Loading...
1305 Corporate Center Dr - Edward Jones Test & Balance Report 2021-11-22 1p, I II . 1 Modern Heating & Air Building Efficiency and Sustainability A Service Logic Company TEST, ADJUST, AND BALANCE REPORT PROJECT: EDWARD JONES- EAGAN 1305 CORPORATE CENTER DR. -SUITE 120 EAGAN, MN HVAC CONTRACTOR: MODERN HEATING &AIR CONDITIONING, INC. 2318 FIRST STREET NE MINNEAPOLIS, MN 55418 PHONE: 612-781-3358 FAX: 612-781-3428 TAB FIRM: MODERN HEATING &AIR CONDITIONING, INC. 2318 FIRST STREET NE MINNEAPOLIS, MN 55418 PHONE: 612-781-3358 FAX: 612-781-3428 i Modern Heating &Air Building Efficiency and Sustainability A Service Logic Company AIR OUTLET TEST REPORT PROJECT EDWARD JONES- EAGAN SYSTEM TEST APPARATUS FLOW HOOD OUTLET DESIGN PRELIMINARY FINAL PERCENT AIRFLOW AIRFLOW AIRFLOW OF AREA SERVED NO. TYPE SIZE CFM CFM CFM DESIGN HP 1 DAIKIN 375 797 371 99% RECEPTION 1 2X2 LAYIN 8" 135 156 128 95% OPEN 107 2 2X2 LAYIN 8" 90 242 92 102% SUPPLY 104 3 2X2 LAYIN 6" 50 132 49 98% HALL 4 2X2 LAYIN 8" 100 267 102 102% HP 2 DAIKIN 900 1455 883 98% BOA 101 1 4' LINEAR 8" 150 304 142 95% OPEN 106 2 4' LINEAR 8" 150 326 149 99% OPEN 106 3 4' LINEAR 8" 150 61 143 95% OFFICE 102 4 4' LINEAR 8" 150 230 146 97% OFFICE 102 5 4' LINEAR 8" 150 1 268 153 102% OFFICE 102 6 4' LINEAR 8" 150 266 150 100% REMARKS: TEST DATE 11-18-2021 READINGS BY JOSH MCKNIGHT PAGE 1