670 Diffley Rd - Test & Balance ReportMASTER MECHANICAL, INC.
1027 GEMINI RD. EAGAN, MN 55121
(651) 905-1600 FAX: (651) 905-1601
To: City of Eagan
3830 Pilot Knob Rd.
Eagan, MN 55122
We are sending you:
The following items:
Shop Drawings
Specifications
Copies
Date
No.
X Attached
Prints
Letter
Letter of Transmittal
Date: 1.10.03 Project:
Proj. No: #3435
Attn: HVAC Inspector /
Dale Schoeppner
Re:
Praise Lutheran Church
Permit #EA055183
Under separate cover via: Mail
Plans
Change order
Description
Samples
1
Test and Balance Report.
These are transmitted as noted below:
For approval Approved as submitted
For your use
Per request
For review and comment
For Bids Due
Remarks:
Approved as noted
Return for corrections
JAN 1 3 2003
Resubmit
Submit
Return
Retum
copies for approval
copies for distribution
corrected prints
corrected submittals
Prints returned after loaned to us
By
Copy To:
Signed: Tom Palermo, ext. 235
PRAISE LUTHERAN CHURCH
ADDITION & REMODEL
EAGAN, MINNESOTA
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
SYSTEMS MANAGEMENT & BALANCING
OF MINNESOTA, INC
199 Coon Rapids Blvd., Suite 111
Coon Rapids, MN 55433
CERTIFICATION:
TEST AND BALANCE ANALYSIS REPORT
FOR
763 - 717 -1965
FAX: 763- 717 -1997
PROJECT:
CONTRACTOR:
ARCHITECT:
ENGINEER:
PRAISE LUTHERAN CHURCH
ADDITION & REMODEL
MASTER MECHANICAL, INC.
MASTER MECHANICAL, INC.
EAGAN, MINNESOTA
EAGAN, MINNESOTA
EAGAN, MINNESOTA
Mechanical systems have been completely tested and balanced to their optimum capabilities and in accordance
with engineering design.
CERTIFICATION NO.: 99 -04-25
By: Systems Management & Balancing of Minnesota, Inc.
DA'Z'E: January 6, 2003
MANUFACTURER
TRANE
MODEL, SIZE
YAC048A
CONDITIONS
REQUIRED
FINAL
NOTE
TOTAL CFM
1600
1747
1,2
FAN STATIC PRESSURE (in. w.c.)
0.52
3
FAN INLET PRESSURE (in. w.c.)
0.21
FAN DISCHARGE PRESSURE (in. w.c.)
0.31
MOTOR HP
0.60
MOTOR RPM
1075
MOTOR (VOLTS /FLA/PHASE)
230
3.60
1
239
3.46
1
MOTOR AMPS
2.7
FAN RPM
1075
MOTOR SHEAVE
FAN PULLEY
DRIVE BELTS
DIRECT DRIVE SPEED /SET
DIRECT
HIGH
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Systems Management & Balancing of MN, Inc.
FAN NO. RTU -1
Fan Test
NOTES: 1. Total air is the summation of airflows at the individual outlets.
2. 1749 CFM required at outlets.
3. Tabulated pressures are external to the unit.
Page 1
ROOM
NUMBER
OUTLET
"K"
REQUIRED
PREL
FINAL
TYPE
SIZE'
VEL
CFM
VEL
VEL
CFM
NOTE
130 SE
LD
4
1.0
300
300
312
304
304
LD
4
1.0
300
300
356
285
285
LD
4
1.0
300
300
358
319
319
CD
10
1.0
283
283
212
292
292
•
CD
10
1.0
283
283
251
290
290
NW
CD
10
1.0
283
283
306
257
257
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Systems Management & Balancing of MN, Inc. Page 2
RTU -1
Outlet Schedule
NOTES:
MANUFACTURER
TRANE
MODEL, SIZE
YAC048A
CONDITIONS
REQUIRED
FINAL
NOTE
TOTAL CFM
1600
1544
1
FAN STATIC PRESSURE (in. w.c.)
0.48
2
FAN INLET PRESSURE (in. w.c.)
0.19
FAN DISCHARGE PRESSURE (in. w.c.)
0.29
MOTOR HP
0.60
MOTOR RPM
1075
MOTOR (VOLTS /FLA/PHASE)
230
3.60
1
239
3.46
1
MOTOR AMPS
2.6
FAN RPM
1075
MOTOR SHEAVE
FAN PULLEY
DRIVE BELTS
DIRECT DRIVE SPEED /SET
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Systems Management & Balancing of MN, Inc.
FAN NO. RTU -2
Fan Test
NOTES: 1. Total air is the summation of airflows at the individual outlets.
2. Tabulated pressures are external to the unit.
Page 3
ROOM
NUMBER
OUTLET
"K"
REQUIRED
PREL
FINAL
TYPE
SIZE"
VEL
CFM
VEL
VEL
CFM
NOTE
130 NW
CD
8
1.0
200
200
158
190
190
SW
CD
8
1.0
200
200
152
184
184
SE
CD
8
1.0
200
200
165
195
195
NE
CD
8
1.0
200
200
158
187
187
132
CD
8
1.0
100
100
201
108
108
123
CD
8
1.0
250
250
216
243
243
131
CD
8
1.0
250
250
234
239
239
128
CD
8
1.0
200
200
273
198
198
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Systems Management & Balancing of MN, Inc. Page 4
RTU -2
Outlet Schedule
NOTES:
MANUFACTURER
TRANE
MODEL, SIZE
YHCO36A
CONDITIONS
REQUIRED
FINAL
NOTE
TOTAL CFM
1200
1421
1,2
FAN STATIC PRESSURE (in. w.c.)
0.44
3
FAN INLET PRESSURE (in. w.c.)
0.05
FAN DISCHARGE PRESSURE (in. w.c.)
0.39
MOTOR HP
0.33
MOTOR RPM
1075
MOTOR (VOLTS/FLA/PHASE)
230
I 2.30
J
I
I 1
239
2.21
1
MOTOR AMPS
1.8
FAN RPM
1075
MOTOR SHEAVE
FAN PULLEY
DRIVE BELTS
DIRECT DRIVE SPEED /SET
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Systems Management & Balancing of MN, Inc.
FAN NO. RTU -3
Fan Test
NOTES: 1. Total air is the summation of airflows at the individual outlets.
2. 1320 CFM required at outlets.
3. Tabulated pressures are external to the unit.
Page 5
ROOM
NUMBER
OUTLET
"K"
REQUIRED
PREL
FINAL
TYPE
SIZE
VEL
CFM
VEL
VEL
CFM
NOTE
136 N
LD
4'
1.0
250
250
272
275
275
S
LD
4'
1.0
250
250
237
252
252
135
LD
4'
1.0
250
250
330
274
274
134
LD
4'
1.0
250
250
269
271
271
133
CD
8"
1.0
220
220
247
240
240
133A
SR
12x8
0.40
250
100
368
272
109
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Systems Management & Balancing of MN, Inc. Page 6
RTU -3
NOTES:
Outlet Schedule
ROOM
NUMBER
OUTLET
"K"
REQUIRED
PREL
FINAL
TYPE
SIZE"
VEL
CFM
VEL
VEL
CFM
NOTE
120 N
CD
8
1.0
220
220
143
143
143
1
S
CD
8
1.0
220
220
119
119
119
1
117
CD
6
1.0
150
150
147
147
147
118
CD
6
1.0
100
100
94
94
94
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Systems Management & Balancing of MN, Inc. Page 7
EXISTING SUPPLY
NOTES: 1. Maximum available.
Outlet Schedule
ROOM
NUMBER
OUTLET
REQUIRED
PREL
FINAL
TYPE
SIZE
"K"
VEL
CFM
VEL
VEL
CFM
NOTE
EF -1
EG
16x12
1.1
409
450
358
358
394
1
EF-1B
EG
16x12
1.1
409
450
333
333
366
1
EF -2
EG
10x10
1.1
91
100
137
137
151
EF -3
EG
12x8
1.1
91
100
63
63
69
1
EF -1
EG
10x10
1.1
91
100
131
131
144
2
Systems Management & Balancing of MN, Inc. Page 8
MISCELLANEOUS BATHROOM EXHAUST
NOTES: 1. Fans have common discharge louver.
2. Two fans on print labeled EF -1.
Outlet Schedule