Loading...
670 Diffley Rd - Test & Balance ReportMASTER MECHANICAL, INC. 1027 GEMINI RD. EAGAN, MN 55121 (651) 905-1600 FAX: (651) 905-1601 To: City of Eagan 3830 Pilot Knob Rd. Eagan, MN 55122 We are sending you: The following items: Shop Drawings Specifications Copies Date No. X Attached Prints Letter Letter of Transmittal Date: 1.10.03 Project: Proj. No: #3435 Attn: HVAC Inspector / Dale Schoeppner Re: Praise Lutheran Church Permit #EA055183 Under separate cover via: Mail Plans Change order Description Samples 1 Test and Balance Report. These are transmitted as noted below: For approval Approved as submitted For your use Per request For review and comment For Bids Due Remarks: Approved as noted Return for corrections JAN 1 3 2003 Resubmit Submit Return Retum copies for approval copies for distribution corrected prints corrected submittals Prints returned after loaned to us By Copy To: Signed: Tom Palermo, ext. 235 PRAISE LUTHERAN CHURCH ADDITION & REMODEL EAGAN, MINNESOTA 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 SYSTEMS MANAGEMENT & BALANCING OF MINNESOTA, INC 199 Coon Rapids Blvd., Suite 111 Coon Rapids, MN 55433 CERTIFICATION: TEST AND BALANCE ANALYSIS REPORT FOR 763 - 717 -1965 FAX: 763- 717 -1997 PROJECT: CONTRACTOR: ARCHITECT: ENGINEER: PRAISE LUTHERAN CHURCH ADDITION & REMODEL MASTER MECHANICAL, INC. MASTER MECHANICAL, INC. EAGAN, MINNESOTA EAGAN, MINNESOTA EAGAN, MINNESOTA Mechanical systems have been completely tested and balanced to their optimum capabilities and in accordance with engineering design. CERTIFICATION NO.: 99 -04-25 By: Systems Management & Balancing of Minnesota, Inc. DA'Z'E: January 6, 2003 MANUFACTURER TRANE MODEL, SIZE YAC048A CONDITIONS REQUIRED FINAL NOTE TOTAL CFM 1600 1747 1,2 FAN STATIC PRESSURE (in. w.c.) 0.52 3 FAN INLET PRESSURE (in. w.c.) 0.21 FAN DISCHARGE PRESSURE (in. w.c.) 0.31 MOTOR HP 0.60 MOTOR RPM 1075 MOTOR (VOLTS /FLA/PHASE) 230 3.60 1 239 3.46 1 MOTOR AMPS 2.7 FAN RPM 1075 MOTOR SHEAVE FAN PULLEY DRIVE BELTS DIRECT DRIVE SPEED /SET DIRECT HIGH 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Systems Management & Balancing of MN, Inc. FAN NO. RTU -1 Fan Test NOTES: 1. Total air is the summation of airflows at the individual outlets. 2. 1749 CFM required at outlets. 3. Tabulated pressures are external to the unit. Page 1 ROOM NUMBER OUTLET "K" REQUIRED PREL FINAL TYPE SIZE' VEL CFM VEL VEL CFM NOTE 130 SE LD 4 1.0 300 300 312 304 304 LD 4 1.0 300 300 356 285 285 LD 4 1.0 300 300 358 319 319 CD 10 1.0 283 283 212 292 292 • CD 10 1.0 283 283 251 290 290 NW CD 10 1.0 283 283 306 257 257 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Systems Management & Balancing of MN, Inc. Page 2 RTU -1 Outlet Schedule NOTES: MANUFACTURER TRANE MODEL, SIZE YAC048A CONDITIONS REQUIRED FINAL NOTE TOTAL CFM 1600 1544 1 FAN STATIC PRESSURE (in. w.c.) 0.48 2 FAN INLET PRESSURE (in. w.c.) 0.19 FAN DISCHARGE PRESSURE (in. w.c.) 0.29 MOTOR HP 0.60 MOTOR RPM 1075 MOTOR (VOLTS /FLA/PHASE) 230 3.60 1 239 3.46 1 MOTOR AMPS 2.6 FAN RPM 1075 MOTOR SHEAVE FAN PULLEY DRIVE BELTS DIRECT DRIVE SPEED /SET 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Systems Management & Balancing of MN, Inc. FAN NO. RTU -2 Fan Test NOTES: 1. Total air is the summation of airflows at the individual outlets. 2. Tabulated pressures are external to the unit. Page 3 ROOM NUMBER OUTLET "K" REQUIRED PREL FINAL TYPE SIZE" VEL CFM VEL VEL CFM NOTE 130 NW CD 8 1.0 200 200 158 190 190 SW CD 8 1.0 200 200 152 184 184 SE CD 8 1.0 200 200 165 195 195 NE CD 8 1.0 200 200 158 187 187 132 CD 8 1.0 100 100 201 108 108 123 CD 8 1.0 250 250 216 243 243 131 CD 8 1.0 250 250 234 239 239 128 CD 8 1.0 200 200 273 198 198 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Systems Management & Balancing of MN, Inc. Page 4 RTU -2 Outlet Schedule NOTES: MANUFACTURER TRANE MODEL, SIZE YHCO36A CONDITIONS REQUIRED FINAL NOTE TOTAL CFM 1200 1421 1,2 FAN STATIC PRESSURE (in. w.c.) 0.44 3 FAN INLET PRESSURE (in. w.c.) 0.05 FAN DISCHARGE PRESSURE (in. w.c.) 0.39 MOTOR HP 0.33 MOTOR RPM 1075 MOTOR (VOLTS/FLA/PHASE) 230 I 2.30 J I I 1 239 2.21 1 MOTOR AMPS 1.8 FAN RPM 1075 MOTOR SHEAVE FAN PULLEY DRIVE BELTS DIRECT DRIVE SPEED /SET 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Systems Management & Balancing of MN, Inc. FAN NO. RTU -3 Fan Test NOTES: 1. Total air is the summation of airflows at the individual outlets. 2. 1320 CFM required at outlets. 3. Tabulated pressures are external to the unit. Page 5 ROOM NUMBER OUTLET "K" REQUIRED PREL FINAL TYPE SIZE VEL CFM VEL VEL CFM NOTE 136 N LD 4' 1.0 250 250 272 275 275 S LD 4' 1.0 250 250 237 252 252 135 LD 4' 1.0 250 250 330 274 274 134 LD 4' 1.0 250 250 269 271 271 133 CD 8" 1.0 220 220 247 240 240 133A SR 12x8 0.40 250 100 368 272 109 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Systems Management & Balancing of MN, Inc. Page 6 RTU -3 NOTES: Outlet Schedule ROOM NUMBER OUTLET "K" REQUIRED PREL FINAL TYPE SIZE" VEL CFM VEL VEL CFM NOTE 120 N CD 8 1.0 220 220 143 143 143 1 S CD 8 1.0 220 220 119 119 119 1 117 CD 6 1.0 150 150 147 147 147 118 CD 6 1.0 100 100 94 94 94 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Systems Management & Balancing of MN, Inc. Page 7 EXISTING SUPPLY NOTES: 1. Maximum available. Outlet Schedule ROOM NUMBER OUTLET REQUIRED PREL FINAL TYPE SIZE "K" VEL CFM VEL VEL CFM NOTE EF -1 EG 16x12 1.1 409 450 358 358 394 1 EF-1B EG 16x12 1.1 409 450 333 333 366 1 EF -2 EG 10x10 1.1 91 100 137 137 151 EF -3 EG 12x8 1.1 91 100 63 63 69 1 EF -1 EG 10x10 1.1 91 100 131 131 144 2 Systems Management & Balancing of MN, Inc. Page 8 MISCELLANEOUS BATHROOM EXHAUST NOTES: 1. Fans have common discharge louver. 2. Two fans on print labeled EF -1. Outlet Schedule