2737 West Service Rd - Test & Balance ReportTest and Balance Report Ultra- Lox (office buildout) Eagan, MN Date Tested Dec 19-2020 The following pages containg the detailed test and data for the system (s) tested, if there are any questions please call, Kenny 952-994-7970 Prepaired For: Centraire Heating and Air Conditioining 6811 Washington Ave South Edina, MN 55439 ULTRA LOX- OFFICE BUILDOUT 2737 WEST SERVICE ROAD EAGEN, MN Unit Manufacture Model Total CFM Fan RPM Motor RPM Motor Volts Motor Amps Horsepower O.A. Damper CFM RTU-1 CARRIER 48FCM07 2,400 1680 1628 208/3 4.0 3/4 350 RTU-2 CARRIER 48FCA05 1,600 1550 1500 20/3 3.0 1/2 250 RTU-1 15% outside fresh air motor locked, RTU-2 15% outside fresh air motor locked, RTU-3 15% outside fresh air motor locked, RTU-4 15% outside fresh air motor locked, RTU-3 RTU-4 CARIER CARRIER 48FCA05 48FCM07 1,600 2,400 1550 1680 1500 1628 208/3 208/3 3.0 4.0 1/2 3/4 250 350 enthalpy control enthalpy control enthalpy control enthalpy control STANDARD THERMOSTATS WITH NO SPACE SENSORS. Unit Number: PRV-1 Unit Manufacture: ACME - Unit Model: ACS102 AREA SERVED Outlet Number Diffuser TYPE Neck SIZE DESIGN CFM Actual CFM Percent of Required BATH-1 1 DROP 6" 200 200 100% BATH-1 2 DROP 6" 200 190 90% BATH-2 3 DROP 6" 200 200 100% BATH-2 4 DROP 6" 200 200 100% Totals 800 790 95% PRV FAN IS TIED WITH LIGHT SWITCH, RUNS ALL TIMES WHEN LIGHTS ARE ON NOTE- TIME OF TESTING HAD TO TEMP WIRE THE PRV FAN AS IT WAS NOT WIRED AT THIS TIME. CURB ADAPTER WITH BACKDRAFT DAMPER INSTALLED ALL DUCTS SEALED WITH WATER BASED SEALENT Unit Number: RTU-1 Unit Manufacture: CARRIER Unit Model: 48FCM07 AREA SERVED Outlet Number Diffuser TYPE Neck SIZE DESIGN CFM Actual CFM Percent of Required CONF 1 LAYIN 8" 300 310 105% CONF 2 LAYIN 8" 300 280 90% OFFICE 3 LAYIN 8" 300 300 100% OFFICE 4 LAYIN 8" 300 275 85% OFFICE 5 LAYIN 8" 300 300 100% OFFICE 6 LAYIN 8" 300 300 100% OFFICE 7 LAYIN 8" 300 290 95% OFFICE 8 LAYIN 8" 300 295 97% Totals 2400 2350 95% NOTE- PACKAGED CARRIER RTU, ECONOMIZER SET AT 15% OUTISIDE AIR WITH ENTHALPY CONTROL. SMOKE DETECTOR LOCATED IN ECONOMIZER. Unit Number: RTU-2 Unit Manufacture: CARRIER Unit Model: 48FCA05 AREA SERVED Outlet Number Diffuser TYPE Neck SIZE DESIGN CFM Actual CFM Percent of Required BREAK 1 LAYIN 8" 250 260 105% BREAK 2 LAYIN 8" 250 280 90% CUBICLE 3 LAYIN 8" 250 250 100% CUBICLE 4 LAYIN 8" 250 225 85% CUBICLE 5 LAYIN 8" 250 240 90% CUBICLE 6 LAYIN 8" 250 250 100% Totals 1600 1505 92% NOTE- ECONOMIZER LOCKED AT 15% WITH ENTHALPY CONTROL SMOKE DETECTOR LOCATED IN R/A BY ECONOMIZER. STANDA ALONE THERMOSTAT Unit Number: RTU-3 Unit Manufacture: CARRIER Unit Model: 48FCA05 AREA SERVED Outlet Number Diffuser TYPE Neck SIZE DESIGN CFM Actual CFM Percent of Required BATH 1 LAYIN 8" 230 230 105% BATH 2 LAYIN 8" 230 220 90% CUBICLE 3 LAYIN 8" 230 250 100% CUBICLE 4 LAYIN 8" 230 225 95% CUBICLE 5 LAYIN 8" 230 240 105% CUBICLE 6 LAYIN 8" 230 230 100% BATH 7 LAYIN 6" 230 200 80% Totals 1600 1595 98% NOTE- ECONOMIZER LOCKED AT 15% WITH ENTHALPY CONTROL SMOKE DETECTOR LOCATED IN R/A BY ECONOMIZER. STAND A -LONE THERMOSTAT HONEYWELL. Unit Number: RTU-4 Unit Manufacture: CARRIER Unit Model: 48FCM07 AREA SERVED Outlet Number Diffuser TYPE Neck SIZE DESIGN CFM Actual CFM Percent of Required COPY 1 LAYIN 8" 250 310 105% COMMON 2 LAYIN 8" 250 280 90% OFFICE 3 LAYIN 8" 250 300 100% OFFICE 4 LAYIN 8" 250 275 85% OFFICE 5 LAYIN 8" 250 300 100% OFFICE 6 LAYIN 8" 250 300 100% OFFICE 7 LAYIN 8" 250 290 95% OFFICE 8 LAYIN 8" 300 295 97% COMON 9 LAYIN 8" 300 280 90% Totals 2350 2350 95% NOTE- ECONOMIZER LOCKED AT 15% WITH ENTHALPY CONTROL SMOKE DETECTOR LOCATED IN R/A BY ECONOMIZER.