3130 Lexington Ave - ADA Surveyy.
SEBEJTA
BLOMBLRC?
ADA SURVEY OF 3M EAGAN FACILITY
Date: March 12, 2007
To: Mr. Roger Counihan, Engineering Technology Manager, Corporate Services
Engineering, 3M Corporation
From: Drew Bjorklund, Senior Architect, Sebesta Blomberg
Project: 3M, Cottage Grove Center
Sebesta Blomberg Project No. 102709.00
Survey Date: March 6, 2007
Intent of Survey:
To verify current status of compliance with the Minnesota Accessibility Code. Survey focused on the
following elements; site access, building access, toilet rooms, cafeteria and common areas. The survey
did not delve into office cubicles and office spaces; it is assumed that if the need arises, accommodations
could be made quickly to adapt these spaces in accordance with accessibility standards.
Manufacturin (F-1) 78,960 SF
Office (B) 23,290 SF
Warehousin
O 8-1) 20,585 SF
Manufacturin (F-1 790
Office B) 232
Warehousin (S-1) 41
Building Statistics
Site Access Notes:
The main entrance is located on the north side of the facility. The main parking lot, which contains the
dedicated accessible parking spaces is also located on the north side of the building. There are seven (7)
parking stalls that are denoted to be accessible, with both pole signs and pavement markings. These stalls
are closest to the accessible walkway> which leads up to the main entrance. The accessible walkway has a
slope of approximately 1:23. The walk has no railings. It does terminate at the parking lot pavement with
a compliant curb ramp.
ADA Survey for 3M Eagan FaciliN
Sebesta Blomberg Project No. 102709A0
March 6, 2007
Page 1 of5
SEBESI-A
BL0MBERG
ADA SURVEY OF 3M EAGAN FACILITY
Site Statistics:
No(es
General parking 281 316 Parking provided exceeds required parking space
count.
Accessible 8 7 Need to add one accessible stall.
One stall must be van accessible and have a minimum
8' wide aisle. Signage for van accessible space must be
provided.
Accessible spaces need to be re-striped to re-define
aisles between arkin stalls.
Building Access and Functional Areas:
As stated above, the main entrance is accessed by an accessible walk and by stairs. This is a secured
entrance, with a card reader inside the vestibule. The exterior door leaves are each 36" wide. The interior
set of door leaves are 35" wide. Both sets of doors provide the minimum 32" wide opening in accordance
with the ADA and Minnesota SBC. The distance between the sets of doors is 8'-6", which exceeds the
required distance between doors in sequence.
Once inside, virtually any function performed within the plant is either accessible or accommodations
could be readily made to provide for universal access. The survey did not search for accessible office
spaces (fixed or cubicles), but it is assumed that if spaces needed to be made accessible, this could be
achieved. The survey concentrated on common use areas, such as corridors, toilet facilities, cafeteria and
dining area. There are no shower areas within the plant.
Corridors and aisles are generally compliant, being at least 36" in width. Most of the aisles and corridors
range from 6' to 10' wide throughout the office and plant areas.
Accessibility signage at toilet rooms B141 and B142 should be removed, since this set of toilet rooms is
not accessible. These toilet rooms were measured and found to be out of compliance with the MN
Accessibility Code, as were CI04C, C108A, C110.
Plumbing Fixture Requirements:
ADA Survey for 3M Eagan Facility March 6, 2007
Sebesta Blomberg Projcct No. 102709.00 Page 2 of 5
Comparison of required fixtures and provided fixtures is as follows*:
SEBtsrn
B Lt)!vl [i E EiG
ADA SURVEY OF 3M EAGAN FACILITY
t
20 + 10 Urinals 24 3+ several bottied
water stations
Total universally accessible 2 2 3
re aired - 5%
Total universally accessible 4 5 2
provided (Exceeds (Exceeds (Add one and repair
re uirements) re uirements) other - see below)
*List covers a!l toilet rooms within the faciliry, including- A116, A117A, B141, B142, C704C, C708A, CI10, D106A, D107A,
E1 SSS.
Specific common-use areas are assessed far universal accessibility as follows:
Space ocatio
Toilet Room D106A Accessible W/C No Move entrance wall of stall to provide
minimum 48" from lip of W/C to front
wall
Accessible urinal Yes
Accessible lav Yes - nominally Bottom of front apron is 28-3/4" from
floor.
Plumbing is protected and
dimensionall com liant.
Towel dis enser Yes
Towel dis osal Yes
Soa dis enser Yes
Mirror Yes
Grab bars Yes - nominally Vertical grab bar missing. Side
horizontal grab bar is 10" from back
wall, vs standard 12".
Toilet a r dis enser No Mount below harizontal rab bar.
Toilet Room D107A Accessible W/C No Move entrance wall of stall to provide
minimum 48° from lip of W/C to front
wall. Centerline of W/C is
a roximatel 17" from side wall.
Accessible lav Yes - nominally Bottom of front apron is 28-3/4" from
floor. Plumbing is protected and
dimensionall com liant.
Towel dis enser Yes
Towel dis osal Yes
Soa dis enser Yes
Mirror Yes
Grab bars Yes - nominally Vertical grab bazmissing. Side
horizontal grab bar is 10" from back
wall, vs standard 12".
ADA Survey for 3M Eagan Faciliry March 6, 2007
Sebesta Blomberg Project No. 102709.00 Page 3 of 5
SEBESTA
BLOMBERG
ADA SURVEY OF 3M EAGAN FACILITY
Toilet a er dis enser No Mount below horizontal rab bar.
Toilet Room A116 Accessible W/C Yes
Accessible urinal Yes
Accessible lav Yes
Towel dis enser Yes
Towel dis osal Yes
Soa dis enser Yes
Mirror No Bottom of mirror and shelf to be moved
down to 40" AFF.
Grab bars Yes
Toilet paper dispenser No Mounted too far from front of toilet.
Should be mounted 7" to 9" from lip of
toilet.
Access to Cloak Room No 18" Clearance on pull-side of jamb is
not provided. Universal access to
space can be gained from Passage
A 165A.
Toilet Room A117A Accessible W/C Yes
Accessible lav Yes
Towel dis enser Yes
Towel dis osal Yes
Soa dis enser Yes
Mirror No Bottom of mircor and shelf to be moved
down to 40" AFF.
Grab bars Yes
Toilet paper dispenser No Mounted too far from front of toilet.
Should be mounted 7" to 9" from lip of
toilet.
Cafeteria Room A172 Tables Yes
Counter No Provide portion of counter that is
between 28" and 34" hi h.
Sink No Provide wheel chair pull-in space and
sink at counter that is between 28" and
34" hi h.
Vendin area Yes
Servin line Yes
Door to atio Yes
Patio tables No Provide wheel chair access to 1 or more
tables.
Unisex Toilet E155S Accessible W/C No Space between lip of toilet and lav is
45°.
Accessible urinal No Space between urinal and lip of toilet is
45".
ADA Survey f'or 3M Eagan Facility
Sebesta Blomherg Projec[ No. 102709.00
March 6, 2007
Page 4 of 5
i?
5EI3ESTA
BLUMBERG
ADA SURVEY OF 3M EAGAN FACILTTY
Accessible lav
Yes - nominall o
Below sink i in is not covered.
Towel dis enser Yes
Towel disposal Yes - nominally Waste basket infringes on clear floor
s ace. Su est wall-mounted model.
Soa dis enser Yes
Mirror Yes
Grab bars Yes - nominally Vertical grab bar is mounted slightly
too hi h.
Toilet a er dis enser Yes
General Office Area Drinking fountain ai
5141/B742 Yes - nominally Compliant but not working.
Manufacturing Area D Drinking fountain at
D 106A / D 107A Yes
Lab Area, Area A Drinking fountain at
Corridor A145 No Fountain mounted too high.
Survey Conducted and Reported by:
Drew C. Bjorklund, AIA, CSI
Senior Architect
Sebesta Blomberg and Associates, Inc.
ADA Survey for 3M Eagan Facility
Sebesta Blomberg ProjectNo. 102709.00
March 6, 2007
Page 5 of 5