2020 Silver Bell Rd - Blackstone Fitness Test & Balance Report 2021-10-25remier
TEST & BALANCE INC
375 230th Ave, Somerset WI 54025 - Phone: (612) 834-0311 Fax: (414) 377-3349
www.Premierbalancing.com
TESTING, ADJUSTING AND BALANCING BUREAU
THE PROFESSIONAL'S CHOICE"
Testing, Adjusting & Balancing Report
TABB TECHNICIAN
Technician: Tony Kompelien
Cell Phone: 612-419-1425
Email Address: tony@premierbalancing.com
PROJECT
Blackstone Fitness
Silver Bell Business Center
2020 Silver Bell Road, Suite 4
Eagan, MN 55122
CLIENT
Kraft Contracting & Mechanical, LLC
2415 Ventura Drive, #100
Woodbury, MN 55125
ENGINEER
NA
Report Date
October 25, 2021
TABB CERTIFICATION
TABB certification of a Supervisor is TABB's statement that the Supervisor is able to
supervise testing, adjusting and balancing of building environmental systems to produce the
design objectives or optimum system performance. For TABB Certification purposes, a
Supervisor is the person who, while employed by a TABB Certified Contractor, is
responsible and accountable for overseeing, coordinating and ensuring that projects are
performed by TABB Certified Technicians in accordance with TABB standards (including the
ICB Code of Conduct and the TAB General Rules).
Measurements recorded in this report are in accordance with the SMACNA I TABB HVAC Systems,
Testing, Adjusting and Balancing manual.
Anthony Kompelien
TABB Technician
1E875224T
December 31, 2022
eru,cmfor 27r2 0.
Premier Test & Balance LLC
Peter Korzenowski
TB0458712C
lIgt Valid Unless Sig
Anthony Kompelien
Premier Test & Balance LLC
TARE Supervisor
TH8752295
December 31, 2022
erzncea 10/27/2020
TABB Certified "The Professional's Choice"
Page 2
TABS QUALITY ASSURANCE PROGRAM
BACKGROUND
TABB seeks to ensure the integrity of its certification program by: (a) setting eligibility criteria for TABB
Certified Supervisors and TABB Certified Contractors, (b) establishing testing procedures for TABB
Certified Supervisors, (c) requiring continuing education and continuous compliance with eligibility criteria
for renewal of certification, and (d) periodically reviewing its recognition of technician certification. High
quality work on the part of TABB Certified Technicians and TABB Certified Supervisors and TABB Certified
Contractors (TABB Professionals) is essential to integrity of the TABB Certification Program. TABB offers
this TABB Quality Assurance Program to help assure high quality work. By accepting TABB qualification or
certification, every TABB Professional accepts the responsibilities or this Program.
Quality Assurance
Every customer of a TABB Certified Contractor shall be entitled to expect: (1) that testing, adjusting and
balancing work by the contractor and its TABB Professionals will meet TABB standards; (2) that testing,
adjusting and balancing reports provided to the customer will have been prepared by a TABB Certified
Technician, and reviewed by a TABB Certified Supervisor; and (3) that the report(s) will include
measurements taken accurately with the date and mode of operation of the systems.
TABB
8403 Arlington Boulevard
Fairfax, VA 22031
Phone - (703) 299-5646
Fax - (703) 683-7615
TABB Certified "The Professional's Choice"
Page 3
INSTRUMENT
CALIBRATION REPORT
INSTRUMENT
MODEL
MANUFACTURER
SERIAL NUMBER
CALIBRATION DATES
Current
Expiration
Rotating Measuring Instrument
PLT-5000
Check -Line
B15985012P
10/05/21
10/05/22
Temperature Measuring Instrument
Temperature Measuring Probe
HM70
HMP75
Vaisala
Vaisala
M4820017
M5040569
10/08/21
10/08/21
10/08/22
10/08/22
Electrical Measuring Instruments
117
322
Fluke
Fluke
18561871
17830473
10/05/21
10/05/21
10/05/22
10/05/22
Air Pressure Measuring Instrument
S-PVF-1
Evergreen Telemetry
1800207
09/02/21
09/02/22
Air Velocity Measuring Instrument
S-PVF-1
Evergreen Telemetry
1800207
09/02/21
09/02/22
Hydronic Pressure Measuring Instrument
0 to 300 psi
HM-675
Alnor
71514005
10/05/21
10/05/22
TABB Certified "The Professional's Choice"
Page 4
Premier Test & Balance
Index
Project:
Technician:
Blackstone Fitness
Tony Kompelien
Premier Job Number: 4232
Report Date: 10/25/21
Page
System I Equipment
Description
Completion Date
6-7
RTU-A (East)
Constant Air Volume
10/25/21
8-9
RTU-B (West)
Constant Air Volume
10/25/21
10
Existing Exhaust
Constant Air Volume
10/25/21
TABB Certified "The Professional's Choice"
Page 5
Premier Test & Balance
Air Handling Unit Test Data
Project:
System:
Technician:
Blackstone Fitness
RTU-A (East)
Tony Kompelien
Premier Job Number: 4232
Completion Date: 10/25/21
System Scheduled Data
Model number: 581KPO5N110A2A0AAA
Manufacturer: Bryant
Total Design CFM: -
Fan Static Pressure: -
Serial number: 2121052834
Outlet Total CFM: 1,625
Min.Outside Air CFM: 439
Equipment Location: Roof
Performance Data
Description
Motor HP:
Motor RPM:
Motor Hertz:
Motor Service Factor:
Motor Phase:
Motor Voltage:
Motor Amperage:
Motor BHP:
Fan RPM:
Scheduled I Submittal Data
0.75
1750
60.0
1.15
1
208
7.1
-
1750
Actual Field Measurements
0.75
1750
60.0
1.15
1
213
5.7
0.62
Direct Drive
Static Pressure Data
Component
Static Pressure
inches of water)
Pressure
Rise 1 Drop
Pressure
Total (inches)
In
Out
RTU ESP:
-0.13
0.39
Rise
0.52
Airflow Measurements
Supply Air
Opening
No.
Area
Served
Size
K
Factor
Design
Final Reading
Preliminary Reading
Velocity
CFM
Velocity
CFM
%
Velocity
CFM
1
Various
Flow Hood
1.00
1625
1625
1613
1613
99%
1631
1631
Total
1625
1613
99%
1631
Minimum Outside Air
Size
K
Factor
Design
Final Reading
Preliminary Reading
Velocity
CFM
Velocity
CFM
%
Velocity
CFM
Total
29x16
3.22
136
439
139
448
102%
43
139
Remarks:
a) Fitness measured square footage: 1817 Sq. Ft. (.3 OA CFM per Sq. Ft.) = 545 OA CFM total required.
(25.7% outside air needed to meet required CFM - Unit was set to 27% outside air).
b) The sum of the outlets used for fan total CFM.
TABB Certified "The Professional's Choice"
Page 6
Premier Test & Balance
Air Outlet Test Report
Project:
System:
Technician:
Blackstone Fitness
RTU-A (East)
Tony Kompelien
Premier Job Number: 4232
Completion Date: 10/25/21
Airflow Measurements
Opening
Area
Size
K
Design
Final Reading
Preliminary Reading
No.
Served
Factor
Velocity
CFM
Velocity
CFM
%
Velocity
CFM
1
Fitness
Flow Hood
1.00
325
325
332
332
102%
396
396
2
Fitness
Flow Hood
1.00
325
325
317
317
98%
265
265
3
Fitness
Flow Hood
1.00
325
325
312
312
96%
493
493
4
Fitness
Flow Hood
1.00
325
325
345
345
106%
179
179
5
Fitness
Flow Hood
1.00
325
325
308
308
95%
298
298
Total
1625
1613
99%
1631
Remarks:
a)
b)
c)
d)
e)
TABB Certified "The Professional's Choice"
Page 7
Premier Test & Balance
Air Handling Unit Test Data
Project:
System:
Technician:
Blackstone Fitness
RTU-B (West)
Tony Kompelien
Premier Job Number: 4232
Completion Date: 10/25/21
System Scheduled Data
Model number: 580FPV036074ABGA
Manufacturer: Bryant
Total Design CFM: -
Fan Static Pressure: -
Serial number: 0407G20151
Outlet Total CFM: 1,145
Min.Outside Air CFM: 309
Equipment Location: Roof
Performance Data
Description
Motor HP:
Motor RPM:
Motor Hertz:
Motor Service Factor:
Motor Phase:
Motor Voltage:
Motor Amperage:
Motor BHP:
Fan RPM:
Scheduled I Submittal Data
0.50
1620
60.0
1.15
1
208
4.9
-
-
Actual Field Measurements
0.50
1620
60.0
1.15
1
213
4.2
0.44
836
Static Pressure Data
Component
Static Pressure
inches of water)
Pressure
Rise 1 Drop
Pressure
Total (inches)
In
Out
RTU ESP:
-0.14
0.34
Rise
0.48
Airflow Measurements
Supply Air
Opening
No.
Area
Served
Size
K
Factor
Design
Final Reading
Preliminary Reading
Velocity
CFM
Velocity
CFM
%
Velocity
CFM
1
Various
Flow Hood
1.00
1145
1145
1143
1143
100%
1058
1058
Total
1145
1143
100%
1058
Minimum Outside Air
Size
K
Factor
Design
Final Reading
Preliminary Reading
Velocity
CFM
Velocity
CFM
%
Velocity
CFM
Total
24x14
2.33
132
309
130
303
98%
54
126
Remarks:
a) Fitness measured square footage: 1817 Sq. Ft. (.3 OA CFM per Sq. Ft.) = 545 OA CFM total required.
(25.7% outside air needed to meet required CFM - Unit was set to 27% outside air).
b) The sum of the outlets used for fan total CFM.
TABB Certified "The Professional's Choice"
Page 8
Premier Test & Balance
Air Outlet Test Report
Project:
System:
Technician:
Blackstone Fitness
RTU-B (West)
Tony Kompelien
Premier Job Number: 4232
Completion Date: 10/25/21
Airflow Measurements
Opening
Area
Size
K
Design
Final Reading
Preliminary Reading
No.
Served
Factor
Velocity
CFM
Velocity
CFM
%
Velocity
CFM
1
Womens Bathroom
Flow Hood
1.00
45
45
47
47
105%
44
44
2
Office
Flow Hood
1.00
90
90
93
93
103%
86
86
3
Corner Office
Flow Hood
1.00
110
110
100
100
91%
116
116
4
Corner Office
Flow Hood
1.00
100
100
101
101
101%
98
98
5
Front Entry Area
Flow Hood
1.00
100
100
92
92
92%
20
20
6
Front Entry Area
Flow Hood
1.00
100
100
104
104
104%
99
99
7
Front Entry Area
Flow Hood
1.00
100
100
95
95
95%
88
88
8
Fitness
Flow Hood
1.00
200
200
219
219
110%
202
202
9
Fitness
Flow Hood
1.00
300
300
292
292
97%
305
305
Total
1145
1143
100%
1058
Remarks:
a)
b)
c)
d)
e)
TABB Certified "The Professional's Choice"
Page 9
Premier Test & Balance
Air Outlet Test Report
Project:
System:
Technician:
Blackstone Fitness
Existing Exhaust
Tony Kompelien
Premier Job Number: 4232
Completion Date: 10/25/21
Airflow Measurements
Opening
No.
Area
Served
Size
K
Factor
Design
Final Reading
Preliminary Reading
Velocity
CFM
Velocity
CFM
%
Velocity
CFM
1
2
3
Shower
Mens Bathroom
Wormens Bathroom
Flow Hood
Flow Hood
Flow Hood
1.00
1.00
1.00
150
100
100
150
100
100
156
98
95
156
98
95
104%
98%
95%
153
116
82
153
116
82
Total
350
349
100%
351
Remarks:
a)
b)
c)
d)
e)
TABB Certified "The Professional's Choice"