1305 Corporate Center Dr - Edward Jones Test & Balance Report 2021-11-22 1p, I
II . 1
Modern Heating & Air
Building Efficiency and Sustainability
A Service Logic Company
TEST, ADJUST, AND BALANCE REPORT
PROJECT: EDWARD JONES- EAGAN
1305 CORPORATE CENTER DR. -SUITE 120
EAGAN, MN
HVAC CONTRACTOR: MODERN HEATING &AIR CONDITIONING, INC.
2318 FIRST STREET NE
MINNEAPOLIS, MN 55418
PHONE: 612-781-3358
FAX: 612-781-3428
TAB FIRM: MODERN HEATING &AIR CONDITIONING, INC.
2318 FIRST STREET NE
MINNEAPOLIS, MN 55418
PHONE: 612-781-3358
FAX: 612-781-3428
i
Modern Heating &Air
Building Efficiency and Sustainability
A Service Logic Company
AIR OUTLET TEST REPORT
PROJECT EDWARD JONES- EAGAN
SYSTEM TEST APPARATUS FLOW HOOD
OUTLET DESIGN PRELIMINARY FINAL PERCENT
AIRFLOW AIRFLOW AIRFLOW OF
AREA SERVED NO. TYPE SIZE CFM CFM CFM DESIGN
HP 1 DAIKIN 375 797 371 99%
RECEPTION 1 2X2 LAYIN 8" 135 156 128 95%
OPEN 107 2 2X2 LAYIN 8" 90 242 92 102%
SUPPLY 104 3 2X2 LAYIN 6" 50 132 49 98%
HALL 4 2X2 LAYIN 8" 100 267 102 102%
HP 2 DAIKIN 900 1455 883 98%
BOA 101 1 4' LINEAR 8" 150 304 142 95%
OPEN 106 2 4' LINEAR 8" 150 326 149 99%
OPEN 106 3 4' LINEAR 8" 150 61 143 95%
OFFICE 102 4 4' LINEAR 8" 150 230 146 97%
OFFICE 102 5 4' LINEAR 8" 150 1 268 153 102%
OFFICE 102 6 4' LINEAR 8" 150 266 150 100%
REMARKS:
TEST DATE 11-18-2021
READINGS BY JOSH MCKNIGHT
PAGE 1