2737 West Service Rd - Test & Balance ReportTest and Balance Report
Ultra- Lox (office buildout)
Eagan, MN
Date Tested
Dec 19-2020
The following pages containg the detailed test and data for the system (s) tested, if there are any
questions please call, Kenny 952-994-7970
Prepaired For:
Centraire Heating and Air Conditioining
6811 Washington Ave South
Edina, MN 55439
ULTRA LOX- OFFICE BUILDOUT
2737 WEST SERVICE ROAD
EAGEN, MN
Unit
Manufacture
Model
Total CFM
Fan RPM
Motor RPM
Motor Volts
Motor Amps
Horsepower
O.A. Damper CFM
RTU-1
CARRIER
48FCM07
2,400
1680
1628
208/3
4.0
3/4
350
RTU-2
CARRIER
48FCA05
1,600
1550
1500
20/3
3.0
1/2
250
RTU-1 15% outside fresh air motor locked,
RTU-2 15% outside fresh air motor locked,
RTU-3 15% outside fresh air motor locked,
RTU-4 15% outside fresh air motor locked,
RTU-3
RTU-4
CARIER
CARRIER
48FCA05
48FCM07
1,600
2,400
1550
1680
1500
1628
208/3
208/3
3.0
4.0
1/2
3/4
250
350
enthalpy control
enthalpy control
enthalpy control
enthalpy control
STANDARD THERMOSTATS WITH NO SPACE SENSORS.
Unit Number: PRV-1
Unit Manufacture: ACME -
Unit Model: ACS102
AREA
SERVED
Outlet
Number
Diffuser
TYPE
Neck
SIZE
DESIGN
CFM
Actual
CFM
Percent of
Required
BATH-1
1
DROP
6"
200
200
100%
BATH-1
2
DROP
6"
200
190
90%
BATH-2
3
DROP
6"
200
200
100%
BATH-2
4
DROP
6"
200
200
100%
Totals
800
790
95%
PRV FAN IS TIED WITH LIGHT SWITCH, RUNS ALL TIMES WHEN LIGHTS ARE ON
NOTE- TIME OF TESTING HAD TO TEMP WIRE THE PRV FAN AS IT WAS NOT
WIRED AT THIS TIME.
CURB ADAPTER WITH BACKDRAFT DAMPER INSTALLED
ALL DUCTS SEALED WITH WATER BASED SEALENT
Unit Number: RTU-1
Unit Manufacture: CARRIER
Unit Model: 48FCM07
AREA
SERVED
Outlet
Number
Diffuser
TYPE
Neck
SIZE
DESIGN
CFM
Actual
CFM
Percent of
Required
CONF
1
LAYIN
8"
300
310
105%
CONF
2
LAYIN
8"
300
280
90%
OFFICE
3
LAYIN
8"
300
300
100%
OFFICE
4
LAYIN
8"
300
275
85%
OFFICE
5
LAYIN
8"
300
300
100%
OFFICE
6
LAYIN
8"
300
300
100%
OFFICE
7
LAYIN
8"
300
290
95%
OFFICE
8
LAYIN
8"
300
295
97%
Totals
2400
2350
95%
NOTE- PACKAGED CARRIER RTU, ECONOMIZER SET AT 15% OUTISIDE AIR
WITH ENTHALPY CONTROL.
SMOKE DETECTOR LOCATED IN ECONOMIZER.
Unit Number: RTU-2
Unit Manufacture: CARRIER
Unit Model: 48FCA05
AREA
SERVED
Outlet
Number
Diffuser
TYPE
Neck
SIZE
DESIGN
CFM
Actual
CFM
Percent of
Required
BREAK
1
LAYIN
8"
250
260
105%
BREAK
2
LAYIN
8"
250
280
90%
CUBICLE
3
LAYIN
8"
250
250
100%
CUBICLE
4
LAYIN
8"
250
225
85%
CUBICLE
5
LAYIN
8"
250
240
90%
CUBICLE
6
LAYIN
8"
250
250
100%
Totals
1600
1505
92%
NOTE- ECONOMIZER LOCKED AT 15% WITH ENTHALPY CONTROL
SMOKE DETECTOR LOCATED IN R/A BY ECONOMIZER.
STANDA ALONE THERMOSTAT
Unit Number: RTU-3
Unit Manufacture: CARRIER
Unit Model: 48FCA05
AREA
SERVED
Outlet
Number
Diffuser
TYPE
Neck
SIZE
DESIGN
CFM
Actual
CFM
Percent of
Required
BATH
1
LAYIN
8"
230
230
105%
BATH
2
LAYIN
8"
230
220
90%
CUBICLE
3
LAYIN
8"
230
250
100%
CUBICLE
4
LAYIN
8"
230
225
95%
CUBICLE
5
LAYIN
8"
230
240
105%
CUBICLE
6
LAYIN
8"
230
230
100%
BATH
7
LAYIN
6"
230
200
80%
Totals
1600
1595
98%
NOTE- ECONOMIZER LOCKED AT 15% WITH ENTHALPY CONTROL
SMOKE DETECTOR LOCATED IN R/A BY ECONOMIZER.
STAND A -LONE THERMOSTAT HONEYWELL.
Unit Number: RTU-4
Unit Manufacture: CARRIER
Unit Model: 48FCM07
AREA
SERVED
Outlet
Number
Diffuser
TYPE
Neck
SIZE
DESIGN
CFM
Actual
CFM
Percent of
Required
COPY
1
LAYIN
8"
250
310
105%
COMMON
2
LAYIN
8"
250
280
90%
OFFICE
3
LAYIN
8"
250
300
100%
OFFICE
4
LAYIN
8"
250
275
85%
OFFICE
5
LAYIN
8"
250
300
100%
OFFICE
6
LAYIN
8"
250
300
100%
OFFICE
7
LAYIN
8"
250
290
95%
OFFICE
8
LAYIN
8"
300
295
97%
COMON
9
LAYIN
8"
300
280
90%
Totals
2350
2350
95%
NOTE- ECONOMIZER LOCKED AT 15% WITH ENTHALPY CONTROL
SMOKE DETECTOR LOCATED IN R/A BY ECONOMIZER.