Loading...
3015 Holiday Lane - Taco Bell Test & Balance Report 2022-03-16r, . 01A �r TEST &BALANCE INC 375 230th Ave, Somerset WI 54025 - Phone: (612) 834-0311 Fax: (414) 377-3349 www.Premierbalancing.com AM TESTING, ADJUSTING AND BALANCING BUREAU THE PROFESSIONAL% CHOICE" Testing, Adjusting & Balancing Report TABB TECHNICIAN Technician: David Ludowese Cell Phone: 651-347-5672 Email Address: lave@premierbalancing.com PROJECT Taco Bell - Eagan 3015 Holiday Lane Eagan, MN 55121 CLIENT Legacy Companies, Inc. 8850 Wentworth Avenue S. Bloomington, MN 55420 ENGINEER Case Engineering, Inc. 796 Merus Court St. Louis, MO 63026 Report Date March 16, 2022 TABB CERTIFICATION TABB certification of a Supervisor is TABB's statement that the Supervisor is able to supervise testing, adjusting and balancing of building environmental systems to produce the design objectives or optimum system performance. For TABB Certification purposes, a Supervisor is the person who, while employed by a TABB Certified Contractor, is responsible and accountable for overseeing, coordinating and ensuring that projects are performed by TABB Certified Technicians in accordance with TABB standards (including the ICB Code of Conduct and the TAB General Rules). Measurements recorded in this report are in accordance with the SMACNA 1 TABB HVAC Systems, Testing, Adjusting and Balancing manual. Certific,,,,,,o�� PA ° ANSI Oen David Ludowese TABB Technician BB1082532T / March 31, 2022 P���t�: o2r2or2o2o S red Te�G�� Gertifr�et a Premier Test & Balance LLC Peter Korzenowski TBO4587120 t Valid Unless Sig d 1 O� E.P. 12/31/2022 G �d Conklo Certifical�o ANSI°�^ Anthony Kompelien Premier Test &81 TABB Supervisor TE875224S December 31. 2022 \ -- 2-1/2— / TABB Certified "The Professional's Choice" Page 2 TABB QUALITY ASSURANCE PROGRAM BACKGROUND TABB seeks to ensure the integrity of its certification program by: (a) setting eligibility criteria for TABB Certified Supervisors and TABB Certified Contractors, (b) establishing testing procedures for TABB Certified Supervisors, (c) requiring continuing education and continuous compliance with eligibility criteria for renewal of certification, and (d) periodically reviewing its recognition of technician certification. High quality work on the part of TABB Certified Technicians and TABB Certified Supervisors and TABB Certified Contractors ( TABB Professionals ) is essential to integrity of the TABB Certification Program. TABB offers this TABB Quality Assurance Program to help assure high quality work. By accepting TABB qualification or certification, every TABB Professional accepts the responsibilities or this Program. Quality Assurance Every customer of a TABB Certified Contractor shall be entitled to expect: (1) that testing, adjusting and balancing work by the contractor and its TABB Professionals will meet TABB standards; (2) that testing, adjusting and balancing reports provided to the customer will have been prepared by a TABB Certified Technician, and reviewed by a TABB Certified Supervisor; and (3) that the report(s) will include measurements taken accurately with the date and mode of operation of the systems. TABB 8403 Arlington Boulevard Fairfax, VA 22031 Phone - (703) 299-5646 Fax - (703) 683-7615 TABB Certified "The Professional's Choice" Page 3 INSTRUMENT CALIBRATION REPORT INSTRUMENT MODEL MANUFACTURER SERIAL NUMBER CALIBRATION DATES Current Expiration Rotating Measuring Instrument PLT -5000 Check -Line B15985012P 10/05/21 10/05/22 Temperature Measuring Instrument Temperature Measuring Probe HM70 HMP75 Vaisala Vaisala M4820017 M5040569 10/08/21 10/08/21 10/08/22 10/08/22 Electrical Measuring Instruments 117 322 Fluke Fluke 18561871 17830473 10/05/21 10/05/21 10/05/22 10/05/22 Air Pressure Measuring Instrument S -PVF -1 Evergreen Telemetry 1800207 09/02/21 09/02/22 Air Velocity Measuring Instrument S -PVF -1 Evergreen Telemetry 1800207 09/02/21 09/02/22 Hydronic Pressure Measuring Instrument 0 to 300 psi HM -675 Alnor 71514005 10/05/21 10/05/22 TABB Certified "The Professional's Choice" Page 4 Premier Test & Balance Project: Taco Bell - Eagan Premier Job Number: 4502 Technician: David Ludowese Report Date: 3/16/22 Index Page System 1 Equipment Description Completion Date 6-7 RTU -1 Constant Air Volume 3/14/22 8-9 RTU -2 Constant Air Volume 3/15/22 10 RTU -3 Constant Air Volume 3/15/22 11 EF -1 Constant Air Volume 3/15/22 12 EF -2 Constant Air Volume 3/15/22 13 EF -3 Constant Air Volume 3/15/22 TABB Certified "The Professional's Choice" Page 5 Premier Test & Balance Project: Taco Bell - Eagan System: RTU -1 (Supply) Technician: David Ludowese Air Handling Unit Test Data Premier Job Number: 4502 Completion Date: 3/14/22 Remarks: a) BAS minimum outside air damper position at max fan speed: 15% Mid fan speed: 19% Min fan speed: 24% b) Fan total is the sum of the diffusers on next page. C) d) e) TABB Certified "The Professional's Choice" Page 6 System Scheduled Data Model number: YHC120 Serial number: 214712743L Manufacturer: Trane Outlet Total CFM: 3,900 Total Design CFM: 4,000 Min.Outside Air CFM: 800 Fan Static Pressure: 1.00 Equipment Location: Roof Performance Data Description Scheduled 1 Submittal Data Actual Field Measurements Motor HP: 2.75 2.75 Motor RPM: 1750 1750 Motor Hertz: 60.0 60.0 Motor Service Factor: 1.15 1.15 Motor Phase: 3 3 Motor Voltage: 208 212 214 212 Motor Amperage: 7.3 5.6 5.8 5.6 Motor BHP: - 2.18 Fan RPM: 1100 Direct Drive Static Pressure Data Component Static Pressure (inches of water) Pressure Pressure Rise 1 Drop Total (inches) In Out Fan: -0.35 0.31 Rise 0.66 Airflow Measurements Suppiv Air Opening Area Design Final Reading Preliminary Reading CFM CFM % CFM No. Served 1 Dining Room 3900 3924 101% 3596 Total 3900 3924 1 101% 3596 Minimum Outside Air Size K Design Final Reading Preliminary Reading Factor Velocity CFM Velocity CFM % Velocity CFM Total 38x24 6.33 126 800 131 830 104% 146 925 Remarks: a) BAS minimum outside air damper position at max fan speed: 15% Mid fan speed: 19% Min fan speed: 24% b) Fan total is the sum of the diffusers on next page. C) d) e) TABB Certified "The Professional's Choice" Page 6 Premier Test & Balance Project: Taco Bell - Eagan System: RTU -1 (Supply) Technician: David Ludowese Air Outlet Test Report Premier Job Number: 4502 Completion Date: 3/15/22 Airflow Measurements Opening Area Size K Design Final Reading Preliminary Reading No. Served Factor Velocity CFM Velocity CFM % Velocity CFM 1 Bathroom Hallway Flow Hood 1.00 200 200 193 193 97% 177 177 2 Entry Flow Hood 1.00 150 150 151 151 101% 155 155 3 Dining Room Flow Hood 1.00 400 400 438 438 110% 436 436 4 Dining Room Flow Hood 1.00 400 400 389 389 97% 319 319 5 Dining Room Flow Hood 1.00 400 400 376 376 94% 290 290 6 Dining Room Flow Hood 1.00 400 400 433 433 108% 404 404 7 Dining Room Flow Hood 1.00 400 400 367 367 92% 316 316 8 Dining Room Flow Hood 1.00 400 400 441 441 110% 445 445 9 Dining Room Flow Hood 1.00 400 400 406 406 102% 279 279 10 Dining Room Flow Hood 1.00 400 400 389 389 97% 348 348 11 Dining Room Flow Hood 1.00 175 175 172 172 98% 195 195 12 Dining Room Flow Hood 1.00 175 175 169 169 97% 232 232 Total L3900 1 3924 101% 3596 Remarks: a) No room number listed for openings 1 thru 12. Please check & fill in. b) C) d) e) TABB Certified "The Professional's Choice" Page 7 Premier Test & Balance Project: Taco Bell - Eagan System: RTU -2 (Supply) Technician: David Ludowese Air Handling Unit Test Data Premier Job Number: 4502 Completion Date: 3/15/22 Remarks: a) BAS minimum outside air damper position at max fan speed: 11 % Mid fan speed: 19% Min fan speed: 26% b) Fan total is the sum of the diffusers on next page. C) d) e) TABB Certified "The Professional's Choice" Page 8 System Scheduled Data Model number: YHC120 Serial number: 214210283L Manufacturer: Trane Outlet Total CFM: 4,000 Total Design CFM: 4,000 Min.Outside Air CFM: 800 Fan Static Pressure: 1.00 Equipment Location: Roof Performance Data Description Scheduled 1 Submittal Data Actual Field Measurements Motor HP: 2.75 2.75 Motor RPM: 1750 1750 Motor Hertz: 60.0 60.0 Motor Service Factor: 1.15 1.15 Motor Phase: 3 3 Motor Voltage: 208 212 214 212 Motor Amperage: 7.3 5.2 5.2 5.2 Motor BHP: - 2.00 Fan RPM: 1100 Direct Drive Static Pressure Data Component Static Pressure (inches of water) Pressure Pressure Rise 1 Drop Total (inches) In Out Fan: -0.32 0.28 Rise 0.60 Airflow Measurements SUPPIVAir Opening Area Size K Design Final Reading Preliminary Reading No. Served Factor Velocity CFM Velocity CFM % Velocity CFM 1 Cooking Area 2420 3.33 1200 4000 1143 3810 95% 883 2943 Total 4000 3810 1 95% 2943 Minimum Outside Air Size K Design Final Reading Preliminary Reading Factor Velocity CFM Velocity CFM % Velocity CFM Total 38x24 6.33 126 800 136 861 108% 136 861 Remarks: a) BAS minimum outside air damper position at max fan speed: 11 % Mid fan speed: 19% Min fan speed: 26% b) Fan total is the sum of the diffusers on next page. C) d) e) TABB Certified "The Professional's Choice" Page 8 Premier Test & Balance Project: Taco Bell - Eagan System: RTU -2 (Supply) Technician: David Ludowese Air Outlet Test Report Premier Job Number: 4502 Completion Date: 3/15/22 Airflow Measurements Opening Area Size K Design Final Reading Preliminary Reading Velocity CFM Velocity CFM % Velocity CFM No. Served Factor 1 Cooking Area Flow Hood 1.00 380 380 361 361 95% 376 376 2 Cooking Area Flow Hood 1.00 380 380 343 343 90% 104 104 3 Cooking Area Flow Hood 1.00 380 380 342 342 90% 127 127 4 Cooking Area Flow Hood 1.00 380 380 358 358 94% 312 312 5 Cooking Area Flow Hood 1.00 350 350 342 342 98% 344 344 6 Cooking Area Flow Hood 1.00 350 350 339 339 97% 352 352 7 Cooking Area Flow Hood 1.00 350 350 343 343 98% 361 361 8 Cooking Area Flow Hood 1.00 350 350 334 334 95% 399 399 9 Cooking Area Flow Hood 1.00 350 350 341 341 97% 411 411 10 Cooking Area Flow Hood 1.00 350 350 340 340 97% 394 394 11 Cooking Area Flow Hood 1.00 380 380 359 359 94% 274 274 Total 4000 3802 95% 3454 Remarks TABB Certified "The Professional's Choice" Page 9 Premier Test & Balance Project: Taco Bell - Eagan System: RTU -3 (Supply) Technician: David Ludowese Air Handling Unit Test Data Premier Job Number: 4502 Completion Date: 3/15/22 Remarks: a) BAS minimum outside air damper position at max fan speed: 12% Mid fan speed: 21 % Min fan speed: 27% b) C) d) e) TABB Certified "The Professional's Choice" Page 10 System Scheduled Data Model number: YHC060 Serial number: 214810578L Manufacturer: Trane Outlet Total CFM: 2,000 Total Design CFM: 2,000 Min.Outside Air CFM: 300 Fan Static Pressure: 0.50 Equipment Location: Roof Performance Data Description Scheduled 1 Submittal Data Actual Field Measurements Motor HP: 1.00 1.00 Motor RPM: 1750 1750 Motor Hertz: 60.0 60.0 Motor Service Factor: 1.15 1.15 Motor Phase: 3 3 Motor Voltage: 208 214 215 214 Motor Amperage: 5.0 4.1 4.1 4.1 Motor BHP: - 0.84 Fan RPM: 858 831 Static Pressure Data Component Static Pressure (inches of water) Pressure Pressure Rise 1 Drop Total (inches) In Out Fan: -0.19 0.26 Rise 0.45 Airflow Measurements Opening Area Size K Design Final Reading Preliminary Reading No. Served Factor Velocity CFM Velocity CFM % Velocity CFM 1 Storage Flow Hood 1.00 475 475 459 459 97% 413 413 2 Storage Flow Hood 1.00 475 475 483 483 102% 479 479 3 Washing Area Flow Hood 1.00 475 475 464 464 98% 448 448 4 Washing Area Flow Hood 1.00 475 475 482 482 101% 474 474 5 Office Flow Hood 1.00 100 100 108 108 108% 234 234 Total L 2000 1 1996 1 100% 2048 Minimum Outside Air Size K Design Final Reading Preliminary Reading Factor Velocity CFM Velocity CFM % Velocity CFM Total 38x24 6.33 47 300 49 310 103% 62 393 Remarks: a) BAS minimum outside air damper position at max fan speed: 12% Mid fan speed: 21 % Min fan speed: 27% b) C) d) e) TABB Certified "The Professional's Choice" Page 10 Premier Test & Balance Project: Taco Bell - Eagan System: EF -1 Technician: David Ludowese Fan Test Data Premier Job Number: 4502 Completion Date: 3/15/22 Remarks TABB Certified "The Professional's Choice" Page 11 System Scheduled Data Model number: SVNCA14FA Manufacturer: Stratovent Outlet Total CFM: 1,530 Total Design CFM: 1,530 Equipment Location: Roof Fan Static Pressure: 1.00 Performance Data Description Scheduled 1 Submittal Data Actual Field Measurements Motor HP: 1.00 1.00 Motor RPM: 1750 1750 Motor Hertz: 60.0 60.0 Motor Service Factor: 1.15 1.15 Motor Phase: 3 3 Motor Voltage: 208 212 213 212 Motor Amperage: 3.3 2.8 2.8 2.8 Motor BHP: - 0.87 Fan RPM: 1156 Direct Drive Static Pressure Data Component Static Pressure (inches of water) Pressure Pressure Rise 1 Drop Total (inches) In Out Fan: -0.71 0.03 Rise 0.74 Airflow Measurements Fan Total Opening Area Size K Design Final Reading Preliminary Reading No. Served Factor VelOcitL CFM Velocity CFM % Velocity CFM 1 Hood 94x14 7.20 213 1530 207 1490 97% 207 1490 Total 1530 1490 1 97% 1490 Remarks TABB Certified "The Professional's Choice" Page 11 Premier Test & Balance Project: Taco Bell - Eagan System: EF -2 Technician: David Ludowese Fan Test Data Premier Job Number: 4502 Completion Date: 3/15/22 Remarks: a) Speed controller used to adjust fan speed. TABB Certified "The Professional's Choice" Page 12 System Scheduled Data Model number: 90C15DH Serial number: 297SJ64661-1701 Manufacturer: Cook Outlet Total CFM: 300 Total Design CFM: 300 Equipment Location: Roof Fan Static Pressure: 0.38 Performance Data Description Scheduled 1 Submittal Data Actual Field Measurements Motor HP: 0.25 0.25 Motor RPM: 1750 1750 Motor Hertz: 60.0 60.0 Motor Service Factor: 1.15 1.15 Motor Phase: 1 1 Motor Voltage: 120 122 Motor Amperage: 1.7 1.2 Motor BHP: - 0.18 Fan RPM: 1278 Direct Drive Static Pressure Data Component Static Pressure (inches of water) Pressure Pressure Rise 1 Drop Total (inches) In Out Fan: -0.21 0.06 Rise 0.27 Airflow Measurements Fan Total Opening Area Size K Design Final Reading Preliminary Reading No. Served Factor VelOcitL CFM Velocity CFM % Velocity CFM 1 Mens Restroom Flow Hood 1.00 150 150 159 159 106% 238 238 2 Womens Restroom Flow Hood 1.00 150 150 165 165 110% 247 247 Total 300 324 108% 485 Remarks: a) Speed controller used to adjust fan speed. TABB Certified "The Professional's Choice" Page 12 Premier Test & Balance Project: Taco Bell - Eagan System: EF -3 Technician: David Ludowese Fan Test Data Premier Job Number: 4502 Completion Date: 3/15/22 Remarks: a) Speed controller used to adjust fan speed. TABB Certified "The Professional's Choice" Page 13 System Scheduled Data Model number: 90C15DH Serial number: 297SJ64661-11901 Manufacturer: Cook Outlet Total CFM: 200 Total Design CFM: 200 Equipment Location: Roof Fan Static Pressure: 0.38 Performance Data Description Scheduled 1 Submittal Data Actual Field Measurements Motor HP: 0.25 0.25 Motor RPM: 1750 1750 Motor Hertz: 60.0 60.0 Motor Service Factor: 1.15 1.15 Motor Phase: 1 1 Motor Voltage: 120 122 Motor Amperage: 1.7 1.1 Motor BHP: - 0.16 Fan RPM: 1194 Direct Drive Static Pressure Data Component Static Pressure (inches of water) Pressure Pressure Rise 1 Drop Total (inches) In Out Fan: -0.21 0.03 Rise 0.24 Airflow Measurements Fan Total Opening Area Size K Design Final Reading Preliminary Reading No. Served Factor VelOcitL CFM Velocity CFM % Velocity CFM 1 Trash Area Flow Hood 1.00 200 200 208 208 104% 495 495 Total 200 208 1 104% 495 Remarks: a) Speed controller used to adjust fan speed. TABB Certified "The Professional's Choice" Page 13