1629 Lena Ct - Grease Fire protectionLLXJ VV'L
FC
F ire Baxrier Duct Wrap 15A .
Commercial Kitchen Grease Duct Fire Protechon System
i?,ap ??r4 •
tJFPA 96 ComAGes wAh Cprowee wit,
?+ M. 6e.rip4b UIBf1YdlOI?l1 Stintlsld
? ?,g?. f996Eaum MlCMniWCb6! Mod781 11Cdceele
Product Data ?O1AS?? °°•? ?-
?,?,., ?.
1_ Proctuct Mscription
3FATM Fire Barrier Duct Wrap 15A is a fire reslstant
wrap consisting of a paterned inorganic blanket
enCBpsulated with a scrim-reinforced toii. 11 is used to
tire rate commercisl kitChen grease ducts and is a
proven aftemative co 1 or 2 hour fire resistant ratea
shaft enciosures. This non-asbestos wrap contains a
sai2r fFbef ConStruCtion" and tnstaifs 2asily because of
its high flexibility and strength. 3M Fre Barrier Duct
Wrap 15A is tfie thinnest standard, sinyte tayer fire
resistant wrap that has passed the UL1978 Sesi which
simulates a grease duct fire. With its exCellent
insutating ppabilities, it is an ideal cho?ce for tight
spaces because it proteets combus[ible constructions
ai zero c[earance to the oveiiap or callar. 3M Fire
Barrier 1000 N/S, 1003 Sll_ and 20op+ Snicone
Sealants used in combination 3M Fire Barrier Duct
Wrap 15A provide an etfeCtive firestop when the duct
penetrates fire rated welfs and floors.
4. 7ypical Physical Properties
Btanket Color: gray/green
Weight 1.38 1bsJsq, ft. (6.73 kg/sq. m)
5. PertormanCe
3M Fire 8arrier Duct Wrap 15A has been tested In
accordance with the following:
ASTA C 411 ASTM E 719
ASTM1A C 518 ASTM E 136
ASTM E 84 ASTM E 814
UL 1978 (SeCtions 12 & 13)
5utface Burning GharacterisGcs (ASTNE E 84)
Foif Encapsu[ated Blanket:
Flame Spread: 4
Smoke Developed: 0
Blanker_
Flame Spread: 0
Smoke Deve[oped: 0 .
Features
. Thinnest, standard one layer.wrap for grease ducts
rated as a shaft altomative per,UL 1978
. Zero dearane0 to che overlap or collar for
cvrgested spaces
• High ftexibiliry for installation ease
. Foil encapsulated with unique cenber overtap seam
tor biariket protectian, less dust, and high wrap
strength
. Widest tange of penetration seal systems
• Sa#er flber construction'
'Has been demonstrated to be soIuMe In she Itmgs A=ord'mg to
Eu guidel'mes 67/548/EVYG, NOte 0 far bio perslStence.
2 Appllcat[Ons
3M Fire Sarrier Duct Wrap 15A is an idaal fire
res[s7Ne endosure for oornmercial kitchen grease
ch
duCts. 1t is a proven pertormance altemative to a
1 or 2 hour fire resistartt ratad shaft enclosures and
Ariovides zero dearance to combustible corrstruction
at pveYiap or coffar. 3M Fre Barrier 1000 N/S, 1003
S!L or 2000+ Slicone Sealent is used in combination
with 3M Fire BarcieY Duct Wrap 15A to firestop the
duct whan the duci penetrates fire rated tloors and
walls.
? 3. Availabilfty
Pradud UnN Size Unps! Wt./
cto. an_
3M Flre Barrler Ratl t.s in.x 2a tn. x 201t P 531bs.
auct wr 15n aemm xsaarn, K w9 24 k
3iN FiR BaRie1' Roll ' 1.51n. x 48 In. x 20 tt. 1 106 (bs,
Duct Wr 15A 39mm z 127 cm x cm 46
Thermal Conductivity
0 are °F (°C) bM r.•ft1-
o.a1'f
iam (W7) o_szz
1500(815) 1.69
1800 (8821 227
For technical data and praperties ot 3M Pire Barr(er
1000 WS, 1003 S/L and 2000+ Silicone SealaMs ses
separate product data sheets avaiiable trorn your 3Ni
representative.
GfLeSB Duct LiStInaS
Fus Esctesure System Omp Poiel La b. D n Nog.
Resistire Doct Sys?eq? Tdreeph.
eaaea rnotrauo
m
1 or 2laurs 1 layer of 3NA Fire Bartier GD 532 F fS $57 W
Duct Wrap 75A . 3 tn. ?D 538 F FS 558 f
(76 mm) peflmeter and ' FS 559 W
longitudipal ayerlaps FS 56Q f
FS 561 F
FS 562 W
FS 563 W
FS 518 F
'FS srs w
Code Complianee
3M F'rce Barrier Duct Wrap 15A complies with
reguiremertfs of ihe.foffowing eodesr
BpGA ES Compliance Report 2161
NFPA 96, 1998 Edkion
Standard Mechanical Code
zd WdbS=OT S00Z 92 'uEt i26ZS0bLS9= 'ON XdA
aIw : woaA
Qooa
InternationW Mech$?l C?Ode
Startdanl Building Code
;--. SBCCI ES Compliance Rsporc 2132
This is only a partial list of code compliance, For the
latest cpde and approval information go to
www.$m.com/6restop or speak to your autharized 3M
distri6utor or sales representative at (&oo) 328.1687,
6. Instatiation Techniques
31VI Fire Barrier Duct Wrap 15A systern should be
iastalfed in 8ccerdance with the following inslaliation
instnactions_
INatsrial and Equipmeat
. 3RA Flre BaRler Duct Wrap 15A blanket, 1-112 in.
(38 mm) ehick, 24 in. (60 cm) or 48 in. (121 cm)
wide, 20 ft (609 Cm) Standard iength_ "fTie 48 in.
(121 cm) wide blanket hetps to minimize waste.
. Aluminum foil tape.
. Minimum 3/4 in. (19 mm) wide filament tape.
• Carbon steel or stainless steel banding material,
minimum 7/2 in. (12,7 rnm) wide, mininlum 0.015 in-
(0,38 mm) thiCk, witli steel banding ctips,
. Hand banding Yensioner, crimping tool, and band'ing
cutter. . Minimum 72 gauge copper-coated steel insuiation
pins; galvanizeci steal or stainless speed dips,
minimum
1-1/2 in_ (36 mm) squace or 1-112 in. (38 mm) dia.
round, or equivalent sized insulated cup-head plns;
capacitor discharge stud gun.
-• . AcCASS doOf hardware: four gahraMzed steel thread
rods, 114 in. (B mm) dfameter by 4-1J2 in. to 5 ir3.
long (114 mm ro 127 mm) with 1/4 in. (8 mm) wing
nuts and 114 In. (6 mm) wash2rs: 4 in. (102 mm)
long steei hollow tu6eng to fif threaded rods.
• Minimum 4.4 lb_ (1,6 kg) dertsiiy mfnsral wool or
scrap pieces of 3M Fre Barrier Duct Wrap 1SA.
. 3M Fire Barrier 1000 W3, 1003 S/L or 2000+
8i!icpne Seakant.
Storege: -The 3M Fre Sarrier Duet 1Nrap 15A and 3M
Fire Barrier 1000 NlS, 1003 S/L and 2000+ SiliCOrte
Sealants must be stored in a dry vrarehouse
ernironment. PafEets should not ne stadced.
preparatory INork: 3M F9re 8arrier Duci Wrap 15A is
'Rlstalled wlth oommon tools, Such as knives, banders
and capacitor discharge guns for applying insulstion
pirts. In order to install tha duci flrestop system, the
sur(aces of aU the openings and penetra,ting items
n9ed to pe c(ean, dry, frost free and free of dust.
Method: To minimixe vvaste, 3M Flra earrler Duct
. Wrap 15A material should be rolled out tautty before
measuring. Generai instructions for instalfing the 3M
Fire 6arrier Duct Wrap 15A inciude a one-layef wrap
construdion appfied directly to the ducc. The 3M Fire
Barrier puct Wrap 16A blanket is wrapped around the
perimeter ot the duCt and is cut to e length to gverlap
" 3tself not tess than 3 in. (76 mm). The overTap made
by adJaceM tdankets tomts the 'ypngitudinal° overlap.
Aluminum ioil tape is used to seal all cut ecfges ot the
blanket and eny cears in the roil scrim.
There are three (3) approved inst8lfatfon
techniqueg for insfalling the 3M Ftre Barrier DuM
Wrap 15A (See Figare 7):
1. Telesceping 3 in_ (78 mm) Overlgp Wrap
UViSh ihe tele$coping averiap wrap rnethod, each
blanket overlaps one ad'?scent blanket, and each
blanket has one edge exposed and one edge covered
by the next blanket as shown in Figure i. The visitNe
edges of the perimeter nverlaps all point in the same
direction.
2. Checkerboard 3 in. (76 mm) avedap Wrap
With the 3 in. (76 mrn) chedcerpoard wehap wrap
method, blenkets with bolh edges exposed alternate
with blankets with covered edges, as shown in Figure
1. The vi5ible ECigeS of the peCialetEf Overlaps
akemate their directions end appear on every other
blankef.
3. 8utt Jolnt 1ARth Coflar
With the butt joint and Collar amethod, adjacent
blankets are bvtted tightly together and 6 in. (152 mrn)
wEde coftar ot 3M Flse Barrier Duct Wrap is centered
vver the joint, ovedapping each blanket by
.3 in. (76 mm) minimum as showa in Figure 1.
In all ihrae ove?lap techniques the penrneter overlap
can oocur at any tocation on the duct.
The blanket is meChaniCaily attsChed io the dud by
steel banding or by welded insutation pins and cEips
for all three installaSon methods listad.above.
For Banding Oniy (See F[gure 1)
Filament tape can be used W tempararily hofd the
blanket in place until the banding is applied. Tha steel
banding is applied arounrl the duct 1-1(2 in. (38 mm)
from each edge oF the biartket, and maximum
10-1/2;n. (26.7 cm) centers. The banding is placed
aroUnd the rnateRaE and tfghtened so as to sumoiently
hokl the 3M Firs Barrier Duct Wrap 15A in pface
against the duct, compressirt9 the foil but not cutting
the foil.
Additional Ptnning to Prevent Sagging of the
Wrap: For Ducts 24 in. (60 crn) and larger in wicfih, .
additional pires a?e needed to support the blanket on
the bottom horizontal surFace and on the outside face
of a vertical duct run. Space pins a maximum ot
10-1/2 in. (26,7 cm) apart in the dirACtion of th9
blanket width, and a maximum of 12 in. (30 cm) apart
in the direction of the blanket length. Refer to
paragraph be{aw for more inforrnation on Mechanical
Fastaning with Pins.
For Mechaniral Fastening wlth Pins Only
Insulation pins are weMed to the duct in the centers
of ihe overlaps a minimum of 7-1/2 in. (38 mm) from
each edge of the blankat, and spaced a maximum of
10-1/2 in. (26,7 cm) on conter afong perirneter
overlap, and a maximum of 10-1/2 in_ (26,7 mm) on
center along longitudinal ovedaps. The blanket is
Impated ovar the pins and neld tn place by gahranized
spee4 clips. (nsulation pins that extend beyond the
blanket vurap shall be rirrned down to efiminate sharp
?l
/
£d WdbS:Oi 5002 9z 'Uet ZZ02SBbti99: 'ON XtiA Q-iW: WDaj
tM 004
;--,
points. Insulated cup-head pins can be used at the
Same spacirtg requirements of the insufat;on pins.
NOTE: Support hangar systems do not need to be
wraPPed proVided the hangar rods are at feast a
rninimum oi 318 in. (9,53 rnm) diameter and spaced a
maximum of 60 in. (152 cm) on eenter alang the
length of the duct. Use a rninimum 2 in. x 2 in. x
1/4 in. (50 rnm x 50 mm x 6,35 mm) steel angle steel
support Channel or SMACNA equivalent support
system.
Access door lnstallation (See Flgure 2)
Four gatvanized steel threaded rods, 7/4 in. diameter
(6,35 mm) by. 41/2 in, to 5 in, long (114 mm to
127 mm) are welded to the duct at the comers of the
door opemng. Feur Steel tubes, each 3 in_ (76 mm)
lotlg, are placed over the rpds fo act as protection br
the 3M Fire Barrier Duct Wrap 15A when fastening
the doar. Four insulation pins are welded to the door
panel for insta{lation of the b[anket. One layer of 3M
Fire Barrier C1uct Wrap 95A fs cut approximatety the
same size as the access panel and impaled over the
insu[ation pins on the panel. k Fs essenHal that thls
layer frt tightly against the wrap surrounding the
access door opening with no through ppenings, A
second layer of 3M Fire Bartier buct Wrap 15A is cut
so as to oveffap the first layer by a minimum of 1 In.
(25,4 mm). The second kayer is impaled over the pins
and both layers are tocked in place with galvanized
Figure i
3M Fire Sarrier Duct Wfap i5A Commerctial Kitchen Grease Duci Systems
1 or 2 Hour Shait Attematfire Zero Clearance to Comvusiinles
Tefescoping Wrap 7'echnique Wlth 13anding For Ducts 24 Inches (60,9 cm) or Less
1_ Onre La r 3M Fm¢ BdtAer Duct Wrap 75A
2. 3te¢I Banding 112 in. (13 mm Wicfe M+rt, T oal
3. 3 in. 7e mm} ti+)in. Lon itudinal pmrfa
4. 3 in. (76 mm) Min. AertmMar pverisp ?
SY9tem irttagrity Is fmited hY 9uaktY of instaltalian.
speed dips. Pins Shat extend beyond the outer Isygr
of 3M Fire 8arcier Duct Wrap 15A shsll be turned
down to avAid sharp points on the door.
The insuiated door pattel is placed aver the threaded
rads and hefd in place with washers and wing nuts.
'fhs det3ils ere showrt in Figure 2.
Penetrations (See Figure 3)
When the duct penetrates a fire fated wall, ceiling or
floor, an epproved firestop syslern must be employed,
Figure 3 illustrafes a typica[ condltlon.
To firestop the wrapped duct, follow the instaftation
parameters detai?ed in the #ollowing Omega Point
Laboratories. Inc. systems*
FS 557 W, FS 558 F, FS 559 W. FS 560 F FS 561 F,
FS 582 W, FS 563 W, FS 578 F, FS 579 W.
Other AppliCations
More details on itie installation of the prqduCt Cat1 be
found in the 3M Product Data and Installation
InstrUCtion Manual (98-0400-5054-8).
7. Maiotersance
No maintenance is required when installed in
accordance with the 3M Installation Instructions.
Once insialled, if any section af the 3M Fire 8arrier
Duct Wrap 15A is damaged so that the blankei is
damag8ct, the f011owing procedureS wi8 apply:
Telescoping°averlap Wrap Option
Cross Sectlonal View
3 . (78 mm) 3° (76 mm)
1-1/8° (36 mm 1-1/2' (38 mm)
1 s
($3.3 om) Typ. ?
r
ChecKerbaard QverEap Wrap Option
Cross Sectional View
3" (76 M,) 3" (76 mr,)
(38 mm) 2 3 1-1/2^ (38 mm3
?
y
?ZI' (53.5 cm) 77rp_ I '
1
Butt Joint With Collar Option
Cross SectEanal View
6" (152 mm)
3" (76 m?n)
7-1?2" (38 m 1-f?2' (39 ?n?)
s
6