Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
980 Discovery Rd - Proozy Test & Balance Reports 2018-09-19
Jeff Mediger Date Tested September 14, 2018 Test and Balance Report Proozy Eagan, MN Tested By Unit Number: Unit Manufacture: Unit Model: AREA Outlet Diffuser Neck DESIGN Actual Percent of SERVED Number TYPE SIZE CFM CFM Required 104 1 Lay-in 10 250 240 96% 101 1 slot 8 80 75 94% 100 1 lay-in 6 205 200 98% 132 1 slot 8 205 205 100% 131 1 slot 8 205 200 98% 130 1 slot 8 205 210 102% 129 1 slot 8 205 210 102% 128 1 slot 8 205 205 100% 127 1 slot 8 205 200 98% 125 1 slot 8 230 235 102%#DIV/0! 1995 1980 99% Goodman CPG060 Totals Proozy Eagan, MN September 14, 2018 RTU1 REMARKS: OA set for 10% minimum Unit Number: Unit Manufacture: Unit Model: AREA Outlet Diffuser Neck DESIGN Actual Percent of SERVED Number TYPE SIZE CFM CFM Required 102 1 Lay-in 10 270 275 102% 102 2 Lay-in 10 270 275 102% 103 1 Lay-in 8 140 135 96% 105 1 Lay-in 6 100 95 95% 106 1 Lay-in 6 100 95 95% 107 1 Lay-in 6 100 100 100% 119 1 Reg 14/6 250 255 102% 119 2 Reg 14/6 250 260 104% 119 3 Reg 14/6 250 255 102% 119 4 Reg 14/6 250 240 96% 1980 1985 100% Daikin DCG060 Proozy Eagan, MN September 14, 2018 RTU2 Totals REMARKS: OA set for 10% Minimum Unit Number: Unit Manufacture: Unit Model: AREA Outlet Diffuser Neck DESIGN Actual Percent of SERVED Number TYPE SIZE CFM CFM Required West 117 1 Reg 14/6 290 285 98% West 117 2 Reg 14/6 290 290 100% West 117 3 Reg 14/6 290 280 97% West 117 4 Reg 14/6 290 285 98% West 117 5 Reg 14/6 290 290 100% West 117 6 Reg 14/6 290 295 102% 123 1 Lay-in 6 80 85 106% RR Hall 1 Lay-in 6 80 85 106% Vestibule 124 1 Lay-in 6 75 75 100% 1975 1970 100% Goodman CPG060 Proozy Eagan, MN September 14, 2018 RTU3 Totals REMARKS: OA set for 20% for health club occupancy at 20 cfm PP and .06 SF - 400 cfm Unit Number: Unit Manufacture: Unit Model: AREA Outlet Diffuser Neck DESIGN Actual Percent of SERVED Number TYPE SIZE CFM CFM Required 119 1 Reg 14/6 250 255 102% 119 2 Reg 14/6 250 260 104% 119 3 Reg 14/6 250 250 100% 119 4 Reg 14/6 250 255 102% 119 5 Reg 14/6 260 255 98% 119 6 Reg 14/6 260 250 96% 112 1 Reg 14/6 260 265 102% 112 2 Reg 14/6 260 260 100% 112 3 Reg 14/6 260 250 96% 113 1 Lay-in 10 250 245 98% 113 2 Lay-in 10 250 240 96% 115 1 Lay-in 6 75 80 107% 116 1 Lay-in 6 75 75 100% 2950 2940 100%Totals Bryant 581JP08D180 Proozy Eagan, MN September 14, 2018 RTU4 REMARKS: OA set for 10% Unit Number: Unit Manufacture: Unit Model: AREA Outlet Diffuser Neck DESIGN Actual Percent of SERVED Number TYPE SIZE CFM CFM Required East 117 1 Reg 14/8 420 415 99% East 117 2 Reg 14/8 420 425 101% East 117 3 Reg 14/8 420 420 100% East 117 4 Reg 14/8 420 430 102% East 117 5 Reg 14/8 420 425 101% East 117 6 Reg 14/8 420 410 98% East 117 7 Reg 14/8 420 405 96% East 117 8 Reg 14/8 420 420 100% Vetibule 1 Lay-in 6 50 50 100% 3410 3400 100%Totals Bryant 581JP09D180 Proozy Eagan, MN September 14, 2018 RTU5 REMARKS: OA set for 20% heath club occupancy 20 cfm PP and .06 SF - 680 CFM OA