Loading...
4155 Lexington Ave - ORSAT testcms ORSAT TEST FORMAT Unit 1 of 8 1). Address 4155 Lexington Ave. Eaaan, Mn 2). Occupant KNOWLEDGE BEGiNNrNgs 3). Electrical By Standard Electric 4). Gas Line By CMS 5). Make Carrier 6). Model 48 GX 03006030 lAD 7). Serial 1001G10463 8). Rated Input 60,000 Btu/Hr 9). Thermostat T874D1074 10). Gas Valve Make & Model White Roaers 36E24 11). Limit Make & Model KIXON 150-40 12). Llmlt Setting (Fixed or AdJust) Fixed 13). Fan SEtting (on/off) Runs all thP t.ima fnr Kit.rhan unnd 14). Pilot Type (standing/intermittent) Intermittent 15). Ignition Type (manual, glow coil, spark) Spark 16). Pilot Make and Model LH33WP003A 17). Pilot Timing (blow pilot out, time till burner goes out) 1 second 18). Gas Pressure (set recommendatlon on valve) 3.5" W.C. 19). Input - Clock meter or get orifice size and # 2#38 20). Gross stack temp before draft hood 310 Deg. F. 21). Ambient temp 70 Deq. F. 22). Measure C02 6.9% 23). Check for trace of CO (yes or no) None 24). Vent size Induced 25). Gas regulator make and model Maxitrol 325-3 26). Filters: #& size each 2- 10 x 14 x 1 27). Check location, spparance & operation of wiring & controls O.K. 28). Post test tag: Tested by CMS - date 8/24/01 29). Check for lighting instructions (post) O.K. CONSTRUCTION MECHANICAL SERVICES 1307 SYLVAN 0 SAINT PAUL, MINNESOTA 55117 0 (612) 488-4032 cms ORSAT TEST FORMAT Unit 2 of 8 1). Address 4155 Lexington Ave. F.aaan Mn 2). Occupant KNOWLEDGE BEGINNINGS 3). Electrical 8y Standard Electric 4). Gas L1ne By CMS 5). Make Carrier 6). Model 48HJE006-531 7). Serial 0601G20300 8). Rated Input 115,000 BTU/Hr 9). Thermostat T874D1074 10). Gas Ualve Make & Model White Roaers 36E24 11). Limit Make & Model KIXON 150-40 12). Limit Setting (Fixed or Adyust) Fixed 13). Fan Setting (on/off) Timed 14). Pilot Type (standing/intermittent) Intermittent 15}. Ignition Type (manual, glow coil, spark) Spark 16). Pilot Make and Model LH33WP003A 17). Pilot Timing (blow Pilot out, time till burner goes out) 1 second 18). Gas Pressure (set recommendation on valve) 3.5" W.C. 19). Input - Clock meter or get orifice size and # 3#42 20). Gross stack temp before draft hood 310 Dearees F. 21). Ambient temp 70 nParees F_ 22). Measure C02 6.7% 23). Check for trace of CO (yes or no) None 24). Vent size Induced 25). Gas regulator make and model Maxitrol 325-3 26). Filters: #& size each 2- 16x25x2 27). Check location, spparance & operation of wiring & controls O.K. 28). Post test tag: Tested by CMS - date $/24/01 29). Check for 1lghting instructions (post) O.K. CONSTRUCTION MECHANICAL SERVICES 1307 SYLVAN * SAINT PAUL, MINNESOTA 55117 9 (672) 488-4032 cms ORSAT TEST FORMAT Unit 3 of 8 1). Address 4155 Texington Ave Ea.gan Mn 2). Occupant KNOWLEDGE BEGINNINGS 3). Electrical By Standard Electric 4). Gas Line By CMS 5). Make Carrier 6). Model 48HJE006-531 7). Serial 0301G24615 8). Rated Input 115,000 Btu/Hr 9). Thermostat T874D1074 10). Gas Valve Make & Model White Roqers 36E24 11). Limit Make & Mode1 KIXON 150-40 12). Limit Setting (Fixed or AdJust) Fixed 13}. Fan Setting (on/off) Timed 14). Pilot Type (standing/intermittent) Intermittent 15). Ignition Type (manual, glow coil, spark) Spark 16). Pilot Make and Model LH33W003A 17). Pilot Timing (blow pilot out, time till burner goes out) 1 Second 18). Gas Pressure (set recommendation on valve) 3.5" W.C. 19). Input - Clock meter or get orifice size and # 3#42 201. Gross stack temp before draft hood 305 Decrrees F. 21). Ambient temp 70 DegrPPG F 22). Measure C02 6-8% 23). Check for trace of CO (yes or no) None 24). Vent size Induced 25). Gas regulator make and model Maxitrol 25- 26). Filters: #& size each 2- 16x25x2 27). Check location, spparance & operation of wiring & controls •• 28). Post test tag: Tested by CMS - date 8/24/01 29). Check for lighting instructions (post) O.K. CONSTRUCTION MECHANICAL SERVICES 1307 SYLVAN 9 SAINT PAUL, MINNESOTA 55117 9 (612) 488-4032 cms ORSAT TEST FORMRT Unit 4 of 8 11. Address 4155 Lexinclton Ave. Eaaan, Mn 2). Occupant KNOWLEDGE BEGINNINGS 3). Electrical By Standard Electric 4). Gas Line By CMS 5). Make Carrier 6), Model 48HJE006-531 7). Serial _Il301G24612 8). Rated Input 115.000 Btu/Hr 9). Thermostat T874D1074 10). Gas Valve Make & Model White Rogers 36E24 11). Limit Make & Model KIXON 150-40 12). Limit Setting (Fixed or Adjust) Fixed 13). Fan Setting (on/off) Timed 14). Pilot Type (standing/intermittent) Intermittent 15). Ignition Type (manual, glow coil, spark) SAark 16). Pilot Make and Model LH33W003A 17). Pilot Timing (blow pilot out, time till burner goes out) 1 second 18). Gas Pressure (set recommendation on valve) 3.5" W.C. 19). Input - C1ock meter or get orifice size and # 3#42 20). Gross stack temp before draft hood 305 Deqrees F. 21). Ambient temp 70 Degrees F. 22). Measure C02 6.8 % 23). Check for trace of CO (yes or no) None 24). Vent size Induced 25). Gas regulator make and model Maxitrol 325-J 26). Filters: # & size each 2-16x25x2 27). Check location, spparance & operation of wiring & controls •• 28). Post test tag: Tested by CMS - clate 8/24/01 29). Check for lighting instructions (post) CONSTRUCTION MECHANICAL SERVICES 1307 SYLVAN o SAINT PAUL, MINNESOTA 55117 •(612) 488-4032 cms ORSAT TEST FORMAT Unit 5 of 8 1). Address 4155 Lexington Ave. Eagan Mn 2). Occupant KNOWLEDGE BEGINNGS 3). Electrical By Standard Electric 4). Gas Line By CMS 5). Make Carrier 6). Model 48HJE006-531 7). Serial 0301G24609 8). Rated Input 115,000 Btu/Hr 9). Triermostat T874D1074 10). Gas Valve Make & Model White Rogers 36E24 11). Llmit Make & Model KIXON 150-40 12). Limit Setting (Fixed or Adjust) Fixed 13). Fan Setting (on/off) Timed 14). Pilot Type (standing/intermittent) Intermittent 15). Ignition Type (manual, glow coil, spark) Spark 16). Pilot Make and Model LH33W003A 17). Pilot Timing (blow pilot out, time till burner goes out) 1 second 18). Gas Pressure (set recommendation on valve) 3.5" W.C. 19). Input - Clock meter or get orifice size and # 3#42 20). Gross stack temp before draft hood 310 Deqrees F. 21). Ambient temp 70 Dearees F. 22). Measure C02 6•8% 23). Check for trace of CO (yes or no) None 24). Vent size Induced 25). Gas regulator make and model Maxi ro - 26). Filters: #& size each 2- 16x25x2 27). Check location, spparance & operation of wiring & controls •• 28). Post test tag: Tested by CMS - date R/?4 Ol 291. Check for lighting instructions (post) n_u_ CONSTRUCTION MECHANICAL SERVICES 1307 SYLVAN 0 SAINT PqUL, MINNESOTA 55117 •(612) 488•4032 cms ORSAT TEST FORMAT 1). 2). 3). 4). 5). Address 4155 Lexington Ave. Eagan, Mn Occupant KNOWLEDGE $EGTDTNENGS Electrical By Standard Electric Gas Line By CMS Make Carrier Unit 6 of 8 6). Model 48HJE006-531 7). Serial 0301G24610 8). Rated Input 115,00OBtu/Hr 9). Thermostat T874D1074 10). Gas Valve Make & Model White Rogers 36E24 11). Limit Make & Mode1 KIXON 150-40 12). Limit Setting (Fixed or Adjust) Fixed 13). Fan Setting (on/off) Timed 14). Pilot Type (standing/intermittent) Intermittent 15). Ignition Type (manual, glow coil, spark) Spark 16). Pilot Make and Model LH33W003A 17). Pilot Timing (blow pilot out, time till burner goes out) 1 second 18). Gas Pressure (set recommendation on valve) 3.5" W.C. 19). Input - Clock meter or get orifice size and # 3#42 20). Gross stack temp before draft hood 312 Degre es F. 21). Ambient temp 70 Degrees F. 22). Measure C02 6.9% 23). Check for trace of CO (yes or no) None 24). Vent 91ze Induced 25). Gas regulator make and model Maxitrol 325-3 26). Filters: #& size each 2- 16x25x2 27). Check location, spparance & operation of wiring & controls •• 28). Post test tag: Tested by CMS - date 8/24/01 29). Check for lighting instructions (post) O.K. CONSTRUCTION MECHANICAL SERVICES 1307 SYLVAN 0 SAINT PAUL, MINNESOTA 55117 0 (612) 488-4032 cms ORSAT TEST FORMAT Unit 7 of 8 1). Addt'ess 4155 Lexington AvP. Eagan. Mn 2). Occupant KNOWLEDGE BEGINNINGS 3). EleCtl'1Cfl1 By St.anda rd R1 Pc-tri r- 4). Gas Line By 5). Make 6). Model 7). Serial 0211324626 8). Rated Input 115,000 Btu/Hr 9). Thermostat T874D1074 10). Gas Valve Make & Model White Roaers 36E24 11). Limit Make & Model KIXON 150-40 12). Limit Setting (Fixed or Adjust) Fixed 13). Fan Setting (on/off) _Timed 14). Pilot Type (standing/intermittent) Tntermittent 15). Ignition Type (manual, glow coil, spark) Spark 16). Pilot Make and Model T,H33WP003A 17). Pilot Timing (blow pilot out, time till burner goes out) 1.5 Sec 18). Gas Pressure (set recommendation on valve) 3.5" W.C. 19). Input - Clock meter or get orifice size and # 3# 41 20). Gross stack temp before draft hood 300 Degrees F. 21). Ambient temp 70 Degrees F. 22). Measure C02 6.75 % 23). Check for trace of CO (yes or no) None 24). Vent size Induced 25). Gas regulator make and model Maxitrol - 26). Filters: #& aize each 2 16x25x2 27). Check location, spparance & operation of wiring & controls O.K. 28). Post test tag: Tested by CMS - ciate 8/24/01 29). Check for lighting instructions (post) O.K. CONSTRUCTION MECHANICAL SERVICES 1307 SYLVAN • SAINT PAUL, MINNESOTA 55117 9 (612) 486-4032 cms ORSAT TEST FORMAT Unit 8 of 8 1). Address 4155 Lexington Ave. Eagan, Mn 2). Occupant KNOWLEDGE BEGINNINGS 3). Electrical By Standard Electric 4). Gas Line By CMS 5). Make Carrier 6). Model 48HJE005-531 7). Serial 0201G24629 B). Rated Input 115,000 Btu/Hr 9). Thermostat T874D1074 10). Gas Valve Make & Model White Roaers 36E24 11). Limit Make & Model KIXON 150-40 12). Llmit Setting (Fixed or Adyust) Fixed 13). Fan Setting (on/off) Timed 14). Pilot Type (standing/intermittent) Intermittent 15). Ignition Type (manual, glow coil, spark) Spark 16). Pilot Make and Model LH33WP003A 17). Pilot Timing (blow pilot out, time till burner goes out) 1.5 Second 18). Gas Pressure (set recommendation on valve) 3.5" W.C. 19). Input - Clock meter or get orifice size and # 3#41 20). Gross stack temp before draft hood 312 Deqrees F. 21). Ambient temp 70 Degrees F. 22). Measure C02 6_g?/ 23). Check for trace of CO (yes or no) None 24). Vent size Induced 25). Gas regulator make and model Maxitrol 325-3 26). Filters: #& size each 2 16x25x2 27). Check location, spparance & operation of wiring & controls O.K. 28). Post test tag: Tested by CMS - date 8/24/01 29). Check for lighting instructions (post) O.K. CONSTRUCTION MECHANICAL SERVICES 1307 SYLVAN 0 SAINT PAUI, MINNESOTA 55117 9 (612) 488-4032