2685 Vikings Cir - USTA HVAC T&B Report 2020-04-231111 Fax (763) 657-0587 HVAC TESTING & BALANCING REPORT USTA NORTHERN TENANT BUILDOUT EGAN Test & Balance Associates, Inc. 7308 Aspen Lane, Suite 110 Brooklyn Park, MN 55428-1006 Phone (763) 657-0159 Cell (612) 272-5651 Test & Balance Associates, Inc. 7308 Aspen Lane, Suite 110 Brooklyn Park, MN 55428 Phone: (763) 657-0159 Fax: (763) 657-0587 Cell: (612) 272-5651 CERTIFIED TEST; ADJUST; BALANCE REPORT # DATE PROJECT ADDRESS ENGINEER HVAC CONTRACTOR NEBB TAB FIRM NEBB TAB SUPERVISOR CERTIFICATION NUMBER 3242 Apr 2020 USTA NORTHERN TENANT BUILDOUT Test & Balance Associates, Inc. Donald J. Henderson MASTER MECHANICAL, INC. (651) 905-1600 MASTER MECHANICAL, INC. (651) 905-1600 2685 VIKING CIRCLE, SUITE 100 EGAN MN Test & Balance Associates, Inc. 7308 Aspen Lane, Suite 110 Brooklyn Park, MN 55428 Phone: (763) 657-0159 Fax: (763) 657-0587 1112 PROJECT ADDRESS THE DATA PRESENTED IN THIS REPORT IS A RECORD OF SYSTEM MEASUREMENTS AND FINAL ADJUSTMENTS THAT HAVE BEEN OBTAINED IN ACCORDANCE WITH THE CURRENT EDITION OF THE NEBB PROCEDURAL STANDARDS FOR TESTING, ADJUSTING, AND BALANCING OF ENVIRONMENTAL SYSTEMS. ANY VARIANCES FROM DESIGN QUANTITIES, WHICH EXCEED NEBB TOLERANCES, ARE NOTED IN THE TEST - ADJUST - BALANCE REPORT PROJECT SUMMARY. SUBMITTED & CERTIFIED BY: NEBB TAB FIRM NEBB TAB SUPERVISOR REG. NO. SIGNATURE DATE CERTIFICATION EXPIRATION DATE CERTIFICATION REPORT USTA NORTHERN TENANT BUILDOUT 2685 VIKING CIRCLE, SUITE 100 EGAN MN Apr 2020 Test & Balance Associates, Inc. Donald J. Henderson 3242 3/31/22 Test & Balance Associates, Inc. 7308 Aspen Lane, Suite 110 Brooklyn Park, MN 55428 Phone: (763) 657-0159 Fax: (763) 657-0587 PROJECT:4940 - USTA NORTHERN TENANT BUILDOUT Project Notes and Summary. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . MULTI AIR DISTRIBUTION SYSTEM EXISTING AHU. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . MULTI AIR DISTRIBUTION SYSTEM EXISTING AHU. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . FLOW FITTING REPORT SYSTEM EXISTING HEATING WATER. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Instrument Calibration Report. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Symbol Report. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Symbol Report. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Symbol Report. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Symbol Report. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 7 8 9 TABLE OF CONTENTS 1 2 3 4 5 Test & Balance Associates, Inc. 7308 Aspen Lane, Suite 110 Brooklyn Park, MN 55428 Phone: (763) 657-0159 Fax: (763) 657-0587 1115 PROJECT:4940 - USTA NORTHERN TENANT BUILDOUT DESCRIPTION:EXECUTIVE SUMMARY PROJECT NOTES AND SUMMARY REPORT PAGE:1 of 9 TEST DATE:Apr 2020 THE SCOPE OF THE TESTING AND BALANCING WAS TO MEASURE AND ADJUST THE SUPPLY CFM TO MEET DESIGN AS LISTED ON THE MECHANICAL DRAWINGS DATED 02/03/2020. THE FANS WERE OPERATING UNDER NORMAL CONDITIONS IN THE OCCUPIED MODE. 1116 PAGE: 2 of 9 PROJECT: USTA NORTHERN TENANT BUILDOUT DATE: Apr 2020 SYSTEM: EXISTING AHU TECH: BRIAN STOUT DESIGN PRELIMINARY FINAL NO.SIZE FACTOR VEL CFM VEL CFM VEL CFM FPVAV-1 10 100 1 8 HOOD --150 --164 100 2 8 HOOD --150 --170 101 3 8 HOOD --150 --161 101 4 8 HOOD --150 --168 101 5 8 HOOD --150 --174 101 6 8 HOOD --150 --171 101 7 8 HOOD --150 --167 MAXIMUM CFM 10 0.545 1927 1050 1938 1056 MINIMUM CFM 10 0.545 578 315 587 320 FAN CFM 735 855* FLOW FACTOR 2.04 FPVAV-2 8 108 1 8 HOOD --200 --218 108 2 8 HOOD --200 --208 MAXIMUM CFM 8 0.349 1146 400 1153 402 MINIMUM CFM 8 0.349 344 120 344 120 FAN CFM 400 306 FLOW FACTOR 1.96 VAV-1 8 103 1 6 HOOD --95 --87 103 2 6 HOOD --95 --90 104 3 6 HOOD --95 --99 105 4 6 HOOD --70 --75 MAXIMUM CFM 355 351 MINIMUM CFM 107 110 FLOW FACTOR 2.15 *FAN ON LOW SPEED. AREA SERVED OPENING TEST & BALANCE ASSOCIATES, INC. AIR DISTRIBUTION REPORT 1117 PAGE: 3 of 9 PROJECT: USTA NORTHERN TENANT BUILDOUT DATE: Apr 2020 SYSTEM: EXISTING AHU TECH: BRIAN STOUT DESIGN PRELIMINARY FINAL NO.SIZE FACTOR VEL CFM VEL CFM VEL CFM VAV-2 8 100 1 8 HOOD --200 --214 100 2 8 HOOD --200 --189 MAXIMUM CFM 400 403 MINIMUM CFM 120 126 FLOW FACTOR 2.25 2.31 VAV-3 10 101 1 8 HOOD --200 --185 101 2 8 HOOD --200 --213 101 3 8 HOOD --200 --200 106 4 8 HOOD --200 --189 107 5 8 HOOD --120 --115 MAXIMUM CFM 920 980 902 MINIMUM CFM 276 278 FLOW FACTOR 2.25 1.97 AREA SERVED OPENING TEST & BALANCE ASSOCIATES, INC. AIR DISTRIBUTION REPORT 1118 UNIT TYPE LOCATION FLOW FITTING SIZE SETTING DESIGN GPM FINAL P.D. FINAL GPM NOTES FPVAV-1 101 3/4 44 1.06 20.2 1.1 FPVAV-2 101 1/2 40 .40 17.0 .55 LOWEST SETTING SYSTEM: EXISTING HEATING WATER DATE: Apr 2020 TEST & BALANCE ASSOCIATES, INC. FLOW FITTING REPORT PROJECT: USTA NORTHERN TENANT BUILDOUT PAGE: 4 of 9 TECHNICIAN: BRIAN STOUT NOTE: *FLOW FITTING MAUNFACTURER IS BELL & GOSSETT. PRESSURE DROP IN FEET OF WATER. FTR 100 3/4 30 2.0 15.9 2.1 FTR 100 3/4 30 2.0 15.1 2.0 Test & Balance Associates, Inc. 7308 Aspen Lane, Suite 110 Brooklyn Park, MN 55428 Phone: (763) 657-0159 Fax: (763) 657-0587 1113 PROJECT:4940 - USTA NORTHERN TENANT BUILDOUT REMARKS: MANUFACTURER MODEL SERIAL 5/1/2019 Shortridge Inst. INSTRUMENT CALIBRATION REPORT ADM-880C M10336 11/13/2019 Alnor HM670 71139142 Apr 2020 PAGE:5 of 9 APPLICATION AIR PRESSURE/VOLUME HYDRONIC CALIBRATION DATE Test & Balance Associates, Inc. 7308 Aspen Lane, Suite 110 Brooklyn Park, MN 55428 Phone: (763) 657-0159 Fax: (763) 657-0587 PROJECT:USTA NORTHERN TENANT BUILDOUT SYMBOL DESCRIPTION SYMBOL DESCRIPTION A/C Air Conditioning(er)CLG Ceiling A/AMP Ampere COM Common AC Alternating Current COMP Compressor Unit AD Access Door CONFIG Configuration ADJ Adjustable CONV Convector ADM Airdata Multimeter CP Condenser Pump AF Air Filter/Airfoil CPS Cycles Per Second AFMS Airflow Measuring Station CR Condenser Water Return AHU Air Handling Unit CS Condenser Water Supply ALT Alternate CT Cooling Tower AMB Ambient CUH Cabinet Unit Heater AP Access Panel CWR Chilled Water Return AUTO Automatic CWS Chilled Water Supply BAL Balancing DB Dry Bulb BBR Baseboard Radiation DC Direct Current BC Balancing Cock DDC Direct Digital Control BHP Break Horse Power DEG Degree BI Backward Inclined DH Duct Heater BLDG Building DIA Diameter BRG Bearing DIAG Diagonal BTU British Thermal Unit DIFF Diffuser BTUH BTU Per Hour DISCH Discharge C Condenser Water DISTR Distribution CD Ceiling Diffuser DM Damper Motor CENT Centrifugal DMPR Damper CF Cubic Feet DN Down CFH Cubic Feet Per Hour DPS Diff. Pressure Switch CFM Cubic Feet Per Minute DX Coil Direct Expansion Coil CKT Circuit E East CL Centerline EA Exhaust Air 6 of 9 ABBREVIATIONS PAGE ONE Test & Balance Associates, Inc. 7308 Aspen Lane, Suite 110 Brooklyn Park, MN 55428 Phone: (763) 657-0159 Fax: (763) 657-0587 PROJECT:USTA NORTHERN TENANT BUILDOUT SYMBOL DESCRIPTION SYMBOL DESCRIPTION EAT Entering Air Temperature GEN General EDH Electric Duct Heater GF Gas Furnace EF Exhaust Fan GHR Glycol-water Heating Return EFF Efficiency GHS Glycol-water Heating Supply ENT Entering GPH Gallons Per Hour EQUIP Equipment GPM Gallons Per Minute ER Exhaust Register GR Grille ESP External Static Pressure H Height EST Estimate HD Head EWT Entering Water Temperature HOA Hand off Automatic EXH Exhaust HORIZ Horizontal EXIST Existing HP Heat Pump/Horsepower EXT Exterior HR Hour F Fahrenheit/Furnace HT Height FA Fresh Air HTG Heating FC Forward Curved HTR Heater FCU Fan Coil Unit HV Heating Ventilating Unit FD Fire Damper HVAC Heating Ventilating and Air Conditioning FIG Figure HWR Heating Hot Water Return FME Flow Measuring Equipment HWS Heating Hot Water Supply FMS Flow Measuring Station HX Heat Exchanger FPM Feet Per Minute HZ Hertz FPS Feet Per Second ID Inside Diameter FSD Fire/Smoke Damper IH Intake Hood FT Feet (Foot)INT Interior; Internal FTR Finned Tube Radiation IN Inch GA Gauge KH Kitchen Hood GAL Gallon KHE Kitchen Hood Exhaust Fan 7 of 9 ABBREVIATIONS PAGE TWO Test & Balance Associates, Inc. 7308 Aspen Lane, Suite 110 Brooklyn Park, MN 55428 Phone: (763) 657-0159 Fax: (763) 657-0587 PROJECT:USTA NORTHERN TENANT BUILDOUT SYMBOL DESCRIPTION SYMBOL DESCRIPTION KHS Kitchen Hood Supply Fan N North KIT Kitchen N/A Not Applicable KV Kilovolt NC Normally Closed KVA Kilovolt Amperes NEMA National Electrical-Manufacturers Assn. KW Kilowatt NIC Not In Contract KWH Kilowatt Hour NO Normally Open/Number LAB Laboratory OA Outside Air LAT Leaving Air Temperature OBD Opposed Blade Damper LB/LBS Pound/Pounds OC On Center LF Linear Foot OD Outside Diameter LIN Linear P/T Pressure/Temp. Test Port LVG Leaving P Pump LWT Leaving Water Temp.PCF Pounds Per Cubic Foot MA Mixed Air PD Pitch Diameter MAN Manual PD Pressure Drop MAU Makeup Air Unit PE Pneumatic Electric MAV Manual Air Vent PF Power Factor MAX Maximum PG Pressure Gage MBH/MBTUH Thousand BTU Per Hour PH Phase MVD Manual Volume Damper PNEU Pneumatic MECH Mechanical PROP Propeller MEZZ Mezzanine PRV Pressure Reducing Valve MHWR Med Temp Heating Water Return PRV Power Roof Ventilation MHWS Med Temp Heating Water Supply PSF Pounds Per Sq. Ft. MIN Minimum PSI Pounds Per Sq. Inch MISC Miscellaneous PSIA Pounds Per Square Inch Absolute 8 of 9 ABBREVIATIONS PAGE THREE Test & Balance Associates, Inc. 7308 Aspen Lane, Suite 110 Brooklyn Park, MN 55428 Phone: (763) 657-0159 Fax: (763) 657-0587 PROJECT:USTA NORTHERN TENANT BUILDOUT SYMBOL DESCRIPTION SYMBOL DESCRIPTION PSIG Pounds Per Square Inch Gauge TEMP Temperature PWR Power TF Transfer Fan RA Return Air TFSP Total Fan Static Pressure RAD or R Radius TONS Tons of Air Conditioning RAT Return Air Temperature TS Temperature Sensor REG Register TSP Total Static Pressure RF Return Fan UH Unit Heater RH Relative Humidity UV Unit Ventilator RH Relief Hood V Volt RHC Reheat Coil VAV Variable Air Volume RPM Revolutions Per Minute VEL Velocity RTU Rooftop Unit VENT Ventilation S Sensor/South VERT Vertical SA Supply Air VFD Variable Frequency Drive SAT Supply Air Temperature VM Voltmeter SD Smoke Damper VOL Volume SENS Sensible VSMC Variable Speed Motor Controller SF Square Foot/Supply Fan W West SP Static Pressure WB Wet Bulb SPL Sound Pressure Level WFMD Water Flow Measuring Device SQ Square WT Weight SUC Suction YD Yard T/T-STAT Thermostat &And TA Transfer Air @ At TB Terminal Box #Number TC Temperature Control + Plus/Positive TD Temperature Differential -Minus/Negative 9 of 9 ABBREVIATIONS PAGE FOUR