3015 Holiday Lane - Taco Bell Test & Balance Report 2022-03-16r, .
01A
�r
TEST &BALANCE INC
375 230th Ave, Somerset WI 54025 - Phone: (612) 834-0311 Fax: (414) 377-3349
www.Premierbalancing.com
AM
TESTING, ADJUSTING AND BALANCING BUREAU
THE PROFESSIONAL% CHOICE"
Testing, Adjusting & Balancing Report
TABB TECHNICIAN
Technician: David Ludowese
Cell Phone: 651-347-5672
Email Address: lave@premierbalancing.com
PROJECT
Taco Bell - Eagan
3015 Holiday Lane
Eagan, MN 55121
CLIENT
Legacy Companies, Inc.
8850 Wentworth Avenue S.
Bloomington, MN 55420
ENGINEER
Case Engineering, Inc.
796 Merus Court
St. Louis, MO 63026
Report Date
March 16, 2022
TABB CERTIFICATION
TABB certification of a Supervisor is TABB's statement that the Supervisor is able to
supervise testing, adjusting and balancing of building environmental systems to produce the
design objectives or optimum system performance. For TABB Certification purposes, a
Supervisor is the person who, while employed by a TABB Certified Contractor, is
responsible and accountable for overseeing, coordinating and ensuring that projects are
performed by TABB Certified Technicians in accordance with TABB standards (including the
ICB Code of Conduct and the TAB General Rules).
Measurements recorded in this report are in accordance with the SMACNA 1 TABB HVAC Systems,
Testing, Adjusting and Balancing manual.
Certific,,,,,,o��
PA ° ANSI Oen
David Ludowese
TABB Technician
BB1082532T /
March 31, 2022
P���t�: o2r2or2o2o S
red Te�G��
Gertifr�et
a
Premier Test & Balance LLC
Peter Korzenowski
TBO4587120
t Valid Unless Sig d
1 O� E.P. 12/31/2022
G
�d Conklo
Certifical�o
ANSI°�^
Anthony Kompelien
Premier Test &81
TABB Supervisor
TE875224S
December 31. 2022
\ -- 2-1/2— /
TABB Certified "The Professional's Choice"
Page 2
TABB QUALITY ASSURANCE PROGRAM
BACKGROUND
TABB seeks to ensure the integrity of its certification program by: (a) setting eligibility criteria for TABB
Certified Supervisors and TABB Certified Contractors, (b) establishing testing procedures for TABB
Certified Supervisors, (c) requiring continuing education and continuous compliance with eligibility criteria
for renewal of certification, and (d) periodically reviewing its recognition of technician certification. High
quality work on the part of TABB Certified Technicians and TABB Certified Supervisors and TABB Certified
Contractors ( TABB Professionals ) is essential to integrity of the TABB Certification Program. TABB offers
this TABB Quality Assurance Program to help assure high quality work. By accepting TABB qualification or
certification, every TABB Professional accepts the responsibilities or this Program.
Quality Assurance
Every customer of a TABB Certified Contractor shall be entitled to expect: (1) that testing, adjusting and
balancing work by the contractor and its TABB Professionals will meet TABB standards; (2) that testing,
adjusting and balancing reports provided to the customer will have been prepared by a TABB Certified
Technician, and reviewed by a TABB Certified Supervisor; and (3) that the report(s) will include
measurements taken accurately with the date and mode of operation of the systems.
TABB
8403 Arlington Boulevard
Fairfax, VA 22031
Phone - (703) 299-5646
Fax - (703) 683-7615
TABB Certified "The Professional's Choice"
Page 3
INSTRUMENT
CALIBRATION REPORT
INSTRUMENT
MODEL
MANUFACTURER
SERIAL NUMBER
CALIBRATION DATES
Current
Expiration
Rotating Measuring Instrument
PLT -5000
Check -Line
B15985012P
10/05/21
10/05/22
Temperature Measuring Instrument
Temperature Measuring Probe
HM70
HMP75
Vaisala
Vaisala
M4820017
M5040569
10/08/21
10/08/21
10/08/22
10/08/22
Electrical Measuring Instruments
117
322
Fluke
Fluke
18561871
17830473
10/05/21
10/05/21
10/05/22
10/05/22
Air Pressure Measuring Instrument
S -PVF -1
Evergreen Telemetry
1800207
09/02/21
09/02/22
Air Velocity Measuring Instrument
S -PVF -1
Evergreen Telemetry
1800207
09/02/21
09/02/22
Hydronic Pressure Measuring Instrument
0 to 300 psi
HM -675
Alnor
71514005
10/05/21
10/05/22
TABB Certified "The Professional's Choice"
Page 4
Premier Test & Balance
Project: Taco Bell - Eagan Premier Job Number: 4502
Technician: David Ludowese Report Date: 3/16/22
Index
Page
System 1 Equipment
Description
Completion Date
6-7
RTU -1
Constant Air Volume
3/14/22
8-9
RTU -2
Constant Air Volume
3/15/22
10
RTU -3
Constant Air Volume
3/15/22
11
EF -1
Constant Air Volume
3/15/22
12
EF -2
Constant Air Volume
3/15/22
13
EF -3
Constant Air Volume
3/15/22
TABB Certified "The Professional's Choice"
Page 5
Premier Test & Balance
Project: Taco Bell - Eagan
System: RTU -1 (Supply)
Technician: David Ludowese
Air Handling Unit Test Data
Premier Job Number: 4502
Completion Date: 3/14/22
Remarks: a) BAS minimum outside air damper position at max fan speed: 15% Mid fan speed: 19% Min fan speed: 24%
b) Fan total is the sum of the diffusers on next page.
C)
d)
e)
TABB Certified "The Professional's Choice"
Page 6
System Scheduled Data
Model number: YHC120
Serial number:
214712743L
Manufacturer: Trane
Outlet Total CFM:
3,900
Total Design CFM: 4,000
Min.Outside Air CFM:
800
Fan Static Pressure: 1.00
Equipment Location:
Roof
Performance Data
Description
Scheduled 1 Submittal Data
Actual Field Measurements
Motor HP:
2.75
2.75
Motor RPM:
1750
1750
Motor Hertz:
60.0
60.0
Motor Service Factor:
1.15
1.15
Motor Phase:
3
3
Motor Voltage:
208
212 214
212
Motor Amperage:
7.3
5.6 5.8
5.6
Motor BHP:
-
2.18
Fan RPM:
1100
Direct Drive
Static Pressure
Data
Component
Static Pressure
(inches of water)
Pressure
Pressure
Rise 1 Drop
Total (inches)
In
Out
Fan:
-0.35
0.31
Rise
0.66
Airflow Measurements
Suppiv Air
Opening
Area
Design
Final Reading
Preliminary Reading
CFM
CFM
%
CFM
No.
Served
1
Dining Room
3900
3924
101%
3596
Total 3900
3924 1 101%
3596
Minimum Outside Air
Size
K
Design Final Reading
Preliminary Reading
Factor
Velocity
CFM Velocity
CFM
%
Velocity
CFM
Total
38x24
6.33
126
800 131
830
104%
146
925
Remarks: a) BAS minimum outside air damper position at max fan speed: 15% Mid fan speed: 19% Min fan speed: 24%
b) Fan total is the sum of the diffusers on next page.
C)
d)
e)
TABB Certified "The Professional's Choice"
Page 6
Premier Test & Balance
Project: Taco Bell - Eagan
System: RTU -1 (Supply)
Technician: David Ludowese
Air Outlet Test Report
Premier Job Number: 4502
Completion Date: 3/15/22
Airflow Measurements
Opening
Area
Size
K
Design
Final Reading
Preliminary Reading
No.
Served
Factor
Velocity
CFM
Velocity
CFM
%
Velocity
CFM
1
Bathroom Hallway
Flow Hood
1.00
200
200
193
193
97%
177
177
2
Entry
Flow Hood
1.00
150
150
151
151
101%
155
155
3
Dining Room
Flow Hood
1.00
400
400
438
438
110%
436
436
4
Dining Room
Flow Hood
1.00
400
400
389
389
97%
319
319
5
Dining Room
Flow Hood
1.00
400
400
376
376
94%
290
290
6
Dining Room
Flow Hood
1.00
400
400
433
433
108%
404
404
7
Dining Room
Flow Hood
1.00
400
400
367
367
92%
316
316
8
Dining Room
Flow Hood
1.00
400
400
441
441
110%
445
445
9
Dining Room
Flow Hood
1.00
400
400
406
406
102%
279
279
10
Dining Room
Flow Hood
1.00
400
400
389
389
97%
348
348
11
Dining Room
Flow Hood
1.00
175
175
172
172
98%
195
195
12
Dining Room
Flow Hood
1.00
175
175
169
169
97%
232
232
Total
L3900
1
3924
101%
3596
Remarks: a) No room number listed for openings 1 thru 12. Please check & fill in.
b)
C)
d)
e)
TABB Certified "The Professional's Choice"
Page 7
Premier Test & Balance
Project: Taco Bell - Eagan
System: RTU -2 (Supply)
Technician: David Ludowese
Air Handling Unit Test Data
Premier Job Number: 4502
Completion Date: 3/15/22
Remarks: a) BAS minimum outside air damper position at max fan speed: 11 % Mid fan speed: 19% Min fan speed: 26%
b) Fan total is the sum of the diffusers on next page.
C)
d)
e)
TABB Certified "The Professional's Choice"
Page 8
System Scheduled Data
Model number: YHC120
Serial number:
214210283L
Manufacturer: Trane
Outlet Total CFM:
4,000
Total Design CFM: 4,000
Min.Outside Air CFM:
800
Fan Static Pressure: 1.00
Equipment Location:
Roof
Performance Data
Description
Scheduled 1 Submittal Data
Actual Field Measurements
Motor HP:
2.75
2.75
Motor RPM:
1750
1750
Motor Hertz:
60.0
60.0
Motor Service Factor:
1.15
1.15
Motor Phase:
3
3
Motor Voltage:
208
212 214
212
Motor Amperage:
7.3
5.2 5.2
5.2
Motor BHP:
-
2.00
Fan RPM:
1100
Direct Drive
Static Pressure
Data
Component
Static Pressure
(inches of water)
Pressure
Pressure
Rise 1 Drop
Total (inches)
In
Out
Fan:
-0.32
0.28
Rise
0.60
Airflow Measurements
SUPPIVAir
Opening
Area
Size
K
Design
Final Reading
Preliminary Reading
No.
Served
Factor
Velocity
CFM
Velocity
CFM
%
Velocity
CFM
1
Cooking Area
2420
3.33
1200
4000
1143
3810
95%
883
2943
Total 4000
3810 1 95%
2943
Minimum Outside Air
Size
K
Design Final Reading
Preliminary Reading
Factor
Velocity
CFM Velocity
CFM
%
Velocity
CFM
Total
38x24
6.33
126
800 136
861
108%
136
861
Remarks: a) BAS minimum outside air damper position at max fan speed: 11 % Mid fan speed: 19% Min fan speed: 26%
b) Fan total is the sum of the diffusers on next page.
C)
d)
e)
TABB Certified "The Professional's Choice"
Page 8
Premier Test & Balance
Project: Taco Bell - Eagan
System: RTU -2 (Supply)
Technician: David Ludowese
Air Outlet Test Report
Premier Job Number: 4502
Completion Date: 3/15/22
Airflow Measurements
Opening
Area
Size
K
Design
Final Reading
Preliminary Reading
Velocity
CFM
Velocity
CFM
%
Velocity
CFM
No.
Served
Factor
1
Cooking Area
Flow Hood
1.00
380
380
361
361
95%
376
376
2
Cooking Area
Flow Hood
1.00
380
380
343
343
90%
104
104
3
Cooking Area
Flow Hood
1.00
380
380
342
342
90%
127
127
4
Cooking Area
Flow Hood
1.00
380
380
358
358
94%
312
312
5
Cooking Area
Flow Hood
1.00
350
350
342
342
98%
344
344
6
Cooking Area
Flow Hood
1.00
350
350
339
339
97%
352
352
7
Cooking Area
Flow Hood
1.00
350
350
343
343
98%
361
361
8
Cooking Area
Flow Hood
1.00
350
350
334
334
95%
399
399
9
Cooking Area
Flow Hood
1.00
350
350
341
341
97%
411
411
10
Cooking Area
Flow Hood
1.00
350
350
340
340
97%
394
394
11
Cooking Area
Flow Hood
1.00
380
380
359
359
94%
274
274
Total
4000
3802
95%
3454
Remarks
TABB Certified "The Professional's Choice"
Page 9
Premier Test & Balance
Project: Taco Bell - Eagan
System: RTU -3 (Supply)
Technician: David Ludowese
Air Handling Unit Test Data
Premier Job Number: 4502
Completion Date: 3/15/22
Remarks: a) BAS minimum outside air damper position at max fan speed: 12% Mid fan speed: 21 % Min fan speed: 27%
b)
C)
d)
e)
TABB Certified "The Professional's Choice"
Page 10
System Scheduled Data
Model number: YHC060
Serial number:
214810578L
Manufacturer: Trane
Outlet Total CFM:
2,000
Total Design CFM: 2,000
Min.Outside Air CFM:
300
Fan Static Pressure: 0.50
Equipment Location:
Roof
Performance Data
Description
Scheduled 1 Submittal Data
Actual Field Measurements
Motor HP:
1.00
1.00
Motor RPM:
1750
1750
Motor Hertz:
60.0
60.0
Motor Service Factor:
1.15
1.15
Motor Phase:
3
3
Motor Voltage:
208
214 215
214
Motor Amperage:
5.0
4.1 4.1
4.1
Motor BHP:
-
0.84
Fan RPM:
858
831
Static Pressure
Data
Component
Static Pressure
(inches of water)
Pressure
Pressure
Rise 1 Drop
Total (inches)
In
Out
Fan:
-0.19
0.26
Rise
0.45
Airflow Measurements
Opening
Area
Size
K
Design
Final
Reading
Preliminary Reading
No.
Served
Factor
Velocity
CFM
Velocity
CFM
%
Velocity
CFM
1
Storage
Flow Hood
1.00
475
475
459
459
97%
413
413
2
Storage
Flow Hood
1.00
475
475
483
483
102%
479
479
3
Washing Area
Flow Hood
1.00
475
475
464
464
98%
448
448
4
Washing Area
Flow Hood
1.00
475
475
482
482
101%
474
474
5
Office
Flow Hood
1.00
100
100
108
108
108%
234
234
Total L 2000
1 1996 1 100%
2048
Minimum Outside Air
Size
K
Design Final Reading
Preliminary Reading
Factor
Velocity
CFM Velocity
CFM
%
Velocity
CFM
Total
38x24
6.33
47
300 49
310
103%
62
393
Remarks: a) BAS minimum outside air damper position at max fan speed: 12% Mid fan speed: 21 % Min fan speed: 27%
b)
C)
d)
e)
TABB Certified "The Professional's Choice"
Page 10
Premier Test & Balance
Project: Taco Bell - Eagan
System: EF -1
Technician: David Ludowese
Fan Test Data
Premier Job Number: 4502
Completion Date: 3/15/22
Remarks
TABB Certified "The Professional's Choice"
Page 11
System Scheduled Data
Model number:
SVNCA14FA
Manufacturer:
Stratovent
Outlet Total CFM:
1,530
Total Design CFM:
1,530
Equipment Location:
Roof
Fan Static Pressure:
1.00
Performance Data
Description
Scheduled 1 Submittal Data
Actual Field Measurements
Motor HP:
1.00
1.00
Motor RPM:
1750
1750
Motor Hertz:
60.0
60.0
Motor Service Factor:
1.15
1.15
Motor Phase:
3
3
Motor Voltage:
208
212 213
212
Motor Amperage:
3.3
2.8 2.8
2.8
Motor BHP:
-
0.87
Fan RPM:
1156
Direct Drive
Static Pressure
Data
Component
Static Pressure
(inches of water)
Pressure
Pressure
Rise 1 Drop
Total (inches)
In
Out
Fan:
-0.71
0.03
Rise
0.74
Airflow Measurements
Fan Total
Opening
Area
Size
K
Design
Final Reading
Preliminary Reading
No.
Served
Factor
VelOcitL
CFM
Velocity
CFM
%
Velocity
CFM
1
Hood
94x14
7.20
213
1530
207
1490
97%
207
1490
Total
1530
1490
1 97%
1490
Remarks
TABB Certified "The Professional's Choice"
Page 11
Premier Test & Balance
Project: Taco Bell - Eagan
System: EF -2
Technician: David Ludowese
Fan Test Data
Premier Job Number: 4502
Completion Date: 3/15/22
Remarks: a) Speed controller used to adjust fan speed.
TABB Certified "The Professional's Choice"
Page 12
System Scheduled Data
Model number: 90C15DH
Serial number:
297SJ64661-1701
Manufacturer: Cook
Outlet Total CFM:
300
Total Design CFM: 300
Equipment Location:
Roof
Fan Static Pressure: 0.38
Performance Data
Description
Scheduled 1 Submittal Data
Actual Field Measurements
Motor HP:
0.25
0.25
Motor RPM:
1750
1750
Motor Hertz:
60.0
60.0
Motor Service Factor:
1.15
1.15
Motor Phase:
1
1
Motor Voltage:
120
122
Motor Amperage:
1.7
1.2
Motor BHP:
-
0.18
Fan RPM:
1278
Direct Drive
Static Pressure
Data
Component
Static Pressure
(inches of water)
Pressure
Pressure
Rise 1 Drop
Total (inches)
In
Out
Fan:
-0.21
0.06
Rise
0.27
Airflow Measurements
Fan Total
Opening
Area
Size
K
Design
Final Reading
Preliminary Reading
No.
Served
Factor
VelOcitL
CFM
Velocity
CFM
%
Velocity
CFM
1
Mens Restroom
Flow Hood
1.00
150
150
159
159
106%
238
238
2
Womens Restroom
Flow Hood
1.00
150
150
165
165
110%
247
247
Total
300
324
108%
485
Remarks: a) Speed controller used to adjust fan speed.
TABB Certified "The Professional's Choice"
Page 12
Premier Test & Balance
Project: Taco Bell - Eagan
System: EF -3
Technician: David Ludowese
Fan Test Data
Premier Job Number: 4502
Completion Date: 3/15/22
Remarks: a) Speed controller used to adjust fan speed.
TABB Certified "The Professional's Choice"
Page 13
System Scheduled Data
Model number: 90C15DH
Serial number:
297SJ64661-11901
Manufacturer: Cook
Outlet Total CFM:
200
Total Design CFM: 200
Equipment Location:
Roof
Fan Static Pressure: 0.38
Performance Data
Description
Scheduled 1 Submittal Data
Actual Field Measurements
Motor HP:
0.25
0.25
Motor RPM:
1750
1750
Motor Hertz:
60.0
60.0
Motor Service Factor:
1.15
1.15
Motor Phase:
1
1
Motor Voltage:
120
122
Motor Amperage:
1.7
1.1
Motor BHP:
-
0.16
Fan RPM:
1194
Direct Drive
Static Pressure
Data
Component
Static Pressure
(inches of water)
Pressure
Pressure
Rise 1 Drop
Total (inches)
In
Out
Fan:
-0.21
0.03
Rise
0.24
Airflow Measurements
Fan Total
Opening
Area
Size
K
Design
Final Reading
Preliminary Reading
No.
Served
Factor
VelOcitL
CFM
Velocity
CFM
%
Velocity
CFM
1
Trash Area
Flow Hood
1.00
200
200
208
208
104%
495
495
Total
200
208
1 104%
495
Remarks: a) Speed controller used to adjust fan speed.
TABB Certified "The Professional's Choice"
Page 13