4250 Lexington Ave - Storage TanksRM/V4nI 10: 1C rINa OIL. L CMMM. MNO?C:ONZT
n
HOOVER GROUR, INC.
C O N T A I N M E N T S Y S T E M S D I V I S I O N
P.O. BOX 398
SEVERNA PARK, MARYLAND 21148
INSTALLATION
OF
ABOVEGROUND STEEL STORAGE TANKS
002
YI Y..•
fPE i
301-987-3800
800.777-2523
FAX 301-987-3890
Aboveground Storage Tanks for Flammable and Combustible Liquids are manu-
factured and tested by HOOVER GROUP, INC. in accordance with the require-
ments of the Underwriter's Laboratories Standard UL142.
Proper installation is of utmost importance to ensure the expected service and life
of the tank. The following installation suggestions are furnished for your consid-
eration:
r?
I. Handle tank carefully. Use cables or chains of adequate length (not more
than 90 degrees between the chains) attached to fit lugs provided. Oversize
hooks will Lear the IM lugs - use shackles, if necessary.
2. To insure compliance with applicable codes and regulations, tank and piping
should be retested at jobsite before being enclosed, or placed in use, using 5
p.s.i. air pressure as soap solution is brushed over weld seams. Inspect tank
contents before filling and replace tin caps with pipe plugs or capped piping
before test.
1 Install appropriate primary and emergency vent connections as indicated on
tank and drawings.
4. Donor cut or weld on any tank that contains flammable or combustible liquids
or vapors. Fire or explosion may result.
5. Contact your local Fire Marshall to assure compliance with local regulations
and codes.
6. Be sure all drain plugs are secure by applying teflon tape or pipe dope around
cast iron plug.
Serving the Industry with ouality Tanks and Systems
_q .
HOOVER GROUP, INC.
C O N T A I N M E N T $ Y 6 T E M 3 D I V I s 1 0 N
P.O. 8OX 396
SEVERNA PARK, MARYLAND 21146
ADDITIONAL INSTALLATION INSTRUCTIONS FOR
U/L DOUBLE WALL TANKS ONLY
n
-T'I'04171 15:17 FILAR OIL S CMM. =4O/CONVT
C=
Y.1
,?F
301-987-3800
800-777-2823
PAX 301-987-3890
When testing a double wall tank the inner tank should be pressurized to a maximum of
5 p.s.i. then pressurize the outer tank by bringing the pressure up very slowly to 3 p-s-f.
Maximum capacity of the outer tank is very small in relation to the primary tank capacity.
Compressors used for testing can overpressurize the outer tank spare u15motids causing
serious damage to the tank-
Ali drain fittings should be checked to make sure they are secure and have been installed
using teflon tape or equal to insure that fittings will not leak.
Serving the Industry with ouallty Tanks and Systems
ae?a.?i ie=zo r:rw oic a CNW. G43/COr4ST
s
:t
HOOVER GROUP, INC.
C 0 N T A i N M E N T S Y 3 7 E M S D I V I S I O N
P.O. BOX 396
SEVERNA PARK, MARYLAND 21146
U/L LISTED LURE CUBE SPECIFICATIONS
aaa
PEI
301-987-3800
800-777-2823
FAX 301-987-3890
U/L Listed Lube Cubes are built, tested and labelled per U/L 142 (steel aboveground
tanks for flammable and combustible liquids.) A25-30 PSI Hydro test wasperformed
on our tank design to test its structural Integrity. Our double wall tank design must
also withstand 15 PSI between the inner and outer shell. Lube Cube meets all
requirements of N.F.P.A. 30.
Each tank is individually tested at 5 PSI air and soap suds are applied to detect weld
seam pinhole leaks before leaving the factory.
Our recommended installation instructions are that each tank is tested to 3-3 PSI at the
site. The largest opening on top is the emergency relief vent. Each tank also has a 27
opening for normal venting.
Serving the Industry with OusRty Tanks and Systems
1w -t w
or ro
p 4' ro
0
1
I I
1 I
1 I
I I
I
1 I
1 I
L----------J
0
61/r
1 1rr
a,_;L If
WL
10 GAUGE
TEST AT 5 PSI
UL 142
STEEL ABOVEGROUND
TANKS FOR FLAMMABLE AND
COMBUSTIBLE LIQUIDS
NOTE;
ADD i Ur TO HEIGHT FOR SKIDS
C ommim S:
INNER TANK
4' EMERGENCY VENT
r REGULAR VENT
r GAUGE
r FILL
I'
1 OUTER TANK
4' EMERGENCY VENT
r INSPECTION
NP
B
a
qa
4
I _o:r PINS a1L S CM". " 4/C=4ZT• am
U HOOVER GROUP, INC
Containment Systems Division
U PO Se Box 396
Severna Nr MD 21146
800 777 2823
Double Wall Above Ground Tanks
capacity Dimensions
(Gallotrsj (Lx W x Hj A
Sin Avallable In
all UL Ll
well UL
x W x H)
(L
120 2'5" x 3'1" x 3'4* 2'2" x 6' 3' 0"
260 5 3" x 3'10 x 3'4" 5' 0" x x J'0'
480 T 6" x 3011" x 3,00 T 3" x 3 x 2680
500 5 3" x 3' 3" x 5 4" 5 0" x x 5' 0"
650 T 4" x 3' 0" x 54" jr 6" x 418 x 5 0"
11000 10'10" x J'00 x 54" 10 0" 2' 8" x 5 0"
1,500 1510" x 3' 0" x 5'4" 15 0" x 2' 8" F ON
2,000 18' 10" x 2' 10" x 6'4w 18-of x 2' 6" 6'r
t 2,000 IT 10" x 3' 4" x 5 4" 18-A' ' X 3' 0" x 5 0"
31000 20' 10" x 4'4" x 5 4" 2 0" x 4'0. X 15,00
Add F- 0T to Helyfd (H) for skids Add 4-to HOt N (H) for Aft
Standard
Features
• Constructed of 10 gauge shed steel
;• Skid mounted to permit inspection
• Shop primed exterior
• Standard NPT fittings
- Openings
Inner tank:
emergency vent
regular vent
gauge
fu
j Outer tank:
emergency vent
inspection
• Meets NFPA-30
T
Optional
Equipment
• Enamel finish in your choice
of color
• Custom NPT fitting pattern
available
• Fill Caps
• Vents V
• Lockable Fill Hatch I/
• lntank Level Gauges
l
t
i
M7 03,'71 15:21 PINE OIL & 0-_°!1. LNC
10 ..
HOOVER GROUP, INC.
0 0 N T A I N M 5 N T S Y S T E M S 0 1 V I S I O N
P.O. BOX 396
SEVERNA PARK, MARYLAND 21146
LUKE CUBE WEIGHTS
(fON
T
UAL WEIGH
120 GALLON 2r L x 3' H x 2'S"W 160#
280 GALLON B L x 3' H x T6'W 300#
480 GALLON 7*6"L x 2" x 3'4'W 3000
500 GALLON 5' L x 5' H x 2'8"W 410#
650 GALLON. 6'6" L x S H x 2-8-W 515#
1000 GALLON 10'L x 5'H x 2'8'W '1210#
1500 GALLON 15'L x 5- H x 2'8"W 1400#
2000 GALLON 18' L x S H x 2'6'W 1900#
500 GALLON 16'L x 190H x 32'W
) 1021 GALLON 18'L x 28"H x 39'W
CATWALK TANKS
500 GALLON I St x 19'11 x 32'W
1021 GALLON 18'L x 28"H x 39'W
.L=.
250#
450#
450#
6500
6250
1300#
1550#
2010#
...
"PE1
301-987-3800
800-777-2823
FAX 301-987-3890
r -00081 F WA/ 1
485#
850#
850#
1350#
1525#
2400#
3000#
3790#
1200# 1950#
1475# 2600#
1383# 2125#
1663# 2804#
OBROUND BASEMENT TANKS 275 GALLONS 210#
BEN CH-TO P TANK WEIG HTS
flouaLe
WALL
CAPACtTYIGALLONS f
180 F
50' VWDTH-
22' Mt=GHT
33 12' r10N U/L WEIGHT
3230 I1/1 I ,HT
439# UA,
8358
240 60' 3P 331? 3750 503a 980#
=0 60' 42' 33 12' 415# 555# 10560
450 78' 4T 331!2' 500# 873# 1265#
S00 72' 50' 33 VY' 575# 810# 1'323#
,rte 500 (2 COMPL) 72' S0' 33 12' 675# 910# 173011
Serving the Industry with Quality Tanks and Systems
.t
• e3l'Oai71 115:27 rINFi OIL S CHCM. CNO"CONST
HOOVER GROUP, INC.
C O N T A I N M e N T s Y s T !_ M s 0 1 v I s 1 0 N
P.O. BOX 396
SEVERNA PARK, MARYLAND 21146
OO3
PEI
301-987.3800
800-777-2823
FAX 301-987-3890
LUBE CUBE PRICE LIST tsrv cu*w un,T•
EOecd" Date., 1/1,91
RMSh Coat
Sinn le Wall Double Wall (NE77
'NON UT yd ••U/L alwfizw7d dbubin wwAfl
1 120 GALLON 2"rL x 3'H x 2'8"W $33600 $425.00 $745.00 $20.00
280 GALLON 59_ x 3'H x ZM 440.00 566.00 1,025.00 25.00
480 GALLON 7'6"L x 298"H x 3'4"W 880.00 970.00 1,795.00 30.00
500 GALLON 51- x 5'H x 21'W 880.00 970.00 1,795.00 30.00
650 GALLON 66-1- x 5'H x 21"W 925.00 1,110.00 2,220.00 35.00
1000 GALLON 101- x SH x 2'8"W 1,290.00 1,390.00 4750.00 45.00
1500 GALLON 15'L x 5'H x 2'8"W 1,800.00 1,900.00 3,780.00 60.00
2000 GALLON 181- x 6'H x 2'8"W 2,380.00 2,490.00 4,980.00 75.00
2000 GALLON 18'L x 5'H x T W 2,440.00 2,550.00 4,995.00 75.00
'
1
;r9 GALLON 209- x 5'1-1 x 4' W 3,500.00 3,825.00 7,050.00 90.00
Note: Add 4" to height for skids
Note: Add 6.5-to width, 3- W length and 5.5" to heightfor Double Wall Tanks UP W 500 gallons. Add 4" to width, 9.5" to length
1 and 5.5- to height for Double Wall Tanks. 650 to 3000 Gallons.
!rfFR THE CATWALK TANKS
500 GALLON 161- x 19-H x 32-W NIA $1.315.00 $2,560.00
1021 GALLON 181- x 28"H x 39'W WA 1,660.00 3,250.00
' Note: Add 1 1/2 ' to height for skids.
CATWALK TANK
500 GALLON S
161 x 19'H X 32"W
WA
$1,515.00
$2,950.00
1021 GALLON 181- x 28"H x 39-W WA 1,870.00 31880.00
'Note: Add 1 1/2" to height for skids.
OPTIONAL
ADD FOR GRATING 8 STEPS ON CATWALK TANK ONLY 5933.00
LEVEL GAUGES $60.00
f;.g,,B. OUR PLANTS: Fort Worth, Texas; Reading, Pennsylvania; Fort Wayne, Indiana; Coffeyville. Kansas:
Beltirtlore, Maryland; Lexington, North Carolina; Los Angeles. Cal9omia
j OBROUND BASEMENT TANKS 275 GALLONS $240.00
(Legs Extra)
I Servlnn the Induatm with Ouality Tanks and Systems