4000 Eagan Outlets Pkwy - Affinity at Eagan - Air Test & Balance Report 2018-07-02EQUIPMENT NAMEPLATE DATA 1988 1994 1668 1744 320 320 H CONDENSING UNIT DATA Daikin DX13SA0603 5 PHASE 3 SERIAL # 1803016975 DIFFUSERS AND GRILLES Supply 1 register 14x8 284 454 290 102% 2 ““284 315 282 99% 3 ““284 313 282 99% 4 ““284 333 284 100% 5 ““284 361 285 100% 6 ““284 325 288 101% 7 ““284 367 283 100% Return 1 grill 24x30 1668 1744 105% REMARKS © 2006 NCI, Inc.AB210-10/06 AIR TEST AND BALANCE REPORT 2-Jul-2018 FAN DESIGN ACTUALMANUFACTURERDaikin Affinity at Eagan MODEL DM92SS120SDNA SUPPLY AIR CFM TYPE furnace RETURN AIR CFM EQUIPMENT #F-12 OUTSIDE AIR CFM SERIAL NUMBER 1803037246 FAN SPEED (L/M/H) Final CFM % of Design READINGS BY Brandon Fowler Room Outlet Number Type Size Required CFM Test 1 J-Berd Mechanical Contractors, Inc.MANUFACTURER MODEL TONNAGE DATE 3308 Southway DriveSaint Cloud, MN 56301PHONE (320) 656-0847 FAX (320) 656-0847PROJECT EQUIPMENT NAMEPLATE DATA 1538 1549 1218 1340 320 320 H CONDENSING UNIT DATA Daikin DX13SA0603 5 PHASE 3 SERIAL # 1803016568 DIFFUSERS AND GRILLES Supply 1 register 14x8 272 520 276 101% 2 ““272 550 273 100% 3 ““272 549 271 100% 4 ““272 435 274 101% 5 “12x6 150 356 152 101% 6 “12x6 150 243 151 101% 7 “12x6 150 361 152 101% #VALUE! Return 1 grill 24x30 1218 1340 110% REMARKS © 2006 NCI, Inc.AB210-10/06 AIR TEST AND BALANCE REPORT 2-Jul-2018 FAN DESIGN ACTUALMANUFACTURERDaikin Affinity at Eagan MODEL DM92SS1205DNA SUPPLY AIR CFM TYPE furnace RETURN AIR CFM EQUIPMENT #F-11 OUTSIDE AIR CFM SERIAL NUMBER 1803037236 FAN SPEED (L/M/H) Final CFM % of Design READINGS BY Brandon Fowler Room Outlet Number Type Size Required CFM Test 1 J-Berd Mechanical Contractors, Inc.MANUFACTURER MODEL TONNAGE DATE 3308 Southway DriveSaint Cloud, MN 56301PHONE (320) 656-0847 FAX (320) 656-0847PROJECT EQUIPMENT NAMEPLATE DATA 1988 1971 1668 1615 320 320 H CONDENSING UNIT DATA Daikin DX13SA0603 5 PHASE 3 SERIAL # 1803016964 DIFFUSERS AND GRILLES Supply 1 register 14x8 284 388 284 100% 2 ““284 270 277 98% 3 ““284 257 272 96% 4 ““284 299 289 102% 5 ““284 318 283 100% 6 ““284 300 286 101% 7 ““284 334 280 99% Return 1 grill 24x30 1668 1615 97% REMARKS © 2006 NCI, Inc.AB210-10/06 AIR TEST AND BALANCE REPORT 2-Jul-2018 FAN DESIGN ACTUALMANUFACTURERDaikin Affinity at EaganMODELDM92SS1205DNASUPPLY AIR CFM TYPE furnace RETURN AIR CFM EQUIPMENT #F-10 OUTSIDE AIR CFM SERIAL NUMBER 1803037237 FAN SPEED (L/M/H) Final CFM % of Design READINGS BY Brandon Fowler Room Outlet Number Type Size Required CFM Test 1 J-Berd Mechanical Contractors, Inc.MANUFACTURER MODEL TONNAGE DATE 3308 Southway DriveSaint Cloud, MN 56301PHONE (320) 656-0847 FAX (320) 656-0847PROJECT EQUIPMENT NAMEPLATE DATA 1988 1952 1638 1578 350 350 H CONDENSING UNIT DATA Daikin DX13SA0603 5 PHASE 3 SERIAL # 1803016816 DIFFUSERS AND GRILLES Supply 1 register 14x8 284 419 285 100% 2 ““284 267 278 98% 3 ““284 245 258 91% 4 ““284 304 287 101% 5 ““284 244 270 95% 6 ““284 304 288 101% 7 ““284 305 286 101% Return 1 grill 24x30 1638 1578 96% REMARKS © 2006 NCI, Inc.AB210-10/06 AIR TEST AND BALANCE REPORT 2-Jul-2018 FAN DESIGN ACTUALMANUFACTURERDaikin Affinity at Eagan MODEL DM92SS12050NA SUPPLY AIR CFM TYPE Furnace RETURN AIR CFM EQUIPMENT #F-9 OUTSIDE AIR CFM SERIAL NUMBER 1803037251 FAN SPEED (L/M/H) Final CFM % of Design READINGS BY Brandon Fowler Room Outlet Number Type Size Required CFM Test 1 J-Berd Mechanical Contractors, Inc.MANUFACTURER MODEL TONNAGE DATE 3308 Southway DriveSaint Cloud, MN 56301PHONE (320) 656-0847 FAX (320) 656-0847PROJECT EQUIPMENT NAMEPLATE DATA 1988 1983 1623 1632 360 360 H CONDENSING UNIT DATA Daikin DX13SA0603 5 PHASE 3 SERIAL # 1803017085 DIFFUSERS AND GRILLES Supply 1 register 14x8 257 354 250 97% 2 ““257 498 253 98% 3 ““257 349 257 100% 4 ““257 240 251 98% 5 ““240 312 248 103% 6 ““240 333 236 98% 7 ““240 261 243 101% 8 ““240 276 245 102% Return 1 grill 24x30 1623 1532 1632 101% REMARKS © 2006 NCI, Inc.AB210-10/06 AIR TEST AND BALANCE REPORT FAN DESIGN ACTUALMANUFACTURERDaikin MODEL Dm92SS1205DN SUPPLY AIR CFM TYPE Furnace RETURN AIR CFM EQUIPMENT #F-8 OUTSIDE AIR CFM SERIAL NUMBER 1803037239 FAN SPEED (L/M/H) Final CFM % of Design READINGS BY Room Outlet Number Type Size Required CFM Test 1 J-Berd Mechanical Contractors, Inc.MANUFACTURER MODEL TONNAGE DATE 3308 Southway DriveSaint Cloud, MN 56301PHONE (320) 656-0847 FAX (320) 656-0847PROJECT EQUIPMENT NAMEPLATE DATA 1200 1165 1060 1032 140 140 H CONDENSING UNIT DATA Daikin Dx13SN0361 3 PHASE single SERIAL # 1601016374 DIFFUSERS AND GRILLES Supply 1 register 14x8 300 411 299 100% 2 ““300 310 304 101% 3 ““300 238 275 92% 4 ““300 280 287 96% Return 1 grill 24x30 1060 1032 1032 97% REMARKS © 2006 NCI, Inc.AB210-10/06 AIR TEST AND BALANCE REPORT 2-Jul-2018 FAN DESIGN ACTUALMANUFACTURERDaikin affinity at eaganMODELDM92SS0803BNSUPPLY AIR CFM TYPE Furnace RETURN AIR CFM EQUIPMENT #F-4 OUTSIDE AIR CFM SERIAL NUMBER 1802278431 FAN SPEED (L/M/H) Final CFM % of Design READINGS BY Brandon fowler Room Outlet Number Type Size Required CFM Test 1 J-Berd Mechanical Contractors, Inc.MANUFACTURER MODEL TONNAGE DATE 3308 Southway DriveSaint Cloud, MN 56301PHONE (320) 656-0847 FAX (320) 656-0847PROJECT EQUIPMENT NAMEPLATE DATA 1600 1641 1360 1450 240 240 H CONDENSING UNIT DATA Daikin DX13SN0481 4 PHASE single SERIAL # 1711355207 DIFFUSERS AND GRILLES Supply 1 register 14x8 250 238 240 96% 2 ““250 258 258 103% 3 ““250 317 257 103% 4 ““250 357 265 106% 5 “12x6 200 297 201 101% 6 ““200 226 206 103% 7 ““200 222 214 107% Return 1 grill 24x30 1360 1509 1450 107% REMARKS © 2006 NCI, Inc.AB210-10/06 AIR TEST AND BALANCE REPORT FAN DESIGN ACTUALMANUFACTURERDaikin affinity at eaganMODELDM92SS1004CNAASUPPLY AIR CFM TYPE Furnace RETURN AIR CFM EQUIPMENT #F-3 OUTSIDE AIR CFM SERIAL NUMBER 1803364431 FAN SPEED (L/M/H) Final CFM % of Design READINGS BY Brandon Fowler Room Outlet Number Type Size Required CFM Test 1 J-Berd Mechanical Contractors, Inc.MANUFACTURER MODEL TONNAGE DATE 3308 Southway DriveSaint Cloud, MN 56301PHONE (320) 656-0847 FAX (320) 656-0847PROJECT EQUIPMENT NAMEPLATE DATA 1596 1632 1356 1260 240 240 H H CONDENSING UNIT DATA Daikin DX13SN0481 4 PHASE single SERIAL # 1711355190 DIFFUSERS AND GRILLES Supply 1 register 14x8 266 410 276 104% 2 ““266 271 277 104% 3 ““266 344 271 102% 4 ““266 296 277 104% 5 ““266 350 289 109% 6 ““266 170 242 91% Return 1 grill 24x30 1356 1260 1260 93% REMARKS © 2006 NCI, Inc.AB210-10/06 AIR TEST AND BALANCE REPORT 2-Jul-2018 FAN DESIGN ACTUALMANUFACTURERDaikin affinity at eagan MODEL DM92SS1004CNAASUPPLY AIR CFM TYPE Furnace RETURN AIR CFM EQUIPMENT #F-2 OUTSIDE AIR CFM SERIAL NUMBER 1711593340 FAN SPEED (L/M/H) Final CFM % of Design READINGS BY Brandon Fowler Room Outlet Number Type Size Required CFM Test 1 J-Berd Mechanical Contractors, Inc.MANUFACTURER MODEL TONNAGE DATE 3308 Southway DriveSaint Cloud, MN 56301PHONE (320) 656-0847 FAX (320) 656-0847PROJECT EQUIPMENT NAMEPLATE DATA 1990 1873 1700 1850 290 290 H H CONDENSING UNIT DATA Daikin DX13SA0603 5 PHASE 3 SERIAL # 1803017080 DIFFUSERS AND GRILLES Supply 1 grill 14x8 225 192 204 91% 2 ““225 260 230 102% 3 ““225 288 224 100% 4 ““225 309 229 102% 5 “12x6 180 163 173 96% 6 ““150 218 157 105% 7 ““150 236 155 103% 8 ““150 214 158 105% 9 ““150 233 151 101% 10 ““140 207 142 101% 11 diffuser 4 45 50 50 111% Return 1 grill 24x30 1700 1900 1850 109% REMARKS © 2006 NCI, Inc.AB210-10/06 AIR TEST AND BALANCE REPORT 7-2-18 FAN DESIGN ACTUALMANUFACTURERDaikin Affinity at EaganMODELDM92SS1205DNAASUPPLY AIR CFM TYPE Furnace RETURN AIR CFM EQUIPMENT #F-1 OUTSIDE AIR CFM SERIAL NUMBER 1803037258 FAN SPEED (L/M/H) Final CFM % of Design READINGS BY Brandon Fowler Room Outlet Number Type Size Required CFM Test 1 J-Berd Mechanical Contractors, Inc.MANUFACTURER MODEL TONNAGE DATE 3308 Southway DriveSaint Cloud, MN 56301PHONE (320) 656-0847 FAX (320) 656-0847PROJECT