Loading...
1380 Marice Dr - Firestopping SubmittalProject: Commons on Marice Firestop Submittal: Associated Mechanical Applications and Recommendations Gvpsum Walls Assemblv: #1. Metallic Pipe: (1 and 2-hour) IPC Drw. Ref iJL System WL-1089-EJ (1/5/98) IPC FS 1900 (Fire Stop Intumescent Caulk) #2. Metallic Vent Pipe (Steel): IPC Drw. Ref UL System WL-7006-EJ (4/9/97) IPC FS 1900 (Flame Safe Intumescent Caulk) #3. PVC Plastic Pipe: IPC Drw. Re£ iJL System WL-2038 (2/21/97) IPC FS 1900 (Flame Safe Intumescent Caulk) #4. Insulated Metallic Pipe (Steel, Iron, or Copper): IPC Drw. Ref. UL System WL-5048-EJ (8/18/97) IPC F5 1900 (Flame Safe Intumescent Caulk) Floor-Ceiling Assemblv: #5. Steel, Copper Pipe or Vent Pipe: IPC Drw. ReP iJL 5ystem FC-1023-EJ (9/11/97) IPC FS 1900 (Flame Safe Intumescent Caulk) #6. PVC Pipe: IPC Drw. Ref iJL System FG2082-EJ (9/10/97) IPC FS 1900 (Flame Safe Intumescent Caulk) #7. Insulated Metallic Pipe (Steel, Iron, or Copper): IPC Drw. Ref: iJL Svstem FC-5012 IPC FS 1900 (Flame 9afe Intumescent Caulk) Pre-Cast Hollow Core Concrete Floor or Block Wall (2-Hour): #8. Metalfic Pipe (Steel, Iron and Copper): IPC Drw. Ref UL System CAJ-1235-EJ (2/I I/97) IPC FS 1900 (Flame Safe Intumescent Caulk) #9. Insulated Metallic Pipe (Steel, Iron, or Copper): IPC Drw. Ref iJL System CBJ-5008-E7 (2/11/98) IPC FS 1900 (Flame Safe Intumescent Caulk) Products i of 1(SBP: CO-AS-] I •. .. p .?... . w. .? ....vwi.i eW" oiw ..II.JU ? ? n Dc INTERNATIONAL PROTECTNE COATINGS CORPORATION I r 725 Carol Avenue Oceen Twp. , N.J. 07712 800-334•8796 908-531-3666 (FAX) 908-531-5192 4. 2. ?? ............... ,,.,,.,,.,..., Elevatioa viaw of penetrant 1. Fira-rated gppeum wallboasd/cYUd vall aesemblp meeting UL raquiramanta for 1 S 4 6our rating. 3. 1(ax. 74' matallia pipa iaetallad oonoentria or aaoentrio through the openinq. 1fin. 0 ia. (pt.of coatact) to a max. 1-7/8 in. annular apace is requirad. - 1 in. diameter or amaller aoppar pipe or tubiaq. - 12 ia. diametar or emallar aast iron or ateel pipa. - 4 ia. diamoter or smallas EM? conduit. 7. (opYionsl) - Hiaexal wool or baaYss sod backing matezial 4. FllmiSifa? 15I9D0 Soilsnt appliad min. 1' deep iato the snnular epaos around pip* aad for a 1 hr. aeaemblT eppl] a min. 119 in. dapth. Malsrial should be appliad at botL vall eurfaaes. NOTICE Thie in(ametion ie based upon internal and ihkd party testing which we believe to be reliable. N Is Intended tor engineering pur- posea only. The user muat determine ihe suitability oT the producl end the dealgn to ihe epplicetion. Since the actual Installetion at the produa Is beyond our control, IPC Corporation's oniy responaibility shail betorsfund orreplaes metsrlelaTound to be detective as per our standard Approved by: • Syetem design evalualedlo the ASTM-E-814 (UL•1479) J. Go a FIRE TESTS OF THROUGH•PENETRATION FIRE STOPS. Dete: • 0e91'gn based upon tealed coMiguredons 6y aaUonapy recognlzed testing lahorelories (eg. UL, FM,elc.) as wel es 5 ,7aa. 1998 Inhousetealing. UL System: ' AddRbnal irgormatbn can be referenced in UL's Fke Resistence Drcectory , euch ea but nol fimAed lo StL1089-E3 Syatemslt:WL1089&CAJ1235 FlreRating: ?y,gta..r;?yn.r•rm;n?c?a?n 1 6 9 hour¦ e o ti ?. ... jso t Section thru wall i i ?. . ? I;.. "G ? ;ii•r ,c. Y. il z. 3. 1. iTL olsesifiad steel or wood stud los 1 hour fire ratad gypgum rsllboard assembly. Provida a min. 1' annular spaoa around the duct. 2. ifax. 12 ia. ( galv. or etaal ) oirculaz - 24 gauqa HVAC duct. 3. lfio. 3-1l2 in. Hineral nool paoked into the annulas epace and racesaed min. 3/4' £rom vall curfaea. 4. f'fimeSrfsO IPC F5J900 Sealsnt. Install min. 374" deep into the aanular space and provide s 114 in. crow rxianding bsyond the wall surEaoe. Foi a 1 hour ratinq apply a miq. 312 ia. dapth with a 114 io. crovn. IPC Pyro•TECN q 1•910•969-6013 m49107 i?. ,a:oa D INTERNATIONAL PR07ECTIVE COATINGS CORPORATION 725 Carol Avenue Ocean Twp. . N J. 07712 800-334•8796 908-531-3666 (FAX)908-531-5192 Qrawiag?Lot To Sc?jg NOTICE Approvad hy:" his fntamation is based upon internel and J, Goga ird party testing whlch we believe to be Dete: •=' ?lieble. It is intended ta engineering pur- 9 Apx il 1997 oses only. The user musl determine the aflability of the product and the design to the UL Syslem: . pplicapon. Since the actuel inslallation ol the w[.7006 oductisbeyondourcontrol,IPC ' FlreRating: orporation s only responsibility sh all atorefundorreplacematerialsiound 1 or 2 hours >bedefactiveasperourstandard FIeldApprv. ; . Y NOTES: • System design evaluatedto the ASTM•E•814 (UL•1479) FIRE TESTS OF THROUGH•PENETRATION FIflE STOPS. .• Design 6asedupon tested coMigurelions by neUoneAy recognlzed lesling lehoralorles (eg. UL. FM,etc.) as wel as In house IesUng. • Add'Aionel intormellon can be referenced'm UL's Fire Resistence Directory , such as bW rwt fimtted to Syslems 0: WL7006 ProJece i. Section ihru vall 4. 4P3 SECTION A-A ? 1. Wali assem6ly tA. Wood studs min. 2 x 4 in. nominal at a max. 16 in. on center or steel studs min. 2 x 4 in. nominal. ot a max. 24 in. on center. 18. One layer of gypsum wallboard copa6le of providing a 1 hr. F rating or two layers of gypsum wall6oard capable of providing a 2 hr. F rating. Max. penetrant opening is a 4 in. diameter. 2. Penetront . 2A. Max. 2 in. rigid nanmetallic conduit, PVC, cc-PVC, or CPVC piping as an open (vented) or closed system. Annular space- min. 5/8 in. to max. 1 in. A 0 A 3. Firestopping - FlameSaTee FS 1900 Series Sealant. 3A. At wall surfaces, apply FS 1900 into annular space to a min. depth of 5/8 in., add o 1/4 In. crown around penetront. NOTES 7. System design evaluated to the lSiM E814 (UL 1479) Fife Teeta of Through-Penetratlon Firestopa. 2. Design based Upon tested conifBuratione by natianally recognized tesling laborotoriee (e.g. UL, FM, etc.) as well as in-house lesting. ' 725 Carol Avenue OekhureL, N7 07766 Internatlonal Protective Coatings Corp. PbOne: 732-631-3887 800-334-8788 Feceimile: 738-631-6182 BBB-631-6192 flrestop Assembly Project: Approved by John Goga C.E. Drawn 6y Joe Charland M.E. Thie lnformaiion 1a beeea upoa Internel and th5rd psrty teeting wh1aL we ProduCt: FlameSOfs FS 1900 Serlee Sealanf ?. foval: PP to he relie6le, Tha ueer muet belleve determine the svitabiLty ol the praduct md the dedgn ot the eppllcntlon. Fire Raiing: 1 or 2 HOUR Insfaller: 5{nce t6e ectual Inetellatlo¢ nf the prnduct le beyond our control. UL System: WL2170 Daie: IPC Corporetlon e anly responelbllty ehall be to retund or replece mnterlela tauad IPC Drawing {/ WL2170 Rev.k 000 !0 6e defactlve as pw our etnnderd werrnnty. 2-406 ?4 c INTERNATIONAL PROTECTIVE COATINGS CORPORATION n ? 1-?J 725 Cerol Avenue Ocean Twp. N.J. 07712 ? 000-334-8796 908-531-3666 (FAX) 908-531-5192 Saction thru gypaum wall Slevation viev of penetration 1. Gypeum vallboardlatud aesambly to maat UL requiremente for 1& 1 hour fire rating. Annular apaae raquisements: Min. 1/2 in. to mex. 2-3/4 ia. enaular apace. 8. Max. 12' diam. or amaller ateel or eaet iron pipe. lSax. 4' diam. ox smalles cappe= pipe or tubing. 3. }fax. 8' fi6erglase inaulation. 4. ll+msSsfe0 IPC 651900 Sesl+nt applied 1-114' deep 3nto tLs annular spaae. Fiaish flveh witL wall surfaces. For a 1 hr. tating till the annular spaca to a 518 ia. depth. Applp a 114 in. arowa axteading beyoad the wall surfaoe. NOTICE This iniormation is based upon Internal & third party testing which we believe to be reliable. It is fntended Forengineering purposes only. The user must determine the suitability af the product and the de- sign to the appliption. Since the actuat instellation of the product is beyond our contml, IPC Corporation's only respon- sibiliry shall be to refund or replace ma- terials found to Ge defective as per aur standard warranty. NOTES: Approved by: • Syalem design evalualed lo lhe ASTM•E-814 (UL•1479) J. Goga FIRETESTSOFTHROUGH•PENETRATIONFIRESTOPS. • Deslgn 6ased upon lested conflgurallona by nellonetly Date: recognized tesling laboreloriee (eg. UL, FM,etc.) as wel ae 18 Auguet 1997 InhousetesUng. • Addftlonel Inlormation cen be referenced In UL's Fire UL System: Resistance Direclory , such as but nol GmRed lo wL5048-SJ Systems A: W L5046, CAJ5116 & CBJ5008 7dhgineering Daterminstioa 1 & 2 hour Pr oieol: r, ___ . irt, ryl u iLUiI w 1 , i:,..bo?_al., •SLyo I llyi !IL.Sy ? PC INTERNATIONAL PROTECTIVE COATINGS CORPORATION O?7 725 Carol Avenue Ocean Twp. , N.J. 07712 800-334-8796 908-531-3666 (FAX)908-531-5192 t_ .? ;i ?l ? `.' i- . i.. ' +:. 2H. 2C. 2D 2A. 1 S 3 4. !'loor-oeiling Aaeembly - A fise-rated Sloor oeilinq aasemblp desiqnad to mset a 1 hour fira xeaistance rating. - Plyraad subfloor of lumber or plpwood. - Nom. 1 x 10 in. wood joists vith 1 x 3 bridging eupporC. - Dauble typa S 5/8 in. qypaum vallbaard. Nax. 5-1/2 ia. openinq - mia. 114 in. eanular spaae. Chase Xsll - aingle or double waod etud / gyp board. A. Studa - Nom 2 x'6 in. or doubl• 2x4 ia. lvmber stude. H. Sole Plate - Nom 2 x 6 ia, or parallel 2x4 in. platea. C. Top Plate - Double top plats coasist of 2 x 6 or double aete of parallal 1x4 in. lumber plaYea. D. Double layer of tppe % 5l9 in. gypeum wallboard. Penetrant aoveraga: ELDB liin. Annular gpaoa - lfax. 4 in. 30 AWG veat 3116 ia. • - Nax. 4 in. ElIT or Sl10 eCeel 1/4 in. - Na:. J ia. Coppar, ffif or stael " Pt. of Contaat FlimsaifsOIPC fS1900 Sefflaot. Inetall iato aaaular epaae aad finiah flush with floor and aeiliag aurfaoe. , NOTES: NOTICE Approved by: • System deslgn eveluefedto the ASTM•E-814 (UL-1479) Thfa intormation is beaea upon internal and J. Goga FIRE TESTS OFTHROUGH•PENETRATION FIRE STOPS th'vd parly testing which we believe to be • Design based upon teated coMlguratlons by nellonalty relieble. It is intended for engineering pur- Date: recognized lestlng laborelories (eg. UL, FM,etc.) es wel as poaes only. The user must determine the 11 ss e. 1997 I^ house lesting, suitability o( ihe product and ihe deai n to Ihe UL $ Stem: ' AddHionel Inlormalion can be referenced In UL's Flre g Y Resislance Directory , auch as but rrot fimAed to application, Since the actual Installation ot Ihe E'C3023 Systems i: FC1023 produel la beyond ar control, IPC Caporation'eonlyresponaibilityshalf FlreRating; betoretundorreplece materialsfound 1 hour tObedeTeCpv88eP6roUr alflhderd FIeIAAonnr_ projeott IY? Yyl V" 1 L,1 1 N I LIJ'JUU-uJIJ .Alat iultli •.?IJ.Itl PC INTERNATIONAL PROTECTNE COAl1NG5 CORPORATION ?6 725 Carol Avenue Ocean Twp. , N.J. 07712 800-334-8796 900-531-9666 (FAX) 908-531-5192 Drawinq Not To Scale 11' j, i ' r' ? i? 0 .; 28. 2C. 2D "LA. 1. 2. ] 4. I 4 3 Floor-oailing Assemblp - A fire-ratad aolid or trussed I aeeamblp deeigned to meat a 1 hour fire =esistance ratiag. - Plyvood subfloor af lumbsr or plproad. - Nom. 2 x 30 ia. wood joiete nith 1 x 3 brldging support. - Siagle typa % 5/8 ia. gypavm vallboa=d. Max. 4-3/4 in. opening - Nin. 118 in. to a max. 319 in. annular epace. Chass Kall - siagle or donblo vood stud / gpp bosrd. A. Studs - Nom 1 z 6 ia. or double 1x4 ia. lvmbor stqds. B. Sola Plate - Nom 2 x 6 in. or paxallel 2x4 in. plates. C. Top Plate - Double top plale consiet of (Z) 1 x 6 or (2) double sete of parallel 2x4 in. lumber plates. ?. Siagle lapar of type 8 516 ia. gppsum wallboard. Nax. 4' diameter or smaller oa-PVC, PVC or CPVC piping as aa opea ( vanted ) or oloeed system Flwmesa1e0 IPCFS1900 Ssslent. Install iato annuldr spaae a min. 112 in dapth into the top floor surface and apply a min. 318 ia.crova. Iastsll into annular apace of ' lovex top plate a min 314 in. deptL and applq a min. 318 in. erown. NOTES: NOTICE ApproVed by: ' Syslem design evalualed lo the AS7M-E-814 (UL-1479) ' This Information ie based upon internal and J. Goga FIFiE TESTS OF 7HROUGH-PENETRATION FIRE STOPS. third perty testing which we believe to be • Design based upon tested conflguratbns by nationeny relieble. It is inlended (or engineering pur- Date: recagnaed lealing laboreloriea (eg. UL, FM,etc.) ea wel es in poaes only. The user must determine the 10 s.ps. 1997 house lesting. • Adddional inlormation can be relerenced in UL's Fire suilabillty of the product and the design io the UL System: pesistance Directory , such as but not Iimited lo appllcaUon. Since the actual installation of the tresoes-Ea systems s• FC20928 FC2042 product is beyond our eontrol, IPC Carporation'eonlyreeponsibilityehall FlreRating: betorefundorreplecematerialefound 1 hour tobedefectiveaeperourstendard FIeldApprv. Projoct: warranty, ^--..,-__, ..---- ;Or 7 11; F. Two layers of gypsum wollboord capa6le of providing a 2 hr. F rating (lacated on ali walis and ceilings of chase system). 'enetront A. Max. 1-1/2 in. steel pipe, copper pipe, or copper tu6ing with 1 in. nominal fibergloss insulation. SECTION A-A Annulor space - Min. 1/2 in. ta max. 5/8 in. at top plate and subiloor. 1. Chose wall assembly tA. 2x6 in. or dauble 2:4 in. lum6er studs. 18. Sole Plote - Nom. 2z6 in. or two parallel 2x4 in. lum6er plotes. 1C. Min. 3/4 in. lumber or plywood subfloor with o max. 4-3/4 in. diameter penetrant opening. 3. Firestopping - FlomeSafee FS 1900 Series Sealant 3A. At floor surface, apply FS 1900 3/4 in. deep in[o annular space with a 1/4 in. crown. 3B. At bottom of top plote apply FS 1900 3/4 in. deep into annulor apace wiih o 1/4 in. crown. 1o. Nominol zxlo in. Iumber joist5. NOTES IE. Dou61e top ploie consi5ting of two 2x6 in, or 1. Sys[em design evaluated to ihe ASTM E814 (UL 1479) Fre two sets of parallel 2x4 in. lumber ploies. Tests of Through-Penetration Frestopa. 2. Deeign baeed upon teated configuratione 6y nationally reeognized teeting lo6aratories (e.g. UL, FM, etc.) oe well a in-house testing. 725 Cn1'ol Avenue Dekhurat, N! 0775! Phone: 732-631-3887 800-334-879' p(B International Protective Coatings Corp . Faceimile: 732-631-5192 888-531-519: Firesiop Assembly Projecf: Approved 6y John Goga C.E. Drawn by Joe Charland M.E. 7'h1e informetion ie bexd upoa iatcmnl end LLird perty leeling which we Producf: FiomeSafe FS 1900 $eries Sealon} Approval: helieve to De reliahle. The uner muet determine the suitaeitity of the produc Flre Roiin 2 NOUR 8: Insfaller: end lhe desian of the epp llealfon. 91nca Lhe nctusl imteqetlon of the 1 Ul Sysfem: FC5072 Da18: product le beyond our conkrol, IPC Corporet[on'e oNy reepomlblity ehe •? 6a to ro[und or roplace meteHals toum IPC Orowing # FC5012 Rev.# OOD to be defect[ve ae per our ¦tendnrd warranly. 5- 203 I IV(: F'yro- I tl;H ? PL 7T 1-215-368-6313 +w2/111e8 017:21 INTERNATIONAI PROTECENE COATINGS CORPORATION ?g 725 Carol Avenue Ocean Twp. , N.J. 07712 800-334-8796 906-531-3666 (FAX) 908-551-5192 Drawing Not To Scale o. .? ! ; ?. ?. , Saotion thru floor ?. 2. i , 4. ? 1. 0 4 b -w,.-:. ; .,.. . , ....::..:....... .. .. ?Plaa view of floo= l. Miu. 4-1l2 in. cancrete floor / Pro-caet hollow core floos or oonotete block I C1fU wall capable of praoidinq a 2 or 3 houx F ratinq. Mia. D in (pt. of contact) to a max. 1-7/8 in. annular space (Refer to taLle). 2. PenetrantSnacificaSi9Ae F Ratinq SealAnt/degU - Max. 14 ia. stael or cast iron 3 hr. 1" FS1900 or 112' FS900 - Max. 6 in. copper pipe/tubiag 3 hr. 1" FS1900 or 112' FS900 - Ma:. 4 in. EMT coaduit 3 hr. 1' F51900 or 112' FS900 - Nax. 12 in. atael or caet iraa 2 hr. 1/2' FS1900 - Max. 6 in. copper pipe/tubinq 8 hr. 112' FS1900 - liax. 4 in. EliT conduit 2 Lr. 1/2' F51900 3. (Optioaal) Not Shown - Backer Aod - foam baaking material. (Optional) Not Sho" - 4 16. densilp miaeral wool baakiaq. 4. I'lsaesafeg FS1900 or FS900 serlmt. Applp iato the anaular spaoe. Fiaieh flueh vith the floor. Refer to table for the proper depth. Fox e rall application finish with both vall aurfacea. 5. (Optioael) llin. S110 steel eleeve caet o= grouted into the floor. Fiaieh flveh with Loth eurfaoea. ' NOTICE Approved by: - System design evaluatedto the ASTM•E•814 (UL•1479) This iniormalion is based upon internal and J, Goga FIRE TES7S OFTHROUGH-PENETRATION FIRE STOPS. third party testing which we believe to be Dete: • Design based upon tested caMiguretions by natlonegy recagnfzed lesling laboralodes (eg. UL, FM,elc.) as wel es relieble. It is intended Ta engineerinq pur- 11 Feb. 1997 In house testmg. poses only. The UBer must determine the . Addit(onei intormalion can be relerenced fn UL'a Fire suitability o1 the product and the design to the UL System: Resislance Direaory , such es but rrot GmRed to appHcetion. Sinqe the eclual installetion of the cAa1235-aJ systems a, CAJ1235 productisbeyondourcontrol,IPC Corpora[ion'sonlyresponsibilityshal) FireRa[Ing: mqinearingnet.rminazian be to refund or repiece meteriele found a or 7 hour rojeot: tobedefecUveasperourstandard FIeldApprv. 11 i j F. , t i ;?. i i ? t ? • ? ' IN(: F'yro- I t(:H Yi 1-11S-368-6313 4il2111/98 CU17:20 ? P ? INTERNATIONAL PROTECTNE COATINGS CORPORATION 'Q 725 Carol Avenue, Oakhurst , N.J. 07755 800-334-8796 908-531-3666 (FAX) 908-531-5192 1 5. 1. 4. 3 1. Mia. 6' aoncrste floor or Pro-oast hollov core floor or coacrat• bloat or CMQ vall conctsuclad to moot UL saquiromoaL¦ for 2 Lour fisa rating. 1lax. 16" diam. opsaing. llia. annular apaaa of 112 in. and a max. of 2-3f4 iaohes. 1. lfax. 10' diam. or smallet etael ar aaet iran pipe. Max. 4' diam. or smaller oopper pipe or tubiag. 3. ]faz. 1 in. fiberqlase iaeulatioa. 4. Min. 2' thiok mineral vool baoking aompreaeed iato the aanular spaoe. Racaee min. 1' from floor and vall aurfaoes to aaaomodata the FS1900. 5. !'1tmsSefs0 IpC FSl900 Ssalsat. Iastall min. 1" depth on top of the mineral vaol. Add sa addiLioasl 114 ia. c=o" sztsadinq 6eyond the floor os both vall eusfaoae. 6. ( Optioaal ) eteel elaeve cact or grouted into the ooncrate and Elush With Floor or bolh vall surfacae. 8rgi0eoricg Dotarmtortian NOTICE Thla Inlormelion Is based upon internel end third party testing which we belfeve to be ' rellaWe. N is Imended }a engineering pur- posea only. The user must determine the suitabiliry of the product and the design to the epplicetion. Since the actuai Installation oi the ' product is beyond our control, IPC Caparation's onlyreeponsibility shall beloretund orreplace materials(ound to be defective ae per our etanderd werrenty. ApproVed by: • Syslem design evelueled lo the ASTM-E-814 (UL•1479) J. Goga FIRETESTSOFTHROUGH•PENETRATIONFIRE9TOPS. • Dealgn besed upon teated conliguretlons by netbnaAy Date: recogrized testfng laboraloriee (eg. UL, FM,eIcJ as weG ae , 11 Feb. 1998 In houee l9sling. I UL System: • Addltional IMortnalbn cen be reterenced In UL's Flre Realstence Diredory , euch as but nol Omlled to C&75008-E7 Systems:CBJ5008 6 CAJ¢116 2 houre Projsat: IeldApprv. Elevation vior of ponatsatioa Seotion thru floor 6 ? F IameSafel FS 1900 is a high-performance, elas- (\ tomeric and intumescent sealant. lt is a high- Qiiwr solids, wa(er-based compound engineered to pro- vide exceptional adhesive and elasromeric propertics for the demanding firestop requirements of pipe, cable, sprinkler penetrations and construction joints in environ- ments subjected to frequent expansion and contraction. FS 1900 is high]y inmmescent It expands up to 7[imes (700%) i[s original volume to fill lhe void creat- ed by the melting and burning of PVC, CPVC, cc-PVC, insulated pipe, and plastic-coaled cables. FS 1900 does not contain solvents. As a result, it is not toxic and cannot damage plastic pipes or cable jackets. ? Color: ?. ' Red* Odor Faint Latex 'Vehicle Water-based Weight 10.0 lbs/gal (1.2 kg/L) ?pH ? 10-11 Volume Expansion 700% Installation Temp. (40° to 90° F)/(4°to 32° C) ; 5torage Temp. (40° to 90° F)/(4°to 32° C) ASTM C719 Passed rFlame Spread 0 (ASTM E84) Smoke Developed 5 (ASTM E84) * Prior to SII S/97, FS 1900 was blue/gray. :j FS 1900 SERIES SEALANT INTUMESCENT, ELASTOMERIC FIRESTOP • UL Approved • Tactory Mutual certified • Warnock Hersey listed • Up to 3 hour fire-rating • UL 1 and 2 hour fire-rated systems for CPVC • Tested to UL 1479 (ASTM E814), UL 2079, ASTM C719 • Used in bus and HVAC ducts, through-penetrations with mixed penetrants, metallic or non-metallic pipes, and construction joints • Wood joist and chase wall tloor-ceil- ing assemblies • Excellent adhesion • Water-based, high-solids • No solvents • No silicones, no outgassing • Caulkable or trowelable • Tvo-stage intumescent system • Highly intumescent - 700% • Elastomeric • Sandable/paintaUle • Easily repaired or repenetrated FlameSafe° FS 1900 Series Sealant - Dynamic Movement Approved (Patent Pending) , r.m:...?- . . _ GVPSUM WALLBOAflD 5/8" TWO LAYENS MA% z' oin rvc. cavc. OR NON-METALLIC CONDUIT FlameSale• FS 1900 1 1/4' DEEP CPVC & PVC System UL Sysfem WL 2038 -1 & 2 Hoar FlemeSate• F51900. FOR 3 HR. FIRERATING, APPLYAMIN.7 M THICK FLUSH WITHTHE FLOOR. APPLV A 3/8 IN. CROWN A7 THE POINT OF CONTACT. MIN. 4421N. CONCRETE PLOOR MIN. 1 IN.7HICK (BACKER ROD) POLYURETHANEeACKING. NOMINAL 61N. OIAMETEP OR SMALLER COP- PER PIPE. MAX. 241N DIAM OR SMALLER STEEL OR CAST IRON PIPE MAX.41N DIAM.OR SMALIEFi EMT CONDUIT OR 61N. DIAM. OR SMALLER STEEL CONDUIT. : Metallic Pipe Penetration UL System CAJ1235 - 3 Hour .? Flame5ale• FS 1900 AI lloor sudece apply a 3/4' tlepth wilh a 3W crawn. Nom. 2' x 6' or parallel 2' z 4' lumbar pl9les. Mln. 3/4' lumber or plywood su60oor Max. 4-3(4' openlrg. Nom. 2' a 10' lumber jolsls. One layer ol gypsum wallboard celling cepeble ol providing a 7 hr. F rating Dou61e lop plate consisling ol Iwo 2' x 6' of Iwo sets of 2' z 6' or tlouble 2' x 4' IumCer Mex 4' dieme[er or smatler PVC (solid or cellular core) end CPVC plping as en open (venled) or tlo5etl system. I ? Nam 1N" ennular spece. Apply a 3/4' tleplh ol FS 1900 at the I bonom pfate Apply e 3/8' crown. i ? ?- - --- Wood Jolst and Chase Wall Floor-Celling System FC2082 - l Hour FlamcSafe°D FS 1900 is classified by Undenvrit- ers Laborarories Inc., and Underwriters Labora- tories of Canada for l, 2 and 3 hour rated sys- [ems, in accordance with ASTM E814 (UL 1479/CAN4-S I I SM), Fire Tesls of Through- Penetration Firestops. FS 1900 is Factory Mutual approved and listed by Warnock Hersey. It has been tested to and passed ASTM C719, Adhe- sionlCohesion of Elastomeric Joint Sealant for Cyclic Movemenl (UL 2079, Standard for Fire Tests of Joint Systems). in addition, the FS 1900 is accepled by the city of New York (MEA). Systems are available for: metallic and non- metallic pipe, cable, conduit, cable tray and duct penetrations through typical wall and floor con- struction; expansionjoints; constructionjoints such as wall to wall, floor to floor, wall to floor and curtain wall; concrete, masonry, fluted deck and gypsum substrates; wood joist floor-ceiling and chase wall assemblies. • 1 FlameSafe FS 1900 is used to seal openings in fire-rated struclures where burning plastic pipe, insulated pipe, or coated cables may compro- mise the rated system. It also can be used in bus and HVAC ducts and through-penetrations with metallic pipes anJ mixed penetrants. It is used in conjunction with mineral wool boards in saf- ing applications to prevent smoke, fire and toxic gases from spreading lhrough perimeterjoints and floor slabs, openings 6etween fluted roof and 17oor decks, tops of fire-rated walls, wood joist and chase wall floor-ceiling assemblies and other construction/seismic joints. See Figures 1-4 for examples of typical details. FS 1900 is parlicularly suited for use in appli- cations where system vibration and building movement are concerns. Install.litiolit All contact surfaces must be free of loose dirt, scale, oil or other foreign materials. Installation procedures and material used may vary accord- ing to the size of opening being protec[ed and the type of penetrant. Material may be installed using a standard or powered caulk gun, or trow- eled into place using a mason's trowel or putty knife. FS 1900 is a wateo-based sealant that dries through evaporation. Time required for drying will vary according to environmental conditions. When dry, FS 1900 remains elastomeric, indefinitely. ? ? . Applications using FS 1900 are maintenance (^? free, however, installations should be inspected periodically for accidental damage, and repaired using FS 1900 as per lhe original approved design. IPC provides Toll-Free Technical Support for all its products including FlameSafeO FS 1900. Please call 1-800-334-8796 fot assistance in product selection and for detailed specifications and approvals. We provide engineering analysis for unique firestopping applications, including system design drawings suitable for submittals. Material SaFety Data SheeGs are also available. You can also reach us at our Web site: http://www.flamesafe.com. All statements, technical information, and rec- ommendations contained herein are based on tests we believe to be reliable. However, since the conditions of use and applications are ? beyond our control, IPC shall not be liable for any damage, direct or consequential, resulting from the use of this material or design. IPC's only warranty shall be to replace any of its products found to be defective. FlameSafe" FS 1900 is available through authorized IPC distributors in the following quantities: ,Oescdption Cai. No. Volume Std. Pack Caulk Tube FS 1900 19.0 a. in. 12 10.3 oz. (305 ml) (311 cu. cm.) ;(aulk Tube' B 1929 51 w. in. 6 t31 az (.920 (934 a. cm.) Poly Poil FS 1901 231.0 cu. in. 4 1 gaL (3.81) (3,168 cu. (m.) Poly Pail FS 1905 1,155 cu, in. 1 ? ?5 gol. (19.01.) (18,942 m. cm.) , " For use with prowcreJ caulk gun only. Call 1I'C for tool rccommeodation. MINEHAL WOOL INSULATION FlomeSere' FS /900 SealenC SW DEEP GVPSUM WALLBOARD, 7 or 2 Hq. RATED M? TWOS/B'THICKLAVERS Raof/VJaII (Fluted Steel Deck) Assembly WHI System PSV 1095 - 2 Hour WNI Syslem PSV 1097 - 1 Hour FS 1900 can 6e used in joints between rool/lloor decks (above) and drywalf or masonry wa!!s, or, power caulked into consfruction joint applications (below). .. 4 ?0 ?S '. . ? .'r.. ? -I fS 1900 volume can be esiimated using this lormula: VOL =[(1/2 D x L) +(S x L)] x T where L = Length of wall (in) S = Space from top of wall to bottom of inelal pan flute (in) •' D = Depth of flute (in) T = Thickness of FS 1900 (in) " Vol = Cubic inches FS 1900 required o Large Openings/ ? Small Openings/ O ComUustible Noncombustible Largc Openings/ ? Joint Protection q Noncombusti6le SmallOpenings/ ? Combustible PIPE SIZE OIAMETEP OF HOLE (INCHES) Pipe O.D. Trada Size 1 2 3 4 5 6.5 7 B 9 10 it 72 13 14 75 16 17 18 19 20 0.54 111 03 1.5 3.4 62 0.68 318 02 1.4 36 61 0.84 1R 0.1 1.3 3.3 60 1.05 314 1 1 311 5.8 1.32 1 09 28 5.6 9.1 1.66 1-114 0.5 25 52 8.7 1.90 1-12 02 2.1 4,9 94 2.38 Z 13 4.1 76 l1 9 2.06 24R 03 30 66 109 3.50 7 1.5 5.0 93 14.4 203 270 C.00 942 35 7.9 130 18.8 255 [ 4.50 4 19 62 11.3 172 239 313 396 48A 5.56 5 2.0 7.7 .0 356 [ 6.67 6 20 7.9 195 22.0 30 597 711 8.63 B 2 6 10.0 18.3 477 59.1 10.75 70 2.1 112 21.0 316 43.0 51 .1 6A 1 81 8 12.T5 12 13.1 245 76.7 49.6 634 10,00 74 11.4 23.5 36.5 502 64.6 601 16.OU 16 12.9 26.7 412 565 18.00 18 14.5 29.8 For Through•Wall Pipe Penetrations FS 1900 required in cubrc rnches per hall-inch ol installed depth. 0 IPC offers distribution throughout Ihe wodd. Please call for more in(ormation. ? Inlemational Roteclive Toll Pcee 900-334-8796 Cnatings Corpnration Tclephone 732-5313667 ? 725 Carol Avcnuc Toll Free Fax 888-53 L5192 Oakhumt, NJ 07755 Fuccimde 732-531-5192 1 O 1? ? E-mail info@flamcsa(e.com our One-Stop Firesrop Company:" Specialty Buiding Products 1500 Jackson St. NE #2003 Minneapolis, MN 55413 (612)781-7655 (Fax-7921) ,n arv, rowin?. " jv"198 • • MATERIAL SAFETY DATA SHEET Manufacturer's Nama: Emergency Telephone No.: , W Internalional Protective Coatings Corp. (800) 424-9300 725 Caroi Ave Oakhurst, NJ 07755 information Telephone No.: Date o( preparation: Octo6er, 1996 Preparad By: M.Navarro (908) 531•3666 (800) 334-8796 SECTION I - PROOUCT IDENTIFICATION HMIS: Product Name: FlameSafee FS1900 Series Firestop Sealants H F R PP Product Class: Filled Vinyl & Acrylic Emulsion 1 0 0 B SECTION II - HAZARDOUS INGREDIENTS Weight Occupational Vapor Preasure Ingredient CAS Number Percent Expoaure Limits mm Hg 0 Temp. Nol Applicable (WA) N/A N/A NlA WA i. This product does nol contain any hazardous material(s) as defined by OSHA, 29 CFR 1910 2. This product does not contain a chemical which is listed in Section 313 above de mrnimis concentration. 5ECTION 111- PHYSICAL DATA BoilingRange:212°F(100°C) VeporDensily:(AIR=1)>t VOC'S: 10.e6 gil Eveporation Rate: (H20=1) 1 % Volatile By Volume: 26.0 WgtJGal.: 10.00 Ibs./GAL. Appearance and Odor: BlueBlack Mastic, Mild Latex Odor. Solubility in Water: Appreciabls. SECTION IV - FIRE AND EXPLOSION HAZARD DATA Flammabilky ClessNication: Flash Point:None (+yater base compound) LEL: Not Applicable (WA) UEL• WA Extinguishing Medif: Foam,alcohal foam,C02, Dry Chemical, Water Fog. Unusual Fire And Eploaian Hazards: This product will not burn, but may spatter if the temperature ezcaeds the boiling point. Dried film may burn in an imtanse (ire. SPECIAL FIREFlGH7ING PROCEDURES: Sell contained breathing apparatus should be used in enclosed areas. SECTION V- HEALTH HAZARD DATA EHects OI Overexposure: Eyes: Irritation. Skin: Excassive exposure may cause drying and chapping. Inheletion: May cause gagging, nausea and upper respiratory dislress. Ingeatlon: Possible nausea. Medieel Conditions Prone To Approvation By Exposure: None Known. ! ?.. , FS /FS 1900 SERIES FIRESTOP SEALANT primety Route(s) Of Entry; Dermal,lnhalation, Ingestion. Emergency and First Aid P,rocedurea: Eyes: Flush with water for 15 minutes. Oo nol rub. ConsuR physician if irritation persists. Sldn: Wash with mild soap and water. Inhalation: Remove to fresh air. Ingestion: I nduce vomiting. Chemicel liated as a carcinogen NTP NO OSHA NO or potential carcinagen: IARC NO SECTION VI - REACTIVITY DATA Stability: Stable Hazerdous Polymerization: Will not occur. Hawrdous Decomposition Pfodvcta: Carbon Monoxida,Carbon dioxide. Trace amounts of Nitrogen and asphyxiants. Condiilona to Avoid: Strong Acids and Strong alkalis. , Incampelibllity ( materiels to avoid ): Strong acids and strong alkali. SECTION VII - SPILL OR LEAK PROCEDURES Steps to be taken in case material Is released or spilled: Keep all speclators away. Uncontaminated material may 6e recovered and reused. If contaminated scoop into receptacle for disposal. Waste Oisposal Methad: Allow materiai to dry.Dispose waste in accordance with federal,state and local regulations. SECTION VIII - SAFE HANDLING & USE INFORMATION Respiretory Protection: Use MSHA/NIOSH approved respirator in poorly ventilated areas. Ventflatfon: General (machanical) room ventilation is to be satisfaclory for normal usage. Protective Gloves: Imperyious. Eye Protection: Safety giasses or goggles. Other Protective Equipment: As needed. Hygienic Practicea: Avoid contact with skin and ciothing. Wash atter handling and launder contaminated clothing before reuse. SECTION IX - SPECIAL PRECAUTIONS Precautiona to he taken in Handling and Storage: Seal container when not in use. Slore in well ventilated area. Other Precautione: The information and recommendations offered herein, are for users consideration and examination and is to be used in adddion to all other information that is available and pertinent. It is the user's responsibility to determine the suitability of Ns specilic conditions and par(icular use. IMPORTANT NOTE:Thie information references the product Raelf, not in combinetion with any other material to which it may eventually be epplied or come in contact whh. The user must determine any local, slate or tederel regulations regard(ng the use and diaposal of this product in conjunction with other materiels which may be reguleted (For exemple: Asbestos ar esbeatoa containing meterials). Specialty Ruiding Proflur.ts pAGE2 1500 JACkson St. NE #2003 A'finneapolis, MN 55413 (612)781-7655 (Fax-7921)