2865 Vikings Cir - Arete Sports T&B Report3365 Fax (763) 657-0587 HVAC TESTING & BALANCING REPORT ARETE SPORTS Test & Balance Associates, Inc. 7308 Aspen Lane, Suite 110 Brooklyn Park, MN 55428-1006 Phone (763) 657-0159 Cell (612) 272-5651 Test & Balance Associates, Inc. 7308 Aspen Lane, Suite 110 Brooklyn Park, MN 55428 Phone: (763) 657-0159 Fax: (763) 657-0587 Cell: (612) 272-5651 CERTIFIED TEST; ADJUST; BALANCE REPORT # DATE PROJECT ADDRESS ENGINEER HVAC CONTRACTOR NEBB TAB FIRM NEBB TAB SUPERVISOR CERTIFICATION NUMBER 3242 2/25/2021 ARETE SPORTS Test & Balance Associates, Inc. Donald J. Henderson LEGEND COMPANIES (952) 818-8500 LEGEND COMPANIES (952) 818-8500 2685 VIKINGS CIRCLE SUITE #350 EGAN MN Test & Balance Associates, Inc. 7308 Aspen Lane, Suite 110 Brooklyn Park, MN 55428 Phone: (763) 657-0159 Fax: (763) 657-0587 3366 PROJECT ADDRESS THE DATA PRESENTED IN THIS REPORT IS A RECORD OF SYSTEM MEASUREMENTS AND FINAL ADJUSTMENTS THAT HAVE BEEN OBTAINED IN ACCORDANCE WITH THE CURRENT EDITION OF THE NEBB PROCEDURAL STANDARDS FOR TESTING, ADJUSTING, AND BALANCING OF ENVIRONMENTAL SYSTEMS. ANY VARIANCES FROM DESIGN QUANTITIES, WHICH EXCEED NEBB TOLERANCES, ARE NOTED IN THE TEST - ADJUST - BALANCE REPORT PROJECT SUMMARY. SUBMITTED & CERTIFIED BY: NEBB TAB FIRM NEBB TAB SUPERVISOR REG. NO. SIGNATURE DATE CERTIFICATION EXPIRATION DATE CERTIFICATION REPORT 3/31/2022 ARETE SPORTS 2685 VIKINGS CIRCLE SUITE #350 EGAN MN 2/25/2021 Test & Balance Associates, Inc. Donald J. Henderson 3242 Test & Balance Associates, Inc. 7308 Aspen Lane, Suite 110 Brooklyn Park, MN 55428 Phone: (763) 657-0159 Fax: (763) 657-0587 PROJECT:5094 - ARETE SPORTS Project Notes and Summary. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . MULTI AIR DISTRIBUTION SYSTEM EXISTING AHU. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . MULTI AIR DISTRIBUTION SYSTEM EXISTING AHU. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . MULTI AIR DISTRIBUTION SYSTEM EXISTING EXHAUST. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . FLOW FITTING REPORT SYSTEM HEATING WATER. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Instrument Calibration Report. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Symbol Report. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Symbol Report. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Symbol Report. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Symbol Report. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 TABLE OF CONTENTS 1 2 3 4 6 7 8 9 10 Test & Balance Associates, Inc. 7308 Aspen Lane, Suite 110 Brooklyn Park, MN 55428 Phone: (763) 657-0159 Fax: (763) 657-0587 3371 PROJECT:5094 - ARETE SPORTS DESCRIPTION:EXECUTIVE SUMMARY PROJECT NOTES AND SUMMARY REPORT PAGE:1 of 10 TEST DATE: THE SCOPE OF THE TESTING AND BALANCING WAS TO MEASURE AND ADJUST SUPPLY, EXHAUST AND HEATING WATER FLOWS TO MEET DESIGN LISTED REQUIREMENTS AS LISTED ON MECHANICAL DRAWINGS DATED 12/28/2020. THE VAV'S LISTED BELOW WERE CALIBRATED UNDER THE EXISTING STATIC SETPOINT OF 1.50"W.C.. -VAV-1 HAS A DESIGN CFM OF 1900. WE HAVE A CALIBRATED TEST CFM OF 1909 (100.0%) IN THE MAXIMUM COOLING CFM MODE. -VAV-2 HAS A DESIGN CFM OF 750. WE HAVE A CALIBRATED TEST CFM OF 767 (102.2%) IN THE MAXIMUM COOLING CFM MODE. -VAV-3 HAS A DESIGN CFM OF 500. WE HAVE A CALIBRATED TEST CFM OF 503 (100.0%) IN THE MAXIMUM COOLING CFM MODE. -VAV-4 HAS A DESIGN CFM OF 1675. WE HAVE A CALIBRATED TEST CFM OF 1694 (101.1%) IN THE MAXIMUM COOLING CFM MODE. 3367 PAGE: 2 of 10 PROJECT: ARETE SPORTS DATE: Feb 2021 SYSTEM: EXISTING AHU TECH: BRIAN STOUT DESIGN PRELIMINARY FINAL NO.SIZE FACTOR VEL CFM VEL CFM VEL CFM VAV-01 14 106A 1 20/6 0.833 570 475 586 488 106A 2 20/6 0.833 570 475 574 478 106A 3 20/6 0.833 570 475 558 465 106A 4 20/6 0.833 570 475 563 469 MAXIMUM CFM 1 18 1.766 1076 1900 1081 1909 MINIMUM CFM 1 18 1.766 269 475 277 489 FLOW FACTOR 1.80 VAV-02 10 CORRIDOR 1 8 HOOD --250 --271 CORRIDOR 2 8 HOOD --250 --225 100 3 8 HOOD --250 --271 MAXIMUM CFM 750 767 MINIMUM CFM 225 233 FLOW FACTOR 1.88 VAV-03 8 104 1 8 HOOD --250 --262 104 2 8 HOOD --250 --241 MAXIMUM CFM 500 503 MINIMUM CFM 150 161 FLOW FACTOR 2.04 STATIC PRESSURE SETPOINT IS 1.5" W.C. AREA SERVED OPENING TEST & BALANCE ASSOCIATES, INC. AIR DISTRIBUTION REPORT 3368 PAGE: 3 of 10 PROJECT: ARETE SPORTS DATE: Feb 2021 SYSTEM: EXISTING AHU TECH: BRIAN STOUT DESIGN PRELIMINARY FINAL NO.SIZE FACTOR VEL CFM VEL CFM VEL CFM VAV-04 14 105 1 10 HOOD --350 --374 103 2 10 HOOD --350 --338 107 3 12/4 0.333 450 150 452 151 103 4 10 HOOD --350 --382 101 5 10 HOOD --350 --318 102 6 8 HOOD --125 --133 MAXIMUM CFM 1675 1694 MINIMUM CFM 500 544 FLOW FACTOR 1.88 AREA SERVED OPENING TEST & BALANCE ASSOCIATES, INC. AIR DISTRIBUTION REPORT 3369 PAGE: 4 of 10 PROJECT: ARETE SPORTS DATE: Feb 2021 SYSTEM: EXISTING EXHAUST TECH: BRIAN STOUT DESIGN PRELIMINARY FINAL NO.SIZE FACTOR VEL CFM VEL CFM VEL CFM WOMEN 1 10 HOOD --300 --83* MEN 2 10 HOOD --300 --86* *INLET DAMPER 100% OPEN. AREA SERVED OPENING TEST & BALANCE ASSOCIATES, INC. AIR DISTRIBUTION REPORT 3370 UNIT TYPE LOCATION FLOW FITTING SIZE SETTING DESIGN GPM FINAL P.D. FINAL GPM NOTES VAV-01 SHELL 3/4 2.5 2.9 1.59 2.73 VAV-02 SHELL 3/4 1.5 1.4 2.84 1.60 VAV-03 104 3/4 .5 .9 6.5 1.05 VAV-04 101 3/4 2.5 2.5 1.50 2.65 TECHNICIAN: BRIAN STOUT FLOW FITTING MANUFACTURER IS TOUR ANDERSON. PRESSURE DROP IN FEET OF WATER. NOTE: DIFFERENTIAL PRESSURE SETPOINT IS UNKNOWN SYSTEM: HEATING WATER DATE: Feb 2021 TEST & BALANCE ASSOCIATES, INC. FLOW FITTING REPORT PROJECT: ARETE SPORTS PAGE: 5 of 10 Test & Balance Associates, Inc. 7308 Aspen Lane, Suite 110 Brooklyn Park, MN 55428 Phone: (763) 657-0159 Fax: (763) 657-0587 3373 PROJECT:5094 - ARETE SPORTS REMARKS: AIR PRESSURE/VOLUME HYDRONIC PAGE:6 of 10 INSTRUMENT CALIBRATION REPORT ADM-880C M10336 11/13/2020 Alnor HM670C M07481 APPLICATIONMANUFACTURERMODELSERIAL 11/13/2020 Shortridge Inst. CALIBRATION DATE Test & Balance Associates, Inc. 7308 Aspen Lane, Suite 110 Brooklyn Park, MN 55428 Phone: (763) 657-0159 Fax: (763) 657-0587 PROJECT:ARETE SPORTS SYMBOL DESCRIPTION SYMBOL DESCRIPTION A/C Air Conditioning(er)CLG Ceiling A/AMP Ampere COM Common AC Alternating Current COMP Compressor Unit AD Access Door CONFIG Configuration ADJ Adjustable CONV Convector ADM Airdata Multimeter CP Condenser Pump AF Air Filter/Airfoil CPS Cycles Per Second AFMS Airflow Measuring Station CR Condenser Water Return AHU Air Handling Unit CS Condenser Water Supply ALT Alternate CT Cooling Tower AMB Ambient CUH Cabinet Unit Heater AP Access Panel CWR Chilled Water Return AUTO Automatic CWS Chilled Water Supply BAL Balancing DB Dry Bulb BBR Baseboard Radiation DC Direct Current BC Balancing Cock DDC Direct Digital Control BHP Break Horse Power DEG Degree BI Backward Inclined DH Duct Heater BLDG Building DIA Diameter BRG Bearing DIAG Diagonal BTU British Thermal Unit DIFF Diffuser BTUH BTU Per Hour DISCH Discharge C Condenser Water DISTR Distribution CD Ceiling Diffuser DM Damper Motor CENT Centrifugal DMPR Damper CF Cubic Feet DN Down CFH Cubic Feet Per Hour DPS Diff. Pressure Switch CFM Cubic Feet Per Minute DX Coil Direct Expansion Coil CKT Circuit E East CL Centerline EA Exhaust Air 7 of 10 ABBREVIATIONS PAGE ONE Test & Balance Associates, Inc. 7308 Aspen Lane, Suite 110 Brooklyn Park, MN 55428 Phone: (763) 657-0159 Fax: (763) 657-0587 PROJECT:ARETE SPORTS SYMBOL DESCRIPTION SYMBOL DESCRIPTION EAT Entering Air Temperature GEN General EDH Electric Duct Heater GF Gas Furnace EF Exhaust Fan GHR Glycol-water Heating Return EFF Efficiency GHS Glycol-water Heating Supply ENT Entering GPH Gallons Per Hour EQUIP Equipment GPM Gallons Per Minute ER Exhaust Register GR Grille ESP External Static Pressure H Height EST Estimate HD Head EWT Entering Water Temperature HOA Hand off Automatic EXH Exhaust HORIZ Horizontal EXIST Existing HP Heat Pump/Horsepower EXT Exterior HR Hour F Fahrenheit/Furnace HT Height FA Fresh Air HTG Heating FC Forward Curved HTR Heater FCU Fan Coil Unit HV Heating Ventilating Unit FD Fire Damper HVAC Heating Ventilating and Air Conditioning FIG Figure HWR Heating Hot Water Return FME Flow Measuring Equipment HWS Heating Hot Water Supply FMS Flow Measuring Station HX Heat Exchanger FPM Feet Per Minute HZ Hertz FPS Feet Per Second ID Inside Diameter FSD Fire/Smoke Damper IH Intake Hood FT Feet (Foot)INT Interior; Internal FTR Finned Tube Radiation IN Inch GA Gauge KH Kitchen Hood GAL Gallon KHE Kitchen Hood Exhaust Fan 8 of 10 ABBREVIATIONS PAGE TWO Test & Balance Associates, Inc. 7308 Aspen Lane, Suite 110 Brooklyn Park, MN 55428 Phone: (763) 657-0159 Fax: (763) 657-0587 PROJECT:ARETE SPORTS SYMBOL DESCRIPTION SYMBOL DESCRIPTION KHS Kitchen Hood Supply Fan N North KIT Kitchen N/A Not Applicable KV Kilovolt NC Normally Closed KVA Kilovolt Amperes NEMA National Electrical-Manufacturers Assn. KW Kilowatt NIC Not In Contract KWH Kilowatt Hour NO Normally Open/Number LAB Laboratory OA Outside Air LAT Leaving Air Temperature OBD Opposed Blade Damper LB/LBS Pound/Pounds OC On Center LF Linear Foot OD Outside Diameter LIN Linear P/T Pressure/Temp. Test Port LVG Leaving P Pump LWT Leaving Water Temp.PCF Pounds Per Cubic Foot MA Mixed Air PD Pitch Diameter MAN Manual PD Pressure Drop MAU Makeup Air Unit PE Pneumatic Electric MAV Manual Air Vent PF Power Factor MAX Maximum PG Pressure Gage MBH/MBTUH Thousand BTU Per Hour PH Phase MVD Manual Volume Damper PNEU Pneumatic MECH Mechanical PROP Propeller MEZZ Mezzanine PRV Pressure Reducing Valve MHWR Med Temp Heating Water Return PRV Power Roof Ventilation MHWS Med Temp Heating Water Supply PSF Pounds Per Sq. Ft. MIN Minimum PSI Pounds Per Sq. Inch MISC Miscellaneous PSIA Pounds Per Square Inch Absolute 9 of 10 ABBREVIATIONS PAGE THREE Test & Balance Associates, Inc. 7308 Aspen Lane, Suite 110 Brooklyn Park, MN 55428 Phone: (763) 657-0159 Fax: (763) 657-0587 PROJECT:ARETE SPORTS SYMBOL DESCRIPTION SYMBOL DESCRIPTION PSIG Pounds Per Square Inch Gauge TEMP Temperature PWR Power TF Transfer Fan RA Return Air TFSP Total Fan Static Pressure RAD or R Radius TONS Tons of Air Conditioning RAT Return Air Temperature TS Temperature Sensor REG Register TSP Total Static Pressure RF Return Fan UH Unit Heater RH Relative Humidity UV Unit Ventilator RH Relief Hood V Volt RHC Reheat Coil VAV Variable Air Volume RPM Revolutions Per Minute VEL Velocity RTU Rooftop Unit VENT Ventilation S Sensor/South VERT Vertical SA Supply Air VFD Variable Frequency Drive SAT Supply Air Temperature VM Voltmeter SD Smoke Damper VOL Volume SENS Sensible VSMC Variable Speed Motor Controller SF Square Foot/Supply Fan W West SP Static Pressure WB Wet Bulb SPL Sound Pressure Level WFMD Water Flow Measuring Device SQ Square WT Weight SUC Suction YD Yard T/T-STAT Thermostat &And TA Transfer Air @ At TB Terminal Box #Number TC Temperature Control + Plus/Positive TD Temperature Differential -Minus/Negative 10 of 10 ABBREVIATIONS PAGE FOUR