant Air Volume
10-11 RTU-4 Constant Air Volume
12 RTU-5 Constant Air Volume
13 RTU-6 Constant Air Volume
14 RTU-7 Constant Air Volume
15-16 RTU-8 Constant Air Volume
17 RTU-9 Constant Air Volume
18-19 RTU-10 Constant Air Volume
20 RTU-11 Constant Air Volume
21 RTU-12 Constant Air Volume
22 RTU-13 Constant Air Volume
23 RTU-14 Constant Air Volume
24 RTU-15 Constant Air Volume
25 MUA-1 Constant Air Volume
26 EF-1 Constant Air Volume
27 EF-2A Constant Air Volume
28 EF-2B Constant Air Volume 4/4/18
4/4/18
4/3/18
4/4/18
4/3/18
4/4/18
4/4/18
4/4/18
4/5/18
4/3/18
4/3/18
4/3/18
4/5/18
4/3/18
4/3/18
2050
Technician:4/6/18
System / Equipment Completion Date
4/5/18
4/4/18
4/3/18
Description
4/4/18
Premier Test & Balance
TABB Certified "The Professional's Choice" Page 5
Air Handling Unit Test Data
Project:White House -Custom Colour
System:RTU-1 Premier Job Number:
Jaime Sevre Completion Date:
Equipment Location:
Motor HP:1.25 1.25
Motor RPM:1670 1670
Motor Hertz:60.0 60.0
Motor Service Factor:1.15 1.15
Motor Phase:3 3
Motor Voltage:460 460 460 460
Motor Amperage:4.9 4.3 4.3 4.3
Motor BHP:1.36 1.10
Fan RPM:601 628
Fan:
Supply Air
Opening Size K
No.Factor Velocity CFM Velocity CFM %Velocity CFM
1 34x28 6.61 605 4000 656 4337 108%679 4489
Total 4000 4337 108%4489
Minimum Outside Air
Size K
Factor Velocity CFM Velocity CFM %Velocity CFM
45x25 7.81 26 200 28 219 109%56 438
Remarks:a)Traverse taken in a turbulent area.
b)
c)
d)
e)
Preliminary Reading
Rise / Drop Total (inches)
Rise 0.35
Preliminary Reading
2050
Premier Test & Balance
4,000 Min.Outside Air CFM: 200
4/4/18
System Scheduled Data
Model number: 48LCE012A2A6-0R0A0 Serial number: 1017P11605
Manufacturer:Carrier Outlet Total CFM: 4,000
Technician:
Fan Static Pressure:0.5 ESP / 0.52 TSP Roof
Performance Data
Description Scheduled / Submittal Data Actual Field Measurements
Total Design CFM:
Component Static Pressure (inches of water)
In Out
Pressure Pressure
Static Pressure Data
-0.12 0.23
Airflow Measurements
Area Design Final Reading
Served
Traverse
Design Final Reading
Total
TABB Certified "The Professional's Choice" Page 6
Air Handling Unit Test Data
Project:White House -Custom Colour
System:RTU-2 Premier Job Number:
Jaime Sevre Completion Date:
Equipment Location:
Motor HP:--
Motor RPM:1670 1670
Motor Hertz:60.0 60.0
Motor Service Factor:1.15 1.15
Motor Phase:3 3
Motor Voltage:460 460 460 460
Motor Amperage:2.9 1.6 1.6 1.6
Motor BHP:1.25 -
Fan RPM:828 798
Fan:
Supply Air
Opening Size K
No.Factor Velocity CFM Velocity CFM %Velocity CFM
1 18x18 2.25 1067 2400 1049 2360 98%986 2219
Total 2400 2360 98%2219
Minimum Outside Air
Size K
Factor Velocity CFM Velocity CFM %Velocity CFM
35x19 4.62 43 200 42 194 97%67 309
Remarks:a)Traverse taken in a turbulent area.
b)
c)
d)
e)
Premier Test & Balance
2050
Technician:4/3/18
System Scheduled Data
Model number: 48LCE007A2A6-0R0A0 Serial number: 4217P83590
Manufacturer:Carrier Outlet Total CFM: 2,400
Total Design CFM:2,400 Min.Outside Air CFM: 200
Fan Static Pressure:1.0 ESP / 1.09 TSP Roof
Performance Data
Description Scheduled / Submittal Data Actual Field Measurements
Static Pressure Data
Component Static Pressure (inches of water)Pressure Pressure
In Out Rise / Drop Total (inches)
-0.16 0.49 Rise 0.65
Airflow Measurements
Area Design Final Reading Preliminary Reading
Served
Traverse
Design Final Reading Preliminary Reading
Total
TABB Certified "The Professional's Choice" Page 7
Air Handling Unit Test Data
Project:White House -Custom Colour
System:RTU-3 Premier Job Number:
Jaime Sevre Completion Date:
Equipment Location:
Motor RPM:1670 1670
Motor Hertz:60.0 60.0
Motor Service Factor:1.15 1.15
Motor Phase:3 3
Motor Voltage:460 460 460 460
Motor Amperage:3.4 3.1 3.1 3.1
Fan RPM:724 743
Fan:
Supply Air
Opening Size K
No.Factor Velocity CFM Velocity CFM %Velocity CFM
1 24x16 2.67 759 2025 792 2112 104%683 1821
Total 2025 2112 104%1821
Minimum Outside Air
Size K
Factor Velocity CFM Velocity CFM %Velocity CFM
45x25 7.81 77 600 78 609 102%98 766
Remarks:a)Traverse taken in a turbulent area.
b)
c)
d)
e)
Premier Test & Balance
2050
Technician:4/3/18
System Scheduled Data
Model number: 48LCE008A2A6-0R0A0 Serial number: 4117P01757
Manufacturer:Carrier Outlet Total CFM: 2,025
Total Design CFM:3,000 Min.Outside Air CFM: 600
Fan Static Pressure:1.0 ESP / 1.01 TSP Roof
Performance Data
Description Scheduled / Submittal Data Actual Field Measurements
Static Pressure Data
Component Static Pressure (inches of water)Pressure Pressure
In Out Rise / Drop Total (inches)
-0.37 0.48 Rise 0.85
Airflow Measurements
Area Design Final Reading Preliminary Reading
Served
Traverse
Design Final Reading Preliminary Reading
Total
TABB Certified "The Professional's Choice" Page 8
Air Outlet Test Report
Project:White House -Custom Colour
System:RTU-3 (Supply)Premier Job Number:
Jaime Sevre Completion Date:
Opening Size K
No.Factor Velocity CFM Velocity CFM %Velocity CFM
1 Flow Hood 1.00 75 75 76 76 101%76 76
2 Flow Hood 1.00 75 75 77 77 103%78 78
3 Flow Hood 1.00 100 100 98 98 98%72 72
4 Flow Hood 1.00 175 175 178 178 102%134 134
5 Flow Hood 1.00 175 175 188 188 107%141 141
6 Flow Hood 1.00 100 100 105 105 105%108 108
7 Flow Hood 1.00 100 100 106 106 106%48 48
8 Flow Hood 1.00 100 100 98 98 98%85 85
9 Flow Hood 1.00 100 100 106 106 106%105 105
10 Flow Hood 1.00 75 75 78 78 104%72 72
11 Flow Hood 1.00 150 150 158 158 105%168 168
12 Flow Hood 1.00 200 200 189 189 95%145 145
13 Flow Hood 1.00 200 200 196 196 98%170 170
14 Flow Hood 1.00 200 200 200 200 100%174 174
15 Flow Hood 1.00 200 200 210 210 105%182 182
Total 2025 2063 102%1758
Remarks:a)
b)
c)
d)
e)
Premier Test & Balance
2050
Technician:4/3/18
Airflow Measurements
Area Design Final Reading Preliminary Reading
Served
2nd Floor Offices
2nd Floor Offices
2nd Floor Offices
2nd Floor Offices
2nd Floor Offices
Womens Bathroom
Hallway
Hallway
Mens Bathroom
2nd Floor Offices
2nd Floor Offices
2nd Floor Offices
2nd Floor Offices
2nd Floor Offices
2nd Floor Offices
TABB Certified "The Professional's Choice" Page 9
Air Handling Unit Test Data
Project:White House -Custom Colour
System:RTU-4 Premier Job Number:
Jaime Sevre Completion Date:
Equipment Location:
Motor RPM:1670 1670
Motor Hertz:60.0 60.0
Motor Service Factor:1.15 1.15
Motor Phase:3 3
Motor Voltage:460 460 460 460
Motor Amperage:6.4 5.7 5.7 5.7
Fan RPM:836 848
Fan:
Supply Air
Opening Size K
No.Factor Velocity CFM Velocity CFM %Velocity CFM
1 63x27 11.81 423 5000 431 5091 102%436 5150
Total 5000 5091 102%5150
Minimum Outside Air
Size K
Factor Velocity CFM Velocity CFM %Velocity CFM
59x23 9.42 60 565 62 584 103%78 735
Remarks:a)Traverse taken in a turbulent area.
b)
c)
d)
e)
Premier Test & Balance
2050
Technician:4/5/18
System Scheduled Data
Model number: 48LCE014A2A6-0R0A0 Serial number: 1217P24100
Manufacturer:Carrier Outlet Total CFM: 5,000
Total Design CFM:5,000 Min.Outside Air CFM: 565
Fan Static Pressure:1.0 ESP / 1.05 TSP Roof
Performance Data
Description Scheduled / Submittal Data Actual Field Measurements
Static Pressure Data
Component Static Pressure (inches of water)Pressure Pressure
In Out Rise / Drop Total (inches)
-0.36 0.52 Rise 0.88
Airflow Measurements
Area Design Final Reading Preliminary Reading
Served
Traverse
Design Final Reading Preliminary Reading
Total
TABB Certified "The Professional's Choice" Page 10
Air Outlet Test Report
Project:White House -Custom Colour
System:RTU-4 (Supply)Premier Job Number:
Jaime Sevre Completion Date:
Opening Size K
No.Factor Velocity CFM Velocity CFM %Velocity CFM
1 Flow Hood 1.00 50 50 52 52 104%119 119
2 Flow Hood 1.00 100 100 102 102 102%119 119
3 Flow Hood 1.00 350 350 350 350 100%334 334
4 Flow Hood 1.00 50 50 52 52 104%132 132
5 Flow Hood 1.00 115 115 118 118 103%256 256
6 Flow Hood 1.00 50 50 53 53 106%124 124
7 Flow Hood 1.00 150 150 148 148 99%265 265
8 Flow Hood 1.00 100 100 103 103 103%99 99
9 Flow Hood 1.00 175 175 176 176 101%214 214
10 Flow Hood 1.00 175 175 171 171 98%187 187
11 Flow Hood 1.00 100 100 102 102 102%118 118
12 24X18 3.00 1195 3585 1184 3552 99%1022 3066
Total 5000 4979 100%5033
Remarks:a)
b)
c)
d)
e)
Premier Test & Balance
2050
Technician:4/5/18
Airflow Measurements
Area Design Final Reading Preliminary Reading
Served
1st Floor Offices
1st Floor Offices
1st Floor Offices
1st Floor Offices
1st Floor Offices
1st Floor Offices
1st Floor Offices
Mens Bathroom
Hallway
Hallway
Womens Bathroom
1st Floor Open area
TABB Certified "The Professional's Choice" Page 11
Air Handling Unit Test Data
Project:White House -Custom Colour
System:RTU-5 Premier Job Number:
Jaime Sevre Completion Date:
Equipment Location:
Motor HP:5.00 5.00
Motor RPM:1755 1755
Motor Hertz:60.0 60.0
Motor Service Factor:1.15 1.15
Motor Phase:3 3
Motor Voltage:460 460 460 460
Motor Amperage:9.7 5.2 5.2 5.2
Motor BHP:3.04 2.68
Fan RPM:904 778
Fan:
Supply Air
Opening Size K
No.Factor Velocity CFM Velocity CFM %Velocity CFM
1 63x27 11.81 508 6000 549 6485 108%621 7336
Total 6000 6485 108%7336
Minimum Outside Air
Size K
Factor Velocity CFM Velocity CFM %Velocity CFM
59x23 9.42 58 550 63 594 108%83 782
Remarks:a)Traverse taken in a turbulent area.
b)
c)
d)
e)
Premier Test & Balance
2050
Technician:4/4/18
System Scheduled Data
Model number: 48LCE017A2A6-0R0A0 Serial number: 4217P16693
Manufacturer:Carrier Outlet Total CFM: 6,000
Total Design CFM:6,000 Min.Outside Air CFM: 550
Fan Static Pressure:1.0 ESP / 1.06 TSP Roof
Performance Data
Description Scheduled / Submittal Data Actual Field Measurements
Static Pressure Data
Component Static Pressure (inches of water)Pressure Pressure
In Out Rise / Drop Total (inches)
-0.17 0.52 Rise 0.69
Airflow Measurements
Area Design Final Reading Preliminary Reading
Served
Traverse
Design Final Reading Preliminary Reading
Total
TABB Certified "The Professional's Choice" Page 12
Air Handling Unit Test Data
Project:White House -Custom Colour
System:RTU-6 Premier Job Number:
Jaime Sevre Completion Date:
Equipment Location:
Motor RPM:1670 1670
Motor Hertz:60.0 60.0
Motor Service Factor:1.15 1.15
Motor Phase:3 3
Motor Voltage:460 460 460 460
Motor Amperage:6.4 5.4 5.4 5.4
Fan RPM:836 823
Fan:
Supply Air
Opening Size K
No.Factor Velocity CFM Velocity CFM %Velocity CFM
1 18"1.77 941 1666 887 1570 94%828 1466
2 22"2.64 1262 3332 1212 3200 96%1266 3342
Total 4998 4770 95%4808
Minimum Outside Air
Size K
Factor Velocity CFM Velocity CFM %Velocity CFM
59x23 9.42 58 550 61 575 105%76 716
Remarks:a)Traverse taken in a turbulent area.
b)
c)
d)
e)
Premier Test & Balance
2050
Technician:4/3/18
System Scheduled Data
Model number: 48LCE014A2A6-0R0A0 Serial number: 1217P24094
Manufacturer:Carrier Outlet Total CFM: 4,998
Total Design CFM:5,000 Min.Outside Air CFM: 550
Fan Static Pressure:1.0 ESP / 1.05 TSP Roof
Performance Data
Description Scheduled / Submittal Data Actual Field Measurements
Static Pressure Data
Component Static Pressure (inches of water)Pressure Pressure
In Out Rise / Drop Total (inches)
-0.18 0.57 Rise 0.75
Airflow Measurements
Area Design Final Reading Preliminary Reading
Served
Traverse
Traverse
Design Final Reading Preliminary Reading
Total
TABB Certified "The Professional's Choice" Page 13
Air Handling Unit Test Data
Project:White House -Custom Colour
System:RTU-7 Premier Job Number:
Jaime Sevre Completion Date:
Equipment Location:
Motor RPM:1670 1670
Motor Hertz:60.0 60.0
Motor Service Factor:1.15 1.15
Motor Phase:3 3
Motor Voltage:460 460 460 460
Motor Amperage:4.9 3.2 3.2 3.2
Fan RPM:601 580
Fan:
Supply Air
Opening Size K
No.Factor Velocity CFM Velocity CFM %Velocity CFM
1 34x28 6.61 605 4000 656 4337 108%778 5143
Total 4000 4337 108%5143
Minimum Outside Air
Size K
Factor Velocity CFM Velocity CFM %Velocity CFM
45x25 7.81 70 550 73 570 104%84 656
Remarks:a)Traverse taken in a turbulent area.
b)
c)
d)
e)
Technician:4/5/18
System Scheduled Data
Premier Test & Balance
2050
Model number: 48LCE012A2A6-0R0A0 Serial number: 1017P11606
Outlet Total CFM: 4,000
Roof
Performance Data
Description Scheduled / Submittal Data Actual Field Measurements
Total Design CFM:4,000 Min.Outside Air CFM: 550
Fan Static Pressure:0.5 ESP / 0.52 TSP
Manufacturer:Carrier
Static Pressure Data
Component Static Pressure (inches of water)Pressure Pressure
In Out Rise / Drop Total (inches)
-0.15 0.55 Rise 0.70
Airflow Measurements
Design Final Reading Preliminary Reading
Design Final Reading Preliminary Reading
Total
Area
Served
Traverse
TABB Certified "The Professional's Choice" Page 14
Air Handling Unit Test Data
Project:White House -Custom Colour
System:RTU-8 Premier Job Number:
Jaime Sevre Completion Date:
Equipment Location:
Motor RPM:1670 1670
Motor Hertz:60.0 60.0
Motor Service Factor:1.15 1.15
Motor Phase:3 3
Motor Voltage:460 460 460 460
Motor Amperage:4.9 3.6 3.6 3.6
Fan RPM:601 574
Fan:
Supply Air
Opening Size K
No.Factor Velocity CFM Velocity CFM %Velocity CFM
1 22x22 3.36 1190 4000 1289 4332 108%1434 4820
Total 4000 4332 108%4820
Minimum Outside Air
Size K
Factor Velocity CFM Velocity CFM %Velocity CFM
45x25 7.81 26 200 25 195 98%39 305
Remarks:a)Traverse taken in a turbulent area.
b)
c)
d)
e)
Premier Test & Balance
2050
Technician:4/3/18
System Scheduled Data
Model number: 48LCE012A2A6-0R0A0 Serial number: 1017P11604
Manufacturer:Carrier Outlet Total CFM: 4,000
Total Design CFM:4,000 Min.Outside Air CFM: 200
Fan Static Pressure:0.5 ESP / 0.52 TSP Roof
Performance Data
Description Scheduled / Submittal Data Actual Field Measurements
Static Pressure Data
Component Static Pressure (inches of water)Pressure Pressure
In Out Rise / Drop Total (inches)
-0.16 0.51 Rise 0.67
Airflow Measurements
Area Design Final Reading Preliminary Reading
Served
Traverse
Design Final Reading Preliminary Reading
Total
TABB Certified "The Professional's Choice" Page 15
Air Outlet Test Report
Project:White House -Custom Colour
System:RTU-8 (Supply)Premier Job Number:
Jaime Sevre Completion Date:
Opening Size K
No.Factor Velocity CFM Velocity CFM %Velocity CFM
1 28x11 2.14 468 1000 493 1054 105%545 1166
2 28x11 2.14 468 1000 489 1046 105%563 1204
3 28x11 2.14 468 1000 491 1050 105%571 1221
4 28x11 2.14 468 1000 500 1069 107%552 1181
Total 4000 4220 106%4772
Remarks:a)
b)
c)
d)
e)
Premier Test & Balance
2050
Technician:4/3/18
Airflow Measurements
Area Design Final Reading Preliminary Reading
Served
1st Floor Area A
1st Floor Area A
1st Floor Area A
1st Floor Area A
TABB Certified "The Professional's Choice" Page 16
Air Handling Unit Test Data
Project:White House -Custom Colour
System:RTU-9 Premier Job Number:
Jaime Sevre Completion Date:
Equipment Location:
Motor RPM:1670 1670
Motor Hertz:60.0 60.0
Motor Service Factor:1.15 1.15
Motor Phase:3 3
Motor Voltage:460 460 460 460
Motor Amperage:2.9 1.7 1.7 1.7
Fan RPM:828 798
Fan:
Supply Air
Opening Size K
No.Factor Velocity CFM Velocity CFM %Velocity CFM
1 18x18 2.25 1151 2590 1115 2509 97%1115 2509
Total 2590 2509 97%2509
Minimum Outside Air
Size K
Factor Velocity CFM Velocity CFM %Velocity CFM
35x19 4.62 65 300 68 314 105%82 379
Remarks:a)Traverse taken in a turbulent area.
b)
c)
d)
e)
Premier Test & Balance
2050
Technician:4/3/18
System Scheduled Data
Model number: 48LCE007A2A6-0R0A0 Serial number: 4217P83589
Manufacturer:Carrier Outlet Total CFM: 2,590
Total Design CFM:2,400 Min.Outside Air CFM: 300
Fan Static Pressure:1.0 ESP / 1.09 TSP Roof
Performance Data
Description Scheduled / Submittal Data Actual Field Measurements
Static Pressure Data
Component Static Pressure (inches of water)Pressure Pressure
In Out Rise / Drop Total (inches)
-0.21 0.67 Rise 0.88
Airflow Measurements
Area Design Final Reading Preliminary Reading
Served
Traverse
Design Final Reading Preliminary Reading
Total
TABB Certified "The Professional's Choice" Page 17
Air Handling Unit Test Data
Project:White House -Custom Colour
System:RTU-10 Premier Job Number:
Jaime Sevre Completion Date:
Equipment Location:
Motor RPM:1670 1670
Motor Hertz:60.0 60.0
Motor Service Factor:1.15 1.15
Motor Phase:3 3
Motor Voltage:460 460 460 460
Motor Amperage:4.9 3.8 3.8 3.8
Fan RPM:601 654
Fan:
Supply Air
Opening Size K
No.Factor Velocity CFM Velocity CFM %Velocity CFM
1 22x22 3.36 1190 4000 1266 4255 106%1266 4255
Total 4000 4255 106%4255
Minimum Outside Air
Size K
Factor Velocity CFM Velocity CFM %Velocity CFM
45x25 7.81 26 200 27 211 105%44 344
Remarks:a)Traverse taken in a turbulent area.
b)
c)
d)
e)
Premier Test & Balance
2050
Technician:4/3/18
System Scheduled Data
Model number: 48LCE012A2A6-0R0A0 Serial number: 1317P11974
Manufacturer:Carrier Outlet Total CFM: 4,000
Total Design CFM:4,000 Min.Outside Air CFM: 200
Fan Static Pressure:0.5 ESP / 0.52 TSP Roof
Performance Data
Description Scheduled / Submittal Data Actual Field Measurements
Static Pressure Data
Component Static Pressure (inches of water)Pressure Pressure
In Out Rise / Drop Total (inches)
-0.18 0.63 Rise 0.81
Airflow Measurements
Area Design Final Reading Preliminary Reading
Served
Traverse
Design Final Reading Preliminary Reading
Total
TABB Certified "The Professional's Choice" Page 18
Air Outlet Test Report
Project:White House -Custom Colour
System:RTU-10 (Supply)Premier Job Number:
Jaime Sevre Completion Date:
Opening Size K
No.Factor Velocity CFM Velocity CFM %Velocity CFM
1 28x11 2.14 468 1000 478 1022 102%478 1022
2 28x11 2.14 468 1000 483 1033 103%483 1033
3 28x11 2.14 468 1000 489 1046 105%489 1046
4 28x11 2.14 468 1000 501 1072 107%501 1072
Total 4000 4173 104%4173
Remarks:a)
b)
c)
d)
e)
Area Design Final Reading Preliminary Reading
Served
1st Floor Area A
1st Floor Area A
1st Floor Area A
1st Floor Area A
Premier Test & Balance
2050
Technician:4/3/18
Airflow Measurements
TABB Certified "The Professional's Choice" Page 19
Air Handling Unit Test Data
Project:White House -Custom Colour
System:RTU-11 Premier Job Number:
Jaime Sevre Completion Date:
Equipment Location:
Motor HP:5.00 5.00
Motor RPM:1755 1755
Motor Hertz:60.0 60.0
Motor Service Factor:1.15 1.15
Motor Phase:3 3
Motor Voltage:460 460 460 460
Motor Amperage:9.7 4.6 4.6 4.6
Motor BHP:3.04 2.37
Fan RPM:904 788
Fan:
Supply Air
Opening Size K
No.Factor Velocity CFM Velocity CFM %Velocity CFM
1 63x27 11.81 508 6000 534 6308 105%564 6662
Total 6000 6308 105%6662
Minimum Outside Air
Size K
Factor Velocity CFM Velocity CFM %Velocity CFM
59x23 9.42 58 550 57 537 98%71 669
Remarks:a)Traverse taken in a turbulent area.
b)
c)
d)
e)
Premier Test & Balance
2050
Technician:4/5/18
System Scheduled Data
Model number: 48LCE017A2A6-0R0A0 Serial number: 4217P16694
Manufacturer:Carrier Outlet Total CFM: 6,000
Total Design CFM:6,000 Min.Outside Air CFM: 550
Fan Static Pressure:1.0 ESP / 1.06 TSP Roof
Performance Data
Description Scheduled / Submittal Data Actual Field Measurements
Static Pressure Data
Component Static Pressure (inches of water)Pressure Pressure
In Out Rise / Drop Total (inches)
-0.16 0.56 Rise 0.72
Airflow Measurements
Area Design Final Reading Preliminary Reading
Served
Traverse
Design Final Reading Preliminary Reading
Total
TABB Certified "The Professional's Choice" Page 20
Air Handling Unit Test Data
Project:White House -Custom Colour
System:RTU-12 Premier Job Number:
Jaime Sevre Completion Date:
Equipment Location:
Motor RPM:1670 1670
Motor Hertz:60.0 60.0
Motor Service Factor:1.15 1.15
Motor Phase:3 3
Motor Voltage:460 460 460 460
Motor Amperage:3.4 2.3 2.3 2.3
Fan RPM:742 726
Fan:
Supply Air
Opening Size K
No.Factor Velocity CFM Velocity CFM %Velocity CFM
1 20x20 2.78 1224 3400 1161 3225 95%1161 3225
Total 3400 3225 95%3225
Minimum Outside Air
Size K
Factor Velocity CFM Velocity CFM %Velocity CFM
45x25 7.81 19 150 20 156 104%32 250
Remarks:a)Traverse taken in a turbulent area.
b)
c)
d)
e)
Premier Test & Balance
2050
Technician:4/3/18
System Scheduled Data
Model number: 48LCE009A2A6-0R0A0 Serial number: 4117P01756
Manufacturer:Carrier Outlet Total CFM: 3,400
Total Design CFM:3,400 Min.Outside Air CFM: 150
Fan Static Pressure:1.0 ESP / 1.02 TSP Roof
Performance Data
Description Scheduled / Submittal Data Actual Field Measurements
Static Pressure Data
Component Static Pressure (inches of water)Pressure Pressure
In Out Rise / Drop Total (inches)
-0.11 0.49 Rise 0.60
Airflow Measurements
Area Design Final Reading Preliminary Reading
Served
Traverse
Design Final Reading Preliminary Reading
Total
TABB Certified "The Professional's Choice" Page 21
Air Handling Unit Test Data
Project:White House -Custom Colour
System:RTU-13 Premier Job Number:
Jaime Sevre Completion Date:
Equipment Location:
Motor RPM:1670 1670
Motor Hertz:60.0 60.0
Motor Service Factor:1.15 1.15
Motor Phase:3 3
Motor Voltage:460 460 460 460
Motor Amperage:3.4 2.1 2.1 2.1
Fan RPM:1441 1409
Fan:
Supply Air
Opening Size K
No.Factor Velocity CFM Velocity CFM %Velocity CFM
1 19x13 1.72 1166 2000 1135 1947 97%1135 1947
Total 2000 1947 97%1947
Minimum Outside Air
Size K
Factor Velocity CFM Velocity CFM %Velocity CFM
28x14 2.72 55 150 53 144 96%68 185
Remarks:a)Traverse taken in a turbulent area.
b)
c)
d)
e)
Premier Test & Balance
2050
Technician:4/3/18
System Scheduled Data
Model number: 48LCE006A2A6-0R0A0 Serial number: 4117C87707
Manufacturer:Carrier Outlet Total CFM: 2,000
Total Design CFM:2,000 Min.Outside Air CFM: 150
Fan Static Pressure:1.0 ESP / 1.12 TSP Roof
Performance Data
Description Scheduled / Submittal Data Actual Field Measurements
Static Pressure Data
Component Static Pressure (inches of water)Pressure Pressure
In Out Rise / Drop Total (inches)
-0.15 0.55 Rise 0.70
Airflow Measurements
Area Design Final Reading Preliminary Reading
Served
Traverse
Design Final Reading Preliminary Reading
Total
TABB Certified "The Professional's Choice" Page 22
Air Handling Unit Test Data
Project:White House -Custom Colour
System:RTU-14 Premier Job Number:
Jaime Sevre Completion Date:
Equipment Location:
Motor HP:5.00 5.00
Motor RPM:1755 1755
Motor Hertz:60.0 60.0
Motor Service Factor:1.15 1.15
Motor Phase:3 3
Motor Voltage:460 460 460 460
Motor Amperage:9.7 5.1 5.1 5.1
Motor BHP:4.73 2.63
Fan RPM:978 763
Fan:
Supply Air
Opening Size K
No.Factor Velocity CFM Velocity CFM %Velocity CFM
1 63x27 11.81 610 7200 623 7359 102%756 8930
Total 7200 7359 102%8930
Minimum Outside Air
Size K
Factor Velocity CFM Velocity CFM %Velocity CFM
59x23 9.42 58 550 57 537 98%73 688
Remarks:a)Traverse taken in a turbulent area.
b)
c)
d)
e)
Premier Test & Balance
2050
Technician:4/4/18
System Scheduled Data
Model number: 48LCE020A2A6-0R0A0 Serial number: 4217P16696
Manufacturer:Carrier Outlet Total CFM: 7,200
Total Design CFM:7,200 Min.Outside Air CFM: 550
Fan Static Pressure:1.0 ESP / 1.08 TSP Roof
Performance Data
Description Scheduled / Submittal Data Actual Field Measurements
Static Pressure Data
Component Static Pressure (inches of water)Pressure Pressure
In Out Rise / Drop Total (inches)
-0.14 0.47 Rise 0.61
Airflow Measurements
Area Design Final Reading Preliminary Reading
Served
Traverse
Design Final Reading Preliminary Reading
Total
TABB Certified "The Professional's Choice" Page 23
Air Handling Unit Test Data
Project:White House -Custom Colour
System:RTU-15 Premier Job Number:
Jaime Sevre Completion Date:
Equipment Location:
Motor HP:5.00 5.00
Motor RPM:1755 1755
Motor Hertz:60.0 60.0
Motor Service Factor:1.15 1.15
Motor Phase:3 3
Motor Voltage:460 460 460 460
Motor Amperage:9.7 5.0 5.0 5.0
Motor BHP:4.73 2.58
Fan RPM:978 778
Fan:
Supply Air
Opening Size K
No.Factor Velocity CFM Velocity CFM %Velocity CFM
1 63x27 11.81 610 7200 632 7466 104%765 9037
Total 7200 7466 104%9037
Minimum Outside Air
Size K
Factor Velocity CFM Velocity CFM %Velocity CFM
59x23 9.42 58 550 61 575 105%73 688
Remarks:a)Traverse taken in a turbulent area.
b)
c)
d)
e)
Total
Traverse
-0.14 0.43 Rise 0.57
Preliminary Reading
Design Final Reading Preliminary Reading
In Out Rise / Drop Total (inches)
Premier Test & Balance
2050
Technician:4/4/18
System Scheduled Data
Manufacturer:Carrier Outlet Total CFM: 7,200
Total Design CFM:7,200 Min.Outside Air CFM: 550
Fan Static Pressure:1.0 ESP / 1.08 TSP Roof
Model number: 48LCE020A2A6-0R0A0 Serial number: 4217P16695
Performance Data
Description Scheduled / Submittal Data Actual Field Measurements
Static Pressure Data
Component Static Pressure (inches of water)Pressure Pressure
Served
Airflow Measurements
Area Design Final Reading
TABB Certified "The Professional's Choice" Page 24
Fan Test Data
Project:White House -Custom Colour
System:MUA-1 Premier Job Number:
Jaime Sevre Completion Date:
Equipment Location:
Motor HP:5.00 5.00
Motor RPM:1725 1725
Motor Hertz:60.0 60.0
Motor Service Factor:1.15 1.15
Motor Phase:3 3
Motor Voltage:208 206 206 206
Motor Amperage:6.6 5.3 5.3 5.3
Motor BHP:2.68 3.98
Fan RPM:886 823
Fan:
Fan Total
Opening Size K
No.Factor Velocity CFM Velocity CFM %Velocity CFM
1 22x18 2.75 1818 5000 1934 5319 106%2132 5863
Total 5000 5319 106%5863
Remarks:a)Traverse taken in a turbulent area.
b)
c)
d)
e)
Premier Test & Balance
2050
Technician:4/4/18
System Scheduled Data
Model number: DG-115-H20 Serial number: 15220650
Manufacturer:Greenheck Outlet Total CFM: 5,000
Total Design CFM:5,000 Roof
Fan Static Pressure:0.25 ESP / 1.311 TSP
Performance Data
Description Scheduled / Submittal Data Actual Field Measurements
Static Pressure Data
Component Static Pressure (inches of water)Pressure Pressure
In Out Rise / Drop Total (inches)
-0.03 0.14 Rise 0.17
Airflow Measurements
Area Design Final Reading Preliminary Reading
Served
Traverse
TABB Certified "The Professional's Choice" Page 25
Fan Test Data
Project:White House -Custom Colour
System:EF-1 Premier Job Number:
Jaime Sevre Completion Date:
Equipment Location:
Motor HP:0.75 0.75
Motor RPM:1725 1725
Motor Hertz:60.0 60.0
Motor Service Factor:1.15 1.15
Motor Phase:1 1
Motor Voltage:120 120
Motor Amperage:10.1 9.4
Motor BHP:-0.70
Fan RPM:-1650
Fan:
Fan Total
Opening Size K
No.Factor Velocity CFM Velocity CFM %Velocity CFM
1 Flow Hood 1.00 210 210 228 228 109%195 195
2 Flow Hood 1.00 210 210 223 223 106%188 188
3 Flow Hood 1.00 75 75 76 76 101%92 92
4 Flow Hood 1.00 75 75 78 78 104%92 92
5 Flow Hood 1.00 280 280 302 302 108%380 380
6 Flow Hood 1.00 75 75 74 74 99%63 63
7 Flow Hood 1.00 280 280 273 273 98%420 420
8 Flow Hood 1.00 75 75 78 78 104%62 62
Total 1280 1332 104%1492
Remarks:a)
b)
c)
d)
e)
Premier Test & Balance
2050
Technician:4/4/18
System Scheduled Data
Model number: G-133-VG7X-QD Serial number: 15156579
Manufacturer:Greenheck Outlet Total CFM: 1,280
Total Design CFM:1,350 Roof
Fan Static Pressure:0.50
Performance Data
Description Scheduled / Submittal Data Actual Field Measurements
Static Pressure Data
Component Static Pressure (inches of water)Pressure Pressure
In Out Rise / Drop Total (inches)
-0.32 0.01 Rise 0.33
Airflow Measurements
Area Design Final Reading Preliminary Reading
Served
1st Level Womens
1st Level Mens
Next to Mens Bathroom
Across from Mens Bathroom
2nd Level Womens
Between Batrooms
2nd Level Mens
Next to Mens Bathroom
TABB Certified "The Professional's Choice" Page 26
Fan Test Data
Project:White House -Custom Colour
System:EF-2A Premier Job Number:
Jaime Sevre Completion Date:
Equipment Location:
Motor HP:Frac.Frac.
Motor RPM:1050 1050
Motor Hertz:60.0 60.0
Motor Service Factor:1.15 1.15
Motor Phase:1 1
Motor Voltage:120 118
Fan RPM:Direct Drive Direct Drive
Fan:
Fan Total
Opening Size K
No.Factor Velocity CFM Velocity CFM %Velocity CFM
1 Flow Hood 1.10 91 100 86 95 95%86 95
Total 100 95 95%95
Remarks:a)
b)
c)
d)
e)
Premier Test & Balance
2050
Technician:4/4/18
System Scheduled Data
Model number: Sig110 Serial number: 81B21H
Manufacturer:Delta Outlet Total CFM: 100
Total Design CFM:100 108
Fan Static Pressure:0.25
Performance Data
Description Scheduled / Submittal Data Actual Field Measurements
Static Pressure Data
Component Static Pressure (inches of water)Pressure Pressure
In Out Rise / Drop Total (inches)
Served
Women's Bathroom
-0.01 0.23 Rise 0.24
Airflow Measurements
Area Design Final Reading Preliminary Reading
TABB Certified "The Professional's Choice" Page 27
Fan Test Data
Project:White House -Custom Colour
System:EF-2B Premier Job Number:
Jaime Sevre Completion Date:
Equipment Location:
Motor HP:Frac.Frac.
Motor RPM:1050 1050
Motor Hertz:60.0 60.0
Motor Service Factor:1.15 1.15
Motor Phase:1 1
Motor Voltage:120 118
Fan RPM:Direct Drive Direct Drive
Fan:
Fan Total
Opening Size K
No.Factor Velocity CFM Velocity CFM %Velocity CFM
1 Flow Hood 1.10 91 100 92 101 101%92 101
Total 100 101 101%101
Remarks:a)
b)
c)
d)
e)
Served
Men's Bathroom
-0.01 0.21 Rise 0.22
Airflow Measurements
Area Design Final Reading Preliminary Reading
Description Scheduled / Submittal Data Actual Field Measurements
Static Pressure Data
Component Static Pressure (inches of water)Pressure Pressure
In Out Rise / Drop Total (inches)
Total Design CFM:100 123
Fan Static Pressure:0.25
Performance Data
System Scheduled Data
Model number: Sig110 Serial number: 81A16H
Manufacturer:Delta Outlet Total CFM: 100
Premier Test & Balance
2050
Technician:4/4/18
TABB Certified "The Professional's Choice" Page 28
For Office UyefC
o e Permit#: / (1C7 73
i C B B BE AGAN
/ 'C'')
��J
1
Permit Fee:
Staff:
3830 PILOT KNOB ROAD I EAGAN, MN 55122-1810 Payment Recvd: Yes No
(651)675-5675 I TDD: (651)454-8535 I FAX:(651)675-5694
Email:buildinginsoections(cr�citvofeagan.com I Plans: Electronic Paper
Plan Submittal: eplans(a�citvofeanan.com L
2018 COMMERCIAL PLUMBING PERMIT APPLICATION
❑ Please submit two(2)sets of paper plans with all commercial applications as well as an electronic set of the submittal,
submitted via email,CD or flash drive
/
Date: _ cc Site Address: d 50 �n (7 k c
/
Tenant: VLJ Ji` lo c ' C ( $1-0 (A Co ite#:
Property
Owner Name: Phone:
Name: a(}( ef y\ ./i1((`iflvj c.j License#:Q 700 5 0
Contractor Address: r ! ! S t'ff)CC°'• (ed City: �q,�� 1 State:k/VZip: 5 .5 (�p
Phone: 6r/ 74227c Email:s "C1- d , oy 1r> ty4
T e of Work ?C New _ Replacement Repair Rebuild Modify Space _Work in R.O.W.
yp
Description of work:
COMMERCIAL `F New Construction Modify Space / ii /77/6
S, Irrigation System( P' yes/ no)( )t RPZ/ PVB)
• Rain sensors required on irrigation systems /424-4_5-6‘,/(A2--(/de
Permit Type • Avg.GPM (2"turbo required unless smaller size allowed by Public Works)
_Meters Call(651)675-5646 to verity that tests passed prior to picking up meter.
Domestic:Size&Type Fire: 1
Avg.GPM High demand devices?_Yes_No Flushometers Yes_No
COMMERCIAL FEES Contract Value$ m 't x.01
$60.00 Permit Fee Minimum / O
00
$60.00 PVB/RPZ Permit(includes State Surcharge) $ (� Permit Fee
Surcharge=Contract Value x$0.0005 = Surcharge
If the project valuation is over$1 million,please call for Surcharge =$ TOTAL FEE
Following fees apply when installing a new lawn irrigation system $ (7 S`0 U Water Permit
Contact the City's Engineering Department,(651)675-5646,for required fee amounts. $ -376,o?) �'fi
$ Water Supply&Storage
$ State Surcharge
=$ T 95. CYD TOTAL FEE
You may subscribe to receive an electronic notification from the City of proposed ordinances by signing up for an email update on the City's website at
www,cityofeagan.comisubscri be.
CALL BEFORE YOU DIG. Call Gopher State One Call at(651)454-0002 for protection against underground utility damage.
I hereby acknowledge that this information is complete and accurate;that the work will be in conformance with the ordinances and codes of the City of Eagan;that I understand this is not a
permit,but only an application for a permit,and work is not to start without a permit;that the work will be in accordance with the approved plan in the c.n? .rk which requires a review
and approval of plans.
77��t
X (��tJ FCIge/4 x
Applicant's Printed Name App' ant's Signature
FOR OFFICE USE Approved By:. Date:
Required Inspections: Under Ground _ Rough-In Air Test Gas Test Final PRV Required: Yes %No
Meter Related Items: Meter Size Radio Read. Manometer Staff:
Page 1 of 3
Peggy Fleck /L79 ?
Ilitm: Abby Decker
t: Monday, March 12, 2018 2:55 PM
To: Peggy Fleck
Cc: Brent Massmann
Subject: irrigation meter 2840 Lone Oak Pkwy
Peggy,
White House Custom Color was approved by Brent for the following: