2065 Cliff Rd - Test & Balance ReportProfessional Independent Test and Balance Trader Joe's Eagan, MN for Quality Heating & Air Conditioning Shakopee, MN Testing by Frank S. Arone Jr. MECTNICAL TEST BnLnn� 1660 Spring Avenue Maple Plain, Minnesota 55359 763/479-6300 763/479-6655 (fax) February 2, 2022 Certified by Amok Associated Air Balance Council Adak AABC Associated Air Balance Council Annua(�WemfiershT Certificate Awarded to Mechanical Test and Balance Corporation as a memder in good standing of the Associated;I it �Bafance Counciffor the year This member has met alf requirements for membership and is entitled to all rights and privireges of,490C certification. 7iis certificate is renewable on an annual basis and expires (December 31, 2022. 41UM Michael S. Kelly, President no C �4 Raymond R. Bert, AABC Associated Air Balance council Annual certificate Timothy J. Mahoney, TBE Mechanical Test and Balance Corporation Oezjo�d ge-wt a"d Oa"ww� &/ff MA'- de,'0/del -Oa&wx,�� amdvzwed &- lwklvnl ffital OwwzwAa&acel m, accoW6ce-1 dela� 2022 ,Tfi� . tit awn4ea° 99-04-24 k fi* rwco�d � del &� . 6' t�, lmezoar k on, aw, almmal km&l ,of t� �� y 1eca1v1,&- to /&wzz/z; ry � 41aw Michael S. Kelly, President i� zr Raymond R. Bert, Executive Director AABC Associated Air Balance Council Frank S. Arone. II t wd1w, s� a&aw O 5� & � myhzee.,,- Mechanical Test and Balance Corporation 62-04-18 i6�rrco�nirzrrLi�i�drt%r tur�bicr��iitr a/ioor nainea�.�./��i'inrin/ir�-arfri�� .�i6 cert Zartr e4irr& -Oecel�8>, 2022on awannaoL/iasi6 41aw Michael S. Kelly, President Raymond R. Bert, Executive Director and AABC National Perfiormance Guaranty Pursuant to the agreement between Mechanical Test and Balance AABC Certified Testing & Balancing Agency Quality Heating & Air Conditioning Client All systems shall be tested and balanced in accordance with the project plans and specifications and to the optimum performance capabilities of the equipment. Testing and balancing shall be done in accordance with the standards published by the Associated Air Balance Council. If the Agency listed above fails to comply with the specifications for any reason other than termination of business by the AABC agency or equipment malfunction or inadequacy which prevents proper balancing of the systems, AABC will investigate and, if warranted, will provide supervisory personnel to assist the member Agency to perform work in accordance with AABC Standards. This supervision will be provided at no additional cost to the building owner. This Guaranty is valid for one year from the date of submission of a test and balance report, provided the Agency is a current member of AABC, and may only be invoked in writing by the building owner, architect, or engineer of record. The Guaranty is limited to the terms and conditions as stated herein. Project Name Trader Joe's Address 2055 Cliff Rd. Eagan, MN 55122 Name of Engineer Hannah Kiger, PE Engineering Firm Design -Aire Engineering, Inc. Email Address NA Address 2707 Rand Rd Indianapolis, IN 446241 )at , 2/2/22 TBE # 99-04-24 By Timothy J. Mahoney AABC Certified TBE "15C Associated Air Balance Council 1518 K Street, N.W. Washington, D.C. 20005 202-737-0202 • Fax 202-638-4833 info@aabc.com • www.aabc.com MECIQNICAL TES16t HHLHncE TABLE OF CONTENTS Instrumentation.................................................................................1 RTU-1..............................................,.............................................2-3 RTU -2 ..............................................,.............................................4- 5 RTU-3..............................................,.............................................6-7 RTU -4 .............................................. , ...........................................8-10 Exhaust..........................................................................................11 AftbAssociated Air Balance Council MECI�NICAL Trader Joe's TEST HHLnncE V1,Eagan, MN 2/2/2022 INSTRUMENT LIST The following instruments were used to successfully measure and set each device. TYPE MAKE I MODEL SERIAL NO. CALIBRATION DATE Multimeter Evergreen Tele. S -PVF -1 1600109 12/22/2021 Multimeter Evergreen Tele. S -PVF -1 1700106 12/2/2021 Multimeter Evergreen Tele. S -PVF -1 1700105 9/12/2021 Multimeter Evergreen Tele. S -PVF -1 1600179 12/8/2021 Multimeter Evergreen Tele. S -PVF -1 1800146 11/23/2021 Multimeter Evergreen Tele. S -PVF -1 1600304 9/15/2021 Multimeter Evergreen Tele. S -PVF -1 1700255 11/5/2021 Water Meter Dwyer 490-4-3 N 12 11/10/2021 Water Meter Dwyer 490-4-3V N32X 10/21/2021 Water Meter Dwyer 490-4-3V N43S 11/10/2021 Anemometor Extech AN 100 11116596 8/30/2021 Duct Pressure Tube United McGill MT5-95 6755-5 NA Duct Pressure Tube United McGill 623000-132 3911-X NA Air Foil Shortridge NA NA NA Vel -grid Shortridge NA NA NA Pitot Tube Dwyer 24" NA NA Pitot Tube Dwyer 48" NA NA Pitot Tube Dwyer 60" NA NA Associated Air Balance Council ,�� Trader Joe's Eagan, MN M EC F I CAL 2/2/2022 TEST BR nna , AIR HANDLING UNIT UNIT: MANUFACTURER: MODEL: SERIAL NO: RTU -1 Lennox LGH120H4MS4Y 5621F09122 CONDITIONS REQUIRED FINAL TOTAL FAN CFM 4,000 4,077 SPEED CONTROLLER -- 75% FAN S.P. -/-/1.02 -.44 / +.35 /.79 EXTERNAL FAN S.P. - / - / .5 -.12 / +.35 /.47 FILTER S.P. -/-/NA -.12 / -.18 /.06 COOLING COIL S.P. -/-/NA -.18 / -.44 /.26 FAN RPM 890 897 OUTDOOR AIR CFM 0 0 MOTOR MANUFACTURER Interlink MOTOR HP 3 3 VOLTAGE 208 210 / 211 / 211 AMPERAGE 8 6.8/6.6/6.6 MOTOR SF 1.15 1.15 MOTOR RPM 11750 11750 MOTOR SHEAVE & SHAFT 1VP40 x 1" FAN SHEAVE & SHAFT AK59 x 1" BELT SIZE / NUMBER AX58 / 1 CENTER TO CENTER 16" SHEAVE ADJUSTMENT I NA Technician: FA Date: 1/31/22 Associated Air Balance Council ,�� Trader Joe's M EC TN I CAL Eagan, MN TEST BflLME 2/2/2022 GRILLES, REGISTERS and DIFFUSERS Unit: RTU -1 ROOM OUTLET REQUIRED PRELIMINARY FINAL % OF NO. NO. TYPE SIZE "K" VEL I CFM VEL I CFM VEL I CFM REQ. 101 1 CD 24 x 24 1.0 400 400 517 517 387 387 97% 101 2 CD 24 x 24 1.0 350 350 518 518 378 378 108% 101 3 CD 24 x 24 1.0 400 400 484 484 371 371 93% 102 4 CD 24 x 24 1.0 300 300 561 561 328 328 109% 101 5 CD 24 x 24 1.0 350 350 535 535 361 361 103% 101 6 CD 24 x 24 1.0 400 400 433 433 412 412 103% 101 7 CD 24 x 24 1.0 400 400 474 474 428 428 107% 101 8 CD 24 x 24 1.0 350 350 585 585 380 380 109% 101 9 CD 24 x 24 1.0 400 400 515 515 402 402 101% 100 10 CD 24 x 24 1.0 300 300 491 491 296 296 99% 101 11 CD 24 x 24 1.0 350 350 420 420 334 334 95% Total CFM: 41000 51533 41077 Technician: FA Date: 1/31/22 Associated Air Balance Council Trader Joe's Eagan, MN M EC F I CAL 2/2/2022 TEST BR nna , AIR HANDLING UNIT UNIT: MANUFACTURER: MODEL: SERIAL NO: RTU -2 Addison PRMA150C2A2DAC4CM3 210601801001 CONDITIONS REQUIRED FINAL TOTAL FAN CFM 3,000 3,066 SPEED CONTROLLER -- 65% FAN S.P. - / - / 1.61 -.62 / +.52 / 1.14 EXTERNAL FAN S.P. -/-/ 1.0 -.18 / +.52 /.70 FILTER S.P. -/-/NA -.18 / -.28 /.10 HEATING COIL S.P. -/-/NA -.28 / -.62 /.34 FAN RPM 11428 11418 OUTDOOR AIR CFM 100% 100% MOTOR MANUFACTURER NA MOTOR HP 4.83 4.83 VOLTAGE 208 211 / 210 / 211 AMPERAGE 9.2 6.3/6.4/6.4 MOTOR SF NA NA MOTOR RPM Direct Drive Direct Drive MOTOR SHEAVE & SHAFT Direct Drive FAN SHEAVE & SHAFT Direct Drive BELT SIZE / NUMBER Direct Drive CENTER TO CENTER Direct Drive SHEAVE ADJUSTMENT I Direct Drive Technician: FA Date: 1/31/22 Associated Air Balance Council ,�� Trader Joe's M EC TN I CAL Eagan, MN TEST BflLME 2/2/2022 GRILLES, REGISTERS and DIFFUSERS Unit: RTU -2 ROOM OUTLET REQUIRED PRELIMINARY FINAL % OF NO. NO. TYPE SIZE "K" VEL I CFM VEL I CFM VEL I CFM REQ. 101 1 CD 24 x 24 1.0 300 300 426 426 310 310 103% 101 2 CD 24 x 24 1.0 300 300 452 452 319 319 106% 101 3 CD 24 x 24 1.0 300 300 411 411 298 298 99% 101 4 CD 24 x 24 1.0 300 300 475 475 315 315 105% 101 5 CD 24 x 24 1.0 300 300 497 497 319 319 106% 101 6 CD 24 x 24 1.0 300 300 591 591 321 321 107% 101 7 CD 24 x 24 1.0 300 300 415 415 288 288 96% 101 8 CD 24 x 24 1.0 300 300 389 389 286 286 95% 101 9 CD 24 x 24 1.0 300 300 432 432 295 295 98% 101 10 CD 24 x 24 1.0 300 300 457 457 315 315 105% Total CF 1 31000 41545 31066 Technician: FA Date: 1/31/22 Associated Air Balance Council Trader Joe's Eagan, MN M EC F I CAL 2/2/2022 TEST BR nna , AIR HANDLING UNIT UNIT: MANUFACTURER: MODEL: SERIAL NO: RTU -3 Lennox LGH036H4EB5Y 5621GO50007 CONDITIONS REQUIRED FINAL TOTAL FAN CFM 1,200 1,251 SPEED CONTROLLER -- 70% FAN S.P. -/-/.58 -.33 / +.15 /.48 EXTERNAL FAN S.P. - / - / .5 -.10 / +.15 /.25 FILTER S.P. -/-/NA -.10 / -.15 /.05 COOLING COIL S.P. -/-/NA -.15 / -.33 /.18 FAN RPM Direct Drive Direct Drive OUTDOOR AIR CFM 185 193 MOTOR MANUFACTURER Interlink MOTOR HP 1/2 1/2 VOLTAGE 208 210 / 211 / 211 AMPERAGE 4.3 2.7 / 2.8 / 2.8 MOTOR SF NA NA MOTOR RPM Direct Drive Direct Drive MOTOR SHEAVE & SHAFT Direct Drive FAN SHEAVE & SHAFT Direct Drive BELT SIZE / NUMBER Direct Drive CENTER TO CENTER Direct Drive SHEAVE ADJUSTMENT I Direct Drive Technician: FA Date: 1/31/22 Associated Air Balance Council ,�� Trader Joe's M EC TN I CAL Eagan, MN TEST BflLME 2/2/2022 GRILLES, REGISTERS and DIFFUSERS Unit: RTU -3 ROOM OUTLET REQUIRED PRELIMINARY FINAL % OF NO. NO. TYPE SIZE "K" VEL I CFM VEL I CFM VEL I CFM REQ. 107 1 CD 24 x 24 1.0 200 200 255 255 210 210 105% 107 2 CD 24 x 24 1.0 200 200 292 292 214 214 107% 107 3 CD 24 x 24 1.0 200 200 270 270 208 208 104% 107 4 CD 24 x 24 1.0 200 200 320 320 214 214 107% 107 5 CD 24 x 24 1.0 200 200 265 265 202 202 101% 107 6 CD 24 x 24 1.0 140 140 278 278 144 144 103% 114 7 CD 12 x 12 1.0 60 60 95 95 59 59 98% Total CFM: 11200 11775 11251 Technician: FA Date: 1/31/22 Associated Air Balance Council Trader Joe's Eagan, MN M EC F I CAL 2/2/2022 TEST BR nna , AIR HANDLING UNIT UNIT: MANUFACTURER: MODEL: SERIAL NO: RTU -4 Lennox LGH074H4TU1Y 5621GO3946 CONDITIONS REQUIRED FINAL TOTAL FAN CFM 2,350 2,358 SPEED CONTROLLER -- 75% FAN S.P. -/-/.76 -.42 / +.29 /.71 EXTERNAL FAN S.P. -/--/.5 -.11 / +.29 /.40 FILTER S.P. -/-/NA -.11 / -.19 /.08 COOLING COIL S.P. -/-/NA -.19 / -.42 /.23 FAN RPM 794 819 OUTDOOR AIR CFM 300 311 MOTOR MANUFACTURER U.S. Motors MOTOR HP 2 2 VOLTAGE 208 210 / 210 / 211 AMPERAGE 6.0 4.2/4.4/4.2 MOTOR SF 1.15 1.15 MOTOR RPM 11740 11740 MOTOR SHEAVE & SHAFT 1VP40 x 1" FAN SHEAVE & SHAFT AK79 x 1" BELT SIZE / NUMBER A53 / 1 CENTER TO CENTER 18" SHEAVE ADJUSTMENT NA Technician: FA Date: 1/31/22 Associated Air Balance Council ,�� Trader Joe's M EC TN I CAL Eagan, MN TEST BflLME 2/2/2022 GRILLES, REGISTERS and DIFFUSERS Unit: RTU -4 ROOM OUTLET REQUIRED PRELIMINARY FINAL % OF NO. NO. TYPE SIZE "K" VEL CFM VEL CFM VEL CFM REQ. Supp1Y Mens 1 CD 24 x 24 1.0 60 60 132 132 63 63 105% 105 2 CD 24 x 24 1.0 150 150 151 151 160 160 107% 105 3 CD 24 x 24 1.0 150 150 133 133 1 148 148 99% Hall 4 CD 24 x 24 1.0 150 150 148 148 162 162 108% Plat 5 CD 24 x 24 1.0 300 300 272 272 276 276 92% Womens 6 CD 24 x 24 1.0 60 60 124 124 63 63 105% 116 7 CD 12 x 12 1.0 150 150 210 210 163 163 109% 115 8 CD 24 x 24 1.0 150 150 213 213 162 162 108% 115 9 CD 24 x 24 1.0 1 150 150 158 158 159 159 106% 115 10 CD 24 x 24 1.0 150 150 207 207 161 161 107% 115 11 CD 24 x 24 1.0 150 150 199 199 1 160 160 107% 115 12 CD 24 x 24 1.0 150 150 171 171 155 155 103% 115 13 CD 24 x 24 1.0 150 150 181 181 158 158 1 105% 115 14 CD 12 x 12 1.0 200 200 154 154 183 183 92% 115 15 CD 12 x 12 1.0 200 200 173 173 185 185 93% Total CFM: 21320 21626 21358 Technician: FA Date: 1/31/22 Associated Air Balance Council Trader Joe's M EC TN I CAL Eagan, MN TEST BflLME 2/2/2022 r GRILLES, REGISTERS and DIFFUSERS Unit: RTU -4 ROOM OUTLET REQUIRED PRELIMINARY FINAL % OF NO. NO. TYPE SIZE "K" VEL I CFM VEL I CFM VEL I CFM REQ. Return 116 1 RG 24 x 24 1.0 150 150 231 231 159 159 106% 115 2 RG 24 x 24 1.0 11300 11300 11487 11487 11331 11331 102% Plat 3 RG 24 x 24 1 1.0 300 300 287 287 1 278 278 93% 105 4 RG 24 x 24 1.0 150 150 161 161 141 141 94% 105 5 RG 24 x 24 1.0 150 150 178 178 138 138 92% Total CFM: 21050 21344 21047 Technician: FA Date: 1/31/22 Associated Air Balance Council Trader Joe's M EC TN I CAL Eagan, MN TEST HHLHnEF 2/2/2022 EXHAUST FAN TEST FAN NUMBER EF -1 EF -2 EF -3 EF -5 MANUFACTURER Greenheck Greenheck Greenheck Cook MODEL NO. SP-A390-QD SP-A390-QD SP-A390-QD 90 ACEH SERIAL NO. 19260084 19260087 19260086 297SJ433/701 CONDITIONS Direct Drive Direct Drive Direct Drive Direct Drive REQUIRED CFM 100 100 150 500 ACTUAL CFM 312* 319* 297* 538 REQUIRED T.S.P. -/-/.25 -/-/.25 -/-/.25 -/-/.25 ACTUAL T.S.P. 0/+.08/.08 0/+.08/.08 0/+.11/.Il -.07/0/.07 REQUIRED RPM Direct Drive Direct Drive Direct Drive Direct Drive ACTUAL RPM Direct Drive Direct Drive Direct Drive Direct Drive MOTOR MANUFACTURER McMillian McMillian McMillian Cook MOTOR HP 1/12 1/12 1/12 1/6 SPEED CONTROLLER NA NA NA 90% REQ VOLTAGE 115 115 115 115 ACT VOLTAGE 115 115 115 115 AMP. RATING 1.42 1.42 1.42 2.36 ACT AMP 1.1 1.1 1.2 1.8 MOTOR SFA NA NA NA NA MOTOR RPM Direct Drive Direct Drive Direct Drive 300-11725 MOTOR SHEAVE Direct Drive Direct Drive Direct Drive Direct Drive FAN SHEAVE Direct Drive Direct Drive Direct Drive Direct Drive BELT SIZE Direct Drive Direct Drive Direct Drive Direct Drive SHEAVE ADJUSTMENT Direct Drive Direct Drive Direct Drive Direct Drive Technician: FA Date: 1/31/22 * Single speed exhaust fan ,�� Associated Air Balance Council ,��